Plan Review Details - Permit 04050240
Plan Review Stops For Permit 04050240
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-28 Cont ID  
Sent By lsmith Date 2004-05-28 Time 10:25 Rev Time 1.00
Received By lsmith Date 2004-05-28 Time 10:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-20 Cont ID  
Sent By dpalmer Date 2004-05-28 Time 09:36 Rev Time 3.00
Received By lsmith Date 2004-05-20 Time 08:41 Sent To  
Notes
2004-05-20 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT THE FOLLOWING PRODUCT APPROVALS:
 WINDOWS
 DOORS
 GARAGE DOORS
 ROOF SYSTEM
 STRUCTURAL COMPONENTS
 HURRICANE PANELS
  
 2. PLANS MUST BE TAKEN TO PBC AND
 IMPACT FEES PAID.SUBMIT A COPY OF THE
 PAID RCEIPT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERKS OFFICE AND A
 COPY SUBMITED BEFORE A PERMIT CAN BE
 ISSUED.
  
 4. THE FLORIDA ENERGY CODE FORMS MUST BE
 SIGNED BY THE OWNER/AGENT AND AN EXTRA
 COPY OF PAGE ONE SUBMITTED FOR PERMIT.
  
 5. THE VALUE OF THE HOUSE HAS BEEN
 INCREASED PER BLDG. CODE SCHEDULE.
 ADDITIONAL FEES OF $703.67 ARE DUE
 BEFORE A PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-04 Cont ID  
Sent By dpalmer Date 2005-03-04 Time 13:18 Rev Time 0.00
Received By dpalmer Date 2005-03-04 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-28 Cont ID  
Sent By dpalmer Date 2004-05-28 Time 09:36 Rev Time 0.33
Received By dpalmer Date 2004-05-28 Time 09:00 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-27 Time 10:53 Rev Time 0.50
Received By dpalmer Date 2004-05-11 Time 15:12 Sent To M
Notes
2004-05-11 00:00:00********** UNSAT********************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM AND
 PANEL SCHEDULE. BOTH SHOW PANELS AS
 MLO. MCB'S REQ'D. 225.31, ETC
  
 2)NOTE: PLEASE SEE MISSING SD INSIDE AND
 OUTSIDE GUEST BEDRM. PLEASE ALSO MOVE
 SD INTO MASTER BEDRM AREA. NFPA-71 8-1
  
 3)NOTE: PLEASE SEE MISSING RECEPT IN
 GUEST BATH PER 210.52D
  
 4)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C UNIT. 210.63
  
 5)NOTE: PLEASE SEE OUTLET SPACING FOR
 BEDRM #3. 210.52 RECEPT APPEARS TO BE
 IN CORNER BEHIND THE DOOR?
  
 6)NOTE: PLEASE SEE RECEPT SPACING ON
 KITCHEN COUNTERSPACE TO BE PER 210.52C1
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-05-27 Time 10:53 Rev Time 0.00
Received By csiegber Date 2004-05-27 Time 10:53 Sent To E
Notes
2004-05-27 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By mmclean Date 2004-05-07 Time 11:49 Rev Time 0.00
Received By lsmith Date 2004-05-07 Time 10:35 Sent To  
Notes
2004-05-10 00:00:00TO SFD RACK/E
2004-05-07 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-17 Cont ID  
Sent By dpalmer Date 2004-05-11 Time 15:12 Rev Time 0.50
Received By hmoser Date 2004-05-17 Time 17:55 Sent To P
Notes
2004-05-17 00:00:00PASS PRIVISO
 NEED 10IN.RETURN AIR IN LIBRARY.
 NEED EXHAUST EAN IN MASTER BATH.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-19 Cont ID  
Sent By hmoser Date 2004-05-17 Time 17:56 Rev Time 0.50
Received By kstevens Date 2004-05-19 Time 18:31 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-07 Cont ID  
Sent By mmclean Date 2004-05-07 Time 11:49 Rev Time 0.00
Received By mmclean Date 2004-05-07 Time 11:49 Sent To I
Notes
***NONE***