Plan Review Details - Permit 04050231
Plan Review Stops For Permit 04050231
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-07 Cont ID  
Sent By lsmith Date 2004-06-07 Time 09:08 Rev Time 0.50
Received By lsmith Date 2004-06-07 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-20 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 08:22 Rev Time 0.50
Received By lsmith Date 2004-05-20 Time 09:23 Sent To  
Notes
2004-05-20 00:00:00PROVISO:
  
 FILE A NOTICE OF COMMENCEMENT WITH THE
 COUNTY CLERKS OFFICE AND SUBMIT A COPY
 BEFORE A PERMIT IS ISSUED.
  
 SEE ELECTRICAL NOTES FOR TITLE BLOCK
 INFORMATION MISSING.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-07 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 08:18 Rev Time 0.33
Received By dpalmer Date 2004-06-07 Time 08:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-08 Cont ID  
Sent By csiegber Date 2004-06-01 Time 11:17 Rev Time 0.25
Received By dpalmer Date 2004-05-08 Time 07:32 Sent To  
Notes
2004-05-08 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 FS 481.219. REQ'S ARCH LICENSE # TO BE
 PRINTED IN TITLE BLOCK.
 PLANS ARE ALSO REQ'D TO SHOW CORRECT
 ADDRESS AND UNIT.
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-05-07 Cont ID  
Sent By mcarsill Date 2004-05-07 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2004-05-07 Time 12:31 Sent To  
Notes
2004-05-07 00:00:001) NEW SOFFITS CANNOT INTERFERE WITH
 ANY COVERAGE PROVIDED BY THE FIRE
 SPRINKLER HEADS CONTAINED WITHIN
 UNIT. IF EXISTING FIRE SPRINKLER HEADS
 WILL BE AFFECTED BY THE NEW SOFFITS,
 THEN THE FIRE SPRINKLER HEADS ARE TO
 BE RELOCATED. A SEPARATE PLAN AND
 PERMIT REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-01 Cont ID  
Sent By csiegber Date 2004-06-01 Time 11:17 Rev Time 0.00
Received By csiegber Date 2004-06-01 Time 11:17 Sent To E
Notes
2004-06-01 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-06-01 Time 11:17 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 10:12 Sent To  
Notes
2004-05-07 00:00:00TO COMM BD#26