Plan Review Details - Permit 04050206
Plan Review Stops For Permit 04050206
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-27 Cont ID  
Sent By rmcdouga Date 2004-10-27 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2004-10-27 Time 15:49 Sent To  
Notes
2004-10-27 00:00:00REVISED FRENCH DOORS, MULLIONS, CASEMENT
 AND FIXED WINDOWS TO IMPACT RESISTANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-09-17 Cont ID  
Sent By csiegber Date 2004-10-25 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2004-09-17 Time 10:57 Sent To  
Notes
2004-09-17 00:00:00REVISION TO BEAMS ON SHEETS A5 AND A6
 ARE OKRM

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:23 Rev Time 0.00
Received By rmcdouga Date 2004-08-05 Time 15:26 Sent To  
Notes
2004-08-05 00:00:00BUILDING PROVISO
  
 1) SUBMIT STATE OR LOCAL PRODUCT
 APPROVAL FOR THE ARCHED TOP FIBERGLASS
 FRONT DOOR FOR APPROVAL BEFORE IT IS
 INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-07 Cont ID  
Sent By mmclean Date 2004-08-04 Time 15:20 Rev Time 3.00
Received By rmcdouga Date 2004-06-07 Time 14:15 Sent To  
Notes
2004-06-07 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT AN ADDITIONAL COPY OF THE
 SURVEY.
  
 4) SOME OF THE SET BACK DIMENSIONS ON
 THE SITE PLAN ON A1 DO NOT CORRESPOND
 WITH THE SURVEY. PLEASE CORRECT.
  
 5) SPECIFY THE REQUIRED SOIL BEARING
 CAPACITY FOR THE STRUCTURE ON THE PLANS.
  
 6) THE SOIL REPORT REQUIRES FOOTINGS TO
 BE NOT LESS THAN 18" BELOW ADJACENT
 GRADE. SOME OF THE FOOTINGS WILL NOT
 MEET THIS REQUIREMENT. PLEASE CORRECT.
  
 7) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE DOORS WITH A 29" CLEAR
 OPENING. SEE FBC CHAPTER 11.
  
 8) THE WINDOWS IN THE BATHROOMS THAT ARE
 WITHIN 3 FEET HORIZONTALLY OF A TUB OR
 SHOWER ARE REQUIRED TO HAVE SAFETY
 GLAZING. SEE FBC 2405.2.
  
 9) THE ID MARK FOR THE FRONT DOOR IS
 INCORRECT ON SHEET A3.
  
 10) PROVIDE A DETAIL/SECTION OF THE
 COLUMNS AT THE BALCONY TO WHICH THE
 GUARDRAILS ATTACH.
  
 11) SPECIFY THE LOCATION OF THE CONTIN-
 OUS 2" SOFFIT SCREEN VENTS ON THE WALL
 SECTIONS.
  
 12) THE STUDY IS REQUIRED TO HAVE EGRESS
 WINDOWS AS REQUIRED BY FBC 1005.4 OR
 INDICATE ON PLAN THAT THIS ROOM NOT TO
 BE USED FOR SLEEPING PURPOSES.
  
 13) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING:
 - CUSTOM FRONT DOOR
 - STRUCTURAL MULLIONS
 - FRENCH DOOR WITH SIDELITES (MASTER BR)
 - TRUSS CONNECTORS
  
 14) REVISE THE DOOR SCHEDULE TO REFLECT
 THE FIBERGLASS DOOR PRODUCT APPROVAL
 THAT WAS SUBMITTED.
  
 15) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE MOUNT TYPE AND FASTENERS THAT WILL
 BE USED BY HIGHLIGHTING OR CIRCLING THE
 APPROPRIATE ITEMS ON THE NOA.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2005-05-26 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-05-19 Cont ID  
Sent By dpalmer Date 2005-05-19 Time 07:03 Rev Time 0.33
Received By dpalmer Date 2005-05-19 Time 07:00 Sent To  
Notes
2005-05-19 00:00:00********** UNSAT ************
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #3 NO, PLEASE CORRELATE
 RISER WITH PANEL SCHEDULES SUBMITTED.
 PLEASE SEE PANEL SCHEDULE FOR M/M COMBO
 NOW SHOWS M/M AS 125A'SRISER SHOWS AS
 400A'S. A 400A MCB WOULD BE REQUIRED.
 PLEASE SEE M/M COMBO SCHEDULE STILL DOES
 NOT INCLUDE THE 2-200A BRKRS FOR SUB
 PANELS AS SHOWN ON RISER.
 PLEASE SEE PANEL "B", THIS PANEL NOTES,
 FEED THRU LUGS TO "PANEL B"? PLEASE
 CLARIFY HOW THIS IS POSSIBLE IF RISER
 SHOWS (2) 200A BRKRS TO FEED EACH SUB
 PANEL?
 PLEASE SEE SEC'S ARE STILL BEING SHOWN
 AS 2/0'S. PLEASE SEE MIN SIZING PER
 310.15B6 FOR A SF RESIDENCE.
 PLEASE SEE RISER ALSO INDICATES "FEED
 THRU" LUGS??? FOR ??
  
 2)NOTE: PLEASE SEE REVISED CALCULATIONS
 FOR EACH PANEL STILL NOT SUBMITTED.
 PLEASE ALSO SEE REVISED CALCULATIONS FOR
 SERVICE.? PLEASE SEE A/C LOAD NOTES 65%,
 HOWEVER 65% OF 20KW AAS SHOWN DOES NOT
 COME OUT TO 16250KW'S? IS THERE
 ADDITIONAL A/C LOAD?
 PLEASE SEE 220.31
  
 PLEASE SEE OTHER NOTES WERE ADDRESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-05-11 Cont ID  
Sent By dpalmer Date 2005-05-11 Time 10:46 Rev Time 1.00
Received By dpalmer Date 2005-05-11 Time 10:42 Sent To  
Notes
2005-05-11 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR 10KW HEATSTRIPS.
 125% MIN.
  
 2)NOTE: PLEASE SEE PLANS MISSING RECEPT
 FOR WHIRLPOOL TUB.
 PLEASE ALSO SEE WP IS SHOWN AS 1-POLE
 10A? BRKR W/2KW LOAD?
 240.24,310.16 ETC.
  
 3)NOTE: PLEASE CORRELATE PLANS , RISER
 DIAGRAM AND PANEL SCHEDULES.
 PLEASE SEE RISER SHOWS 200A DISC W/ 200A
 FUSES ON A 400A METER/MAIN COMBO?
 PLEASE SEE PLANS SHOW PANELS A AND B
 INSIDE GARAGE AND A METER AND A MAIN
 OUTSIDE?
 PLEASE SEE METER/MAIN COMBO SHOWS ONLY
 TWO BRKRS FOR A/C CU AND POOL EQUIPMENT.
 PLEASE SEE POOL EQUIPMENT IS ACTUALLY A
 POOL PANEL. PLEASE SHOW POOL PANEL ON
 PLANS, RISER AND SUBMIT PANEL SCHEDULE
 FOR POOL PANEL.
  
 *** PLEASE NOTE: METER/MAIN COMBO SHALL
 NOT HAVE MORE THAN 6 MIANS, OR 6 SPACES
 FOR MAINS. 230.70,230.71 ETC.***
  
 4)NOTE: PLEASE SEE NO REVISED LOAD
 CALCULATIONS WERE SUBMITTED EXCEPT FOR
 PANEL "C"? PLEASE CORRELATE LOAD
 CALCAULTIONS WITH PANEL SCHEDULES.
 220.31, 215.5
  
 PLEASE SEE TWO ITEMS REDLINED ON
 ORIGINAL PLANS NOT CORRECTED.
  
 1)NOTE: PLEASE SEE LOGGIA AREA IN REAR
 OF HOUSE WILL REQUIRE A MIN OF ONE
 FIXTURE FOR MEANS OF EGRESS LIGHTING.
 210.70, LS 101 5-8.
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL SPACE IN STUDIO. 210.52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By jleech Date 2004-07-27 Time 19:32 Rev Time 0.40
Received By dpalmer Date 2004-07-12 Time 18:43 Sent To P
Notes
2004-07-12 00:00:00REDLINED/ NO NEED FOR REVISION OR CORREC
 -TION.
 RECEPT 210.52
 LT FIXTURE OF SOME TYPE REQUIRED FOR
 MEANS OF EGRESS TO REAR LOGGIA. 210.70
 LS101 5-8

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-07-09 Time 16:32 Rev Time 0.75
Received By dpalmer Date 2004-05-12 Time 07:42 Sent To M
Notes
2004-05-12 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004, FS
 481.219. PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCKS.
 PLEASE ALSO PROVIDETHE FOLLOWING
 FOR VERIFICATION OF "LEGAL" SIGNATURE.
 COPY OF LICENSE, OR SIGNED AND SEALED/
 NOTORIZED LETTER.EITHER WILL BE PLACED
 IN FILE FOOR FUTURE VERIFICATION.
 PLEASE SEE FS 481.221, A "SIGNATURE"
 IS REQ'D CONTAINING A MIN OF FIRST AND
 LAST NAME. DBPR/ FBPE, INITIALS ARE NOT
 PERMITTED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2
 3' FROM BATHS/KITCHENS. SD'S W/IN 20'
 OF COOKING APPLIANCES ETC.
  
 4) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 ONE OD THE BEDRMS
  
 5)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 6)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE. 12"
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 17:57 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 17:57 Sent To E
Notes
2005-05-24 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 13:34 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 13:34 Sent To E
Notes
2005-05-18 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 11:39 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 11:39 Sent To E
Notes
2005-05-09 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 15:19 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 15:19 Sent To M
Notes
2005-01-19 00:00:00TO "M/AC" BOX/REV.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 14:00 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 14:00 Sent To B
Notes
2004-10-25 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 15:23 Sent To B
Notes
2004-09-15 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 16:32 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 16:32 Sent To E
Notes
2004-07-09 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-07 Cont ID  
Sent By mmclean Date 2004-05-07 Time 11:57 Rev Time 0.00
Received By rmcdouga Date 2004-05-07 Time 10:04 Sent To  
Notes
2004-05-10 00:00:00TO SFD RACK/E
2004-05-07 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-01-27 Cont ID  
Sent By pkrauss Date 2005-01-27 Time 06:46 Rev Time 0.35
Received By pkrauss Date 2005-01-27 Time 06:37 Sent To  
Notes
2005-01-27 00:00:00DENIED:
 1.ONLY ONE SET OF PLANS SUBMITTED FOR
 APPROVAL.TWO SETS REQUIRED PER 2001
 FBC 104.2.1.PLEASE PROVIDE ADDITIONAL
 SET.
  
 2.PLEASE CLARIFY RETURN AIR FROM THE
 LAUNDRY AREA.THIS IS NOT A HABITABLE
 ROOM AND DOES NOT REQUIRE A RETURN.
  
 CALLED CONTRACTOR 1-27-05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By pkrauss Date 2004-08-02 Time 14:05 Rev Time 0.35
Received By pkrauss Date 2004-08-02 Time 13:17 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By jleech Date 2004-07-27 Time 19:32 Rev Time 0.40
Received By pkrauss Date 2004-05-14 Time 09:59 Sent To P
Notes
2004-05-14 00:00:00DENIED:
 1. RETURN AIR REQUIRED FROM THE MASTER
 BEDROOM AREA.
  
 2.RETURN AIR REQURIED FROM THE STUDY
 AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-27 Cont ID  
Sent By jleech Date 2004-07-27 Time 19:31 Rev Time 0.33
Received By jleech Date 2004-07-27 Time 19:31 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By dpalmer Date 2004-07-12 Time 18:56 Rev Time 0.50
Received By kstevens Date 2004-05-19 Time 17:53 Sent To B
Notes
2004-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT M-2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) WASH MACHINE REQUIRES A STANDPIPE &
 A CLEANOUT. CLEANOUT SHALL BE INSTALLED
 4' ABOVE THE FLOOR FOR ACCESS. SECTIONS
 1002.1 & 708.10
 B) THE SIZE OF THE DRAINAGE PIPING
 SHALL NOT BE REDUCED IN SIZE IN THE DIR-
 ECTION OF FLOW. WASH MACHINE SHOWS 4"
 PIPE THEN REDUCING TO 2" PIPE. SECTION
 704.2.
 C) TUB AND SHOWER SHALL BE CONNECTED TO
 SANITARY BLDG DRAIN UNDERGROUND NOT UP
 ON THE STACK. SEE RED LINE CORRECTION.
 SECTION 102.4
 2) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE PER DPBR.
 FAC 61G1-16;003 & FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-08-04 Cont ID  
Sent By mmclean Date 2004-08-03 Time 16:48 Rev Time 0.00
Received By mmclean Date 2004-08-04 Time 15:20 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-07 Cont ID  
Sent By mmclean Date 2004-05-07 Time 11:57 Rev Time 0.00
Received By mmclean Date 2004-05-07 Time 11:57 Sent To I
Notes
***NONE***