Plan Review Details - Permit 04050122
Plan Review Stops For Permit 04050122
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-26 Cont ID  
Sent By dpalmer Date 2004-05-26 Time 13:18 Rev Time 0.50
Received By dpalmer Date 2004-05-26 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-08 Cont ID  
Sent By alange Date 2004-05-24 Time 14:44 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 07:19 Sent To P
Notes
2004-05-08 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE 250.6, 250.24.
 EQUIPMENT GROUNDING CONDUCTORS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISC.
  
  
 2)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 MUST CONTAIN PRINTED NAME AND SIGNED
 BY THE PERSON RESPONSIBLE FOR PLAN/ DRAW
 -ING.
  
  
 PLANS SENT TO PLUMB FOR REVIEW
 THE VALUE WAS SHOWN @ $0. ADDED .
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-24 Time 14:44 Rev Time 0.00
Received By alange Date 2004-05-24 Time 14:44 Sent To E
Notes
2004-05-24 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 09:15 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 09:15 Sent To E
Notes
***NONE***