Plan Review Details - Permit 04050072
Plan Review Stops For Permit 04050072
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-08-19 Cont ID  
Sent By rmcdouga Date 2005-08-19 Time 14:37 Rev Time 0.00
Received By rmcdouga Date 2005-08-19 Time 14:37 Sent To  
Notes
2005-08-19 00:00:00REVISED ENERGY CALCS. FOR R-VALUE OF
 INSULATION AT EXTERIOR MASONRY WALLS
 FROM R-5.0 TO R-4.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2005-02-10 Cont ID  
Sent By rmcdouga Date 2005-02-10 Time 07:14 Rev Time 0.00
Received By rmcdouga Date 2005-02-10 Time 07:14 Sent To  
Notes
2005-02-10 00:00:00REVISION TO CHANGE WOOD HEADERS AT
 PORCHES TO POURED LINTELS IS DENIED.
 REVISIONS TO MASTERED PLANS ARE NOT
 ALLOWED AFTER SOME MODELS ARE BUILT TO
 ORIGINAL MASTER PLAN. WHICH IS THE CASE
 PER TELEPHONE CONVERSATION WITH THE
 CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-11-02 Cont ID  
Sent By rmcdouga Date 2004-11-02 Time 15:59 Rev Time 2.00
Received By rmcdouga Date 2004-11-02 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2004-10-13 Time 14:15 Sent To  
Notes
2004-10-13 00:00:00DENIED
  
 1) THE TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED BY THE ARCHITECT
 THEY ARE TO BE STAMPED AND SIGNED BY HIM
 AS BEING REVIEWED AND ACCEPTED.
  
 2) SHEET A2.01 IS MISSING FROM ONE OF
 THE SETS OF PLANS.
  
 3) THE ROOF FRAMING PLAN ON SHEET S2.03
 DOES NOT SPECIFY THE CONNECTORS FOR THE
 FOUR BEARING POINT FOR TRUSSES A3 AND
 A4. SEE TRUSS DRAWINGS AND LAYOUT.
 PLEASE CORRECT.
  
 4) THE STORM PANEL KEY AND INSTALLATION
 PLAN SPECIFIES PANELS FOR THE EXTERIOR
 DOOR AT THE KITCHEN. THE PLANS SPECIFY
 A METAL DOOR WITHOUT GLAZING AT THIS
 LOCATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-12 Time 16:42 Rev Time 2.00
Received By rmcdouga Date 2004-10-07 Time 17:23 Sent To  
Notes
2004-10-07 00:00:00DENIED
  
 1) THE VALUES LISTED IN THE TABLE IN
 DETAIL 5 ON SHEET S2.03 FOR THE USP
 THD28-2 CONNECTOR ARE INCORRECT. SEE
 2004 USP CATALOG.
  
 2) THE STORM PANEL SCHEDULE INDICATES
 STORM PANELS FOR THE FRONT DOOR. THIS
 CONFLICTS WITH THE PLANS AND THE PRODUCT
 APPROVAL WHICH SPECIFY AN IMPACT RATED
 DOOR. PLEASE CLARIFY.
  
 3) THE TRUSS LAYOUT AND DRAWINGS HAVE
 NOT BEEN REVIEWED AND APPROVED BY THE
 ARCHITECT. THEY ARE TO BE STAMPED AND
 SIGNED BY HIM AS BEING REVIEWED AND
 ACCEPTED.
  
 4) THE ROOF FRAMING PLAN ON S2.03 IS NOT
 CLEAR ON THE LOCATION AND UPLIFTS FOR
 THE A3,A4 AND A5 TRUSSES WHICH HAVE
 FOUR BEARING POINTS. PLEASE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-17 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 06:44 Rev Time 2.00
Received By rmcdouga Date 2004-08-16 Time 14:40 Sent To  
Notes
2004-08-16 00:00:00DENIED
  
 1) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE WORST CASE FOR MASTERED MODELS.
 THE A/C AREA ON THE PLANS AND ON THE
 ENERGY CALC. FORMS DO NOT MATCH.
  
 2) DETAIL #5 ON S2.03 IS INCORRECTLY
 NUMBERED AS 201. THE THD28-2 DID NOT GET
 CHANGED TO THE THDH28-2, WHICH HAS THE
 UPLIFT OF 3185# THAT IS SPECIFIED.
  
 3) SPECIFY ON SHEET S2.01 THAT THE
 FINISH FLOOR OF THE MONOLITHIC SLAB IS
 REQUIRED TO BE A MINIMUM OF 4" ABOVE
 FINAL GRADE AT HABITABLE AREAS. SEE CITY
 OF WPB AMENDMENTS TO FBC 1804.1.7.
  
 4) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE INSTALLATION TYPE AND FASTENERS THAT
 WILL BE USED BY CIRCLING OR HIGHLIGHTING
 THE ITEMS ON THE INSTALLATION DRAWINGS.
  
 5) THE PRODUCT APPROVAL FOR THE PGT SH
 4000 WINDOWS DOES NOT MATCH THE NOA
 NUMBERS ON THE MIAMI-DADE NOA THAT WAS
 SUBMITTED. SUBMIT THE CORRECT NOA. ONLY
 ONE COPY WAS SUBMITTED. TWO COPIES ARE
 REQUIRED.
  
 6) THE PRODUCT APPROVAL FOR THE PGT
 FRENCH DOOR DOES NOT MATCH THE NOA
 NUMBERS ON THE MIAMI-DADE NOA THAT WAS
 SUBMITTED. SUBMIT THE CORRECT NOA.
  
 7) THE TRUSS LAYOUT IS TO BE REVIEWED BY
 THE ARCHITECT OF RECORD AND STAMPED AS
 APPROVED BY HIM.
  
 8) THE TRUSS LAYOUT AND TRUSS DRAWINGS
 ARE REQUIRED TO HAVE THE ORIGINAL WET
 SIGNATURE OF THE TRUSS ENGINEER. SEE
 FAC 61G15-23.002.
  
 9) TRUSSES A3, A4, AND A5 HAVE FOUR
 BEARING POINTS INDICATED ON THE TRUSS
 DRAWINGS. THE ROOF FRAMING PLANS ONLY
 SPECIFY CONNECTORS FOR THREE BEARING
 POINTS. PLEASE CORRECT.
  
 10) THE TRUSS LAYOUT NOTES THAT THE
 BEAMS AT THE FRONT AND REAR PORCHES ARE
 BY BUILDER. SHEET S2.03 OF THE PLANS
 SPECIFY WOOD GIRDER TRUSSES. PLEASE
 CORRECT. IF BEAMS ARE BY BUILDER PROVIDE
 DETAILS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-06-02 Cont ID  
Sent By kstevens Date 2004-05-19 Time 15:41 Rev Time 3.00
Received By rmcdouga Date 2004-06-02 Time 13:02 Sent To  
Notes
2004-06-02 00:00:00DENIED
  
 1) SUBMIT TRUSS DRAWINGS AND LAYOUT THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.
  
 2) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE WORST CASE FOR MODELS. THE FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER/AGENT. THE CONDITIONED FLOOR AREA
 ON THE FORM AND THE PLANS SHOULD BE THE
 SAME.
  
 3) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. SEE 2001 FBC TABLE 1604.1.
  
 4) THE MONOLITHIC FOOTING IN THE WALL
 SECTION ON S 2.01 DOES NOT CORRESPOND
 WITH THE F1 FOOTING IN THE SCHEDULE.
 PLEASE CORRECT.
  
 5) THE ISOLATED PAD DETAIL ON S 2.01 IS
 INCORRECTLY LABELED AS 7. IT SHOULD BE
 LABELED 4.
  
 6) SPECIFY THE MATERIAL USED FOR THE
 CEILINGS (DIAPHRAGM) OF THE COVERED
 PORCHES.
  
 7) SUBMIT STATE PRODUCT APPROVALS FOR
 THE USP CONNECTORS.(HLPTA75, TA16, RT16F
 RT22T, THD28-2)
  
 8) THE USP THD28-2 HAS A MAXIMUM UPLIFT
 OF 2390# AT 133% PER 2004 USP CATALOG.
 PLEASE REVISE DETAIL 5 ON S 2.03.
 (THE THDH28-2 HAS AN UPLIFT OF 3185#.)
  
 9) THE EXTERIOR WALLS AT THE REAR PORCH
 ARE NOT SHOWN ON THE ROOF FRAMING PLAN
 ON S2.03.
  
 10) ON S3.01 THE WALL SHEATHING IS
 SPECIFIED AS 15/32" IN ONE PLACE AND
 5/8" IN ANOTHER. PLEASE CORRECT.
  
 11) THE ROOF SHEATHING IS INCORRECTLY
 SPECIFIED AS 15/32" ON SHEET S3.01. CITY
 OF WPB AMENDMENTS TO FBC TABLE 2309.3A
 REQUIRES MINIMUM 19/32" SHEATHING.
  
 12) CITY AMENDMENTS TO FBC TABLE 2306.1
 REQUIRES ROOF SHEATHING TO BE NAILED AT
 4"OC ON THE EDGES AND 6"OC INTERMEDIATE
 IN ZONE 3 WHICH INCLUDE THE CORNERS OF
 HIP ROOFS. PLEASE REVISE NOTES ON S3.01.
  
 13) PLEASE UPDATE THE ACI EDITIONS THAT
 ARE SPECIFIED ON S3.01 TO 2002 EDITIONS
 PER FBC CHAPTER 35. SEE NOTES ON THE
 PLAN.
  
 14) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE INSTALLATION TYPE AND FASTENERS THAT
 WILL BE USED BY CIRCLING OR HIGHLIGHTING
 APPROPRIATE ITEMS ON THE INSTALLATION
 DRAWINGS.
  
 15) SUBMIT STATE PRODUCT APPROVALS FOR
 THE FOLLOWING ITEMS:
 - SINGLE OUTSWING DOOR AT THE KITCHEN
 - DOUBLE OUTSWING DOORS AT STORAGE
 - ALUMINUM SOFFIT
 - TRUSS CONNECTORS
  
 16) ONE OF THE PRODUCT APPROVALS FOR THE
 STORM PANELS IS MISSING THE INSTALLATION
 DRAWINGS.
  
 THE FOLLOWING ITEMS WILL BE REQUIRED TO
 BE SUBMITTED FOR EACH PERMIT APPLICATION
 UNDER THE MASTER.
 - NOTICE OF COMMENCEMENT
 - PAID RECEIPT FOR COUNTY IMPACT FEES.
 (PLANS MUST BE STAMPED BY COUNTY)
 - A SURVEY
 - A SUBSURFACE SOIL REPORT(FBC 1804.2.2)
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-05 Cont ID  
Sent By dpalmer Date 2004-10-05 Time 06:44 Rev Time 0.25
Received By dpalmer Date 2004-10-05 Time 06:44 Sent To B
Notes
2004-10-05 00:00:00MASTER MODEL "A"

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-10 Cont ID  
Sent By csiegber Date 2004-09-24 Time 09:22 Rev Time 0.33
Received By dpalmer Date 2004-08-10 Time 15:37 Sent To P
Notes
2004-08-10 00:00:00***UNSAT ***
  
 1)NOTE: PLEASE SEE LOAD SHOWN FOR COND
 UNIT AS 10KW, IF COOLING LOAD IS LARGER
 THAN HEAT, THEN COOLING LAOD IS FIGURED
 IN LAOD CALCS. PLEASE VERIFY, APPEARS
 TO BE A MISPRINT FOR A 2.5 TON UNIT.
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 SEE NEW RECEPT ADDED FOR PREVIOUS NOTES.
  
 3)NOTE: PLEASE SEE 210.52C3 AND C5 FOR
 PENINSULAR/WALL RECEPT SPACING. PLEASE
 VERIFY IF RECEPT SHOWN IS FOR PENINSULAR
 OR WALL. ?
 PLEASE ALSO SEE 210.52 FOR 6' REQ'MENT.
  
 4)NOTE: PLEASE SEE GEN NOTES#3 LAST
 LINE MENTIONS RECEPTS TO BE ARC-FAULT
 PROTECTED.
 PLEASE SEE NEW NOTE ADDED.
  
 PLEASE SEE PLANS ARE ONLY IN FOR PLAN
 REVIEW. THEY ARE ALSO FOR MASTERS WHICH
 REQUIRES ALL TO BE 100% AND NO REDLINES
 CAN BE DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-10 Cont ID  
Sent By csiegber Date 2004-08-03 Time 14:02 Rev Time 0.50
Received By dpalmer Date 2004-05-10 Time 07:54 Sent To M
Notes
2004-05-10 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 PANEL AS MCB AND YET PLANS/RISER SHOWS
 A MAIN DISCONNECT?
 A MCB IS PERMITTED BUT NOT REQ'D. IF
 SHOWN ON PLANS THEN IT MUST BE INSTALLED
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110, SIZE PER 250.122.
  
 3)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. 2', 6',12'
  
 4)NOTE: PLEASE SEE OCP/AWG SHOWN FOR
 2.5TON A/C COND UNIT. THIS SEEMS TO BE
 TOO HIGH FOR OCP.
  
 5)NOTE: PLEASE SHOW MAIN DISC NEXT TO
 METER ON PLANS.
  
 6)NOTE: DISC FOR A/CTO MEET 110.26,
 SHOWN BEHIND UNIT.
  
 7)NOTE: PLEASE IDENTIFY ARC FAULT PER
 2002 NEC. 210.12B WHICH REQ'S ALL OUTLET
 S. SD'S, RECEPTS, LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 17:27 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 17:27 Sent To B
Notes
2005-08-18 00:00:00TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 15:41 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 15:41 Sent To P
Notes
2005-01-14 00:00:00TO "P" BOX/REV.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:53 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 16:53 Sent To B
Notes
2004-10-20 00:00:00TO RM DESK/

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-12 Cont ID  
Sent By csiegber Date 2004-10-12 Time 16:42 Rev Time 0.00
Received By csiegber Date 2004-10-12 Time 16:42 Sent To B
Notes
2004-10-12 00:00:00TO RM DESK/JOURNAL ENTRY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-24 Cont ID  
Sent By csiegber Date 2004-09-24 Time 09:22 Rev Time 0.00
Received By csiegber Date 2004-09-24 Time 09:22 Sent To E
Notes
2004-09-24 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 14:02 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 14:02 Sent To E
Notes
2004-08-03 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:08 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 14:20 Sent To E
Notes
2004-05-04 00:00:00TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-13 Cont ID  
Sent By rmcdouga Date 2004-10-13 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2004-10-13 Time 11:03 Sent To  
Notes
2004-10-13 00:00:00OK PER P.KRAUSS ON 8/12/04

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By kstevens Date 2004-08-12 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2005-02-10 Time 07:14 Sent To P
Notes
2004-05-14 00:00:00DENIED:
 1.RETURN AIR TO THE MASTER BEDROOM IS
 NOT SIZED PROPERLY.ALL SUPPLY AIR TO
 THE MASTER SUITE IS TO BE INCLUDED FOR
 THE "TOTAL" OF SUPPLY AIR.SUPPLY AIR
 7" TO THE BEDROOM 6" TO THE BEDROOM FOR
 A TOTAL OF 66 SQ INCHES MULTIPY BY 1.5
 EQUALS A TOTAL OF 99 SQ INCHES THEREFOR
 RETURN AIR SHOULD BE A MINIMUM OF 12".
  
 2.SUPPLY AIR DUCT TO BEDROOM #2 IS
 NOT SIZED.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS PER
 402.2 OR 403.3 OF THE 2001 FBC(M).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-05 Cont ID  
Sent By pschmitz Date 2005-02-05 Time 08:20 Rev Time 0.00
Received By pschmitz Date 2005-02-05 Time 08:19 Sent To B
Notes
2005-02-05 00:00:00WATER HEATER LOCATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-08-12 Cont ID  
Sent By kstevens Date 2004-08-12 Time 10:49 Rev Time 0.33
Received By kstevens Date 2004-08-12 Time 10:49 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By dpalmer Date 2004-08-10 Time 15:37 Rev Time 0.50
Received By kstevens Date 2004-05-19 Time 15:40 Sent To B
Notes
2004-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 2.01 SANITARY RISER DIAGRAM. THE
 TRAPS FOR THE TUB ARE "S" TRAPS AS SHOWN
 AND ARE NOT ALLOWED PER SECTION 1002.3
 - ANY PORTION OF THE DRAINAGE SYSTEM IN-
 STALLED UNDERGROUND SHALL NOT BE LESS
 THAN 2". SECTION 710.3 - WASH MACHINE
 DRAIN REQUIRES A TRAP, A STANDPIPE, AND
 A CLEANOUT. THE CLEANOUT SHALL BE MIN.
 4' ABOVE THE FLOOR FOR ACCESS. SEE SECT-
 IONS 1002.1, 802.4, & 708.10.
 2) 2" SHOWN TO WATER CLOSETS. SUBMIT
 MANUF. SPECIFICATION SHEETS INDICATING
 FIXTURE OUTLET SIZE. SEE FOOTNOTE D FOR
 TABLE 709.1
 3) SEE RED LINE CORRECTIONS ON SHEET
 P2.01.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***