Plan Review Details - Permit 04050060
Plan Review Stops For Permit 04050060
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 13:24 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 13:24 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-13 Cont ID  
Sent By csiegber Date 2004-05-04 Time 13:24 Rev Time 0.35
Received By pkrauss Date 2004-05-13 Time 12:29 Sent To  
Notes
2004-05-13 00:00:00PROVISO:
 PLAN INDICATES 2 OF THE BEDROOMS WITH
 THE SUPPLY AIR AS 200 CFM, THE RETURN
 AIR GRILLES SHALL BE NO LESS THAN 100
 SQ INCHES OF GRILLE AREA (12" X 8" = 96
 SQ INCHES).PLEASE REVISE PLAN
 ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.