Plan Review Details - Permit 04042035
Plan Review Stops For Permit 04042035
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-24 Cont ID  
Sent By rbrown Date 2004-06-24 Time 14:42 Rev Time 0.00
Received By rbrown Date 2004-06-24 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-24 Cont ID  
Sent By rbrown Date 2004-05-24 Time 14:45 Rev Time 0.00
Received By rbrown Date 2004-05-24 Time 14:44 Sent To  
Notes
2004-05-24 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 704.3.1 & 1004.1.4(2)SHEET A-1,
 FLOOR PLAN.THE NEW SECTIONS OF TENANT
 WALL AT CORRIDOR NORTH AND CORRIDOR
 EAST SHALL BE ONE-HOUR FIRE-RATED.
 AMEND THE PLAN.
  
 3) FBC 704.3.1 & 1004.1.4(2)SHEET A-2,
 DETAIL 6.WHAT IS THE U.L. LISTING
 REFERENCE FOR THE HORIZONTAL SHAFT WALL?
 ANNOTATE THE PLANS.
  
 4) FBC TABLE 705.1.2SHEET A-1, DOOR
 SCHEDULE.DOOR 611 SHALL HAVE A FIRE
 RESISTANCE RATING OF 20MINUTES.AMEND
 THE SCHEDULE.
  
 5) FBC 11-4.24SHEET A-1, LOUNGE SINK
 DEPTH AND KNEE CLEARANCE.IT IS NOTED
 THAT DETAIL 3 SHOWS 'NO BASE' FOR THE
 UNDER-SINK CABINET.THE SINK SHALL BE A
 MAXIMUM OF 6-1/2" DEEP AND THE KNEE
 CLEARANCE UNDER THE SINK SHALL BE AT
 LEAST 27" HIGH, 30" WIDE AND 19" DEEP.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 6) FBC 2405.2SHEET A-1. THE GLAZING
 SHOWN IN THE ELEVATIONAL VIEW OF DOOR
 TYPE C IS NOT REFERENCED IN THE DOOR
 SCHEDULE, FOR DOOR #603.THE GLAZING
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 7) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-08-09 Cont ID  
Sent By btrobaug Date 2004-08-09 Time 09:46 Rev Time 0.50
Received By btrobaug Date 2004-08-09 Time 09:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-07-08 Cont ID  
Sent By csiegber Date 2004-08-03 Time 16:33 Rev Time 0.33
Received By dpalmer Date 2004-07-08 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-15 Cont ID  
Sent By dpalmer Date 2004-06-15 Time 17:26 Rev Time 0.33
Received By dpalmer Date 2004-06-15 Time 17:26 Sent To  
Notes
2004-06-15 00:00:00******* UNSAT ********
  
 NEW COMMENT:
  
 1)NOTE: PLEASE SEE PLANS/TITLE BLOCK
 CONTAIN CERTIFICATE OF AUTHORIZATION #
 FOR ANOTHER FIRM. THIS NEEDS TO CORRE-
 -LATE WITH STATE CA #.
 PLEASE SEE COPY OF DBPR WEB SITE SHOWING
 # TO DIFFERENT FIRM.
 (MISPRINT OF OLD #?)
  
 THIS IS FOR ALL P
  
 ELEC OK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-04 Cont ID  
Sent By dpalmer Date 2004-05-04 Time 18:37 Rev Time 0.33
Received By dpalmer Date 2004-05-04 Time 18:37 Sent To  
Notes
2004-05-04 00:00:00**********UNSAT *****************
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42,210.19A,210.20A ETC
  
 2)NOTE: PLEASE 250.30 FOR GROUNDING
 OF TRANSFORMER. PLEASE SHOW ATTACHMENT(S
  
 3)NOTE: PLEASE CLARIFY ELECTRICAL ROOM
 SHOWS ELEVATED BUS DUCT WITH DISC AT THE
 SAME LOCATION. PLEASE SEE RISER DIAGRAM,
 INDICATES DISCONNECT UNDER METER?
 PLEASE CORRELATE PLANS/W/ RISER
  
 4)NOTE: PLEASE VERIFY 1/0 CONDUCTORS
 SHOWN FOR 70A FEED TO TRANSFORMER.
 1/0'S ARE PERMITTED, HOWEVER, PLEASE
 VERIFY IF THIS SIZE CONDUCTOR WILL FIT
 INTO 70A BRKR? THIS IS A CLARIFICATION
 NOTE ONLY..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-07-12 Cont ID  
Sent By nmccray Date 2004-07-12 Time 13:18 Rev Time 0.00
Received By nmccray Date 2004-07-12 Time 13:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-06-08 Cont ID  
Sent By nmccray Date 2004-06-08 Time 10:58 Rev Time 0.00
Received By nmccray Date 2004-06-08 Time 10:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-30 Cont ID  
Sent By mcarsill Date 2004-04-30 Time 12:46 Rev Time 0.00
Received By mcarsill Date 2004-04-30 Time 12:46 Sent To  
Notes
2004-04-30 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) IN THE DOOR SCHEDULE REMARKS NONE
 ARE MADE FOR DOOR 611. ANY REASON FOR
 THIS DOOR NOT TO BE FIRE RATED.
  
 3) IT APPEARS THAT DOOR 625 DOES NOT
 NEED TO BE FIRE RATED. THE DOOR
 SCHEDULE INDICATES THAT IT IS. PLEASE
 EXPLAIN.
  
 4) KEY NOTES ON PAGE A-1 INDICATES
 # 8, CARD READER FOR ENTRY AND EXIT
 PLEASE EXPLAIN FURTHER.
  
 5) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER SYSTEM
 REMODEL.
  
 6) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM
 REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 16:33 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 16:33 Sent To E
Notes
2004-08-03 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 11:30 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 11:30 Sent To  
Notes
2004-07-02 00:00:00TO COMM BD#35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-07 Time 11:23 Rev Time 0.00
Received By csiegber Date 2004-06-07 Time 11:23 Sent To  
Notes
2004-06-07 00:00:00TO COMM BD#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-27 Cont ID  
Sent By kstevens Date 2004-05-27 Time 11:25 Rev Time 0.00
Received By kstevens Date 2004-04-30 Time 11:34 Sent To  
Notes
2004-04-30 00:00:00TO COMM BD#16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By pkrauss Date 2004-07-12 Time 10:06 Rev Time 0.40
Received By pkrauss Date 2004-07-12 Time 09:58 Sent To  
Notes
2004-07-12 00:00:00NEW MECHANICAL SHEETS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-13 Cont ID  
Sent By pkrauss Date 2004-05-13 Time 07:54 Rev Time 0.40
Received By pkrauss Date 2004-05-13 Time 07:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-07-14 Cont ID  
Sent By kstevens Date 2004-07-14 Time 16:11 Rev Time 1.00
Received By kstevens Date 2004-07-14 Time 16:11 Sent To  
Notes
2004-07-14 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTOR SHALL BE INSTALLED
 PER PDI-WH 201

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-06-19 Cont ID  
Sent By kstevens Date 2004-06-19 Time 07:24 Rev Time 0.50
Received By kstevens Date 2004-06-19 Time 07:24 Sent To  
Notes
2004-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: SHT A-1 DETAIL
 #3 SHOW COMPLIANCE FOR SECTION 11-4.24.6
 EXPOSED PIPES AND SURFACES ON PLANS.
 2) FROM PREVIOUS REVIEW: SHT PO.1 DOMES-
 TIC WATER ISOMETRIC, THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIX-
 TURE NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS
 3) CORRECT THE CERTIFICATE OF AUTHORIZ-
 ATION NUMBER REQUIRED BY 61G15-23.002(2)
 AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-27 Cont ID  
Sent By kstevens Date 2004-05-27 Time 09:52 Rev Time 0.50
Received By kstevens Date 2004-05-27 Time 09:52 Sent To  
Notes
2004-05-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 DETAIL DETAIL #3 AND FLOOR
 PLAN. SHOW KNEE CLEARANCEPER SECTION
 114.24.3, SINK DEPTH 11-4.24.4, CLEAR
 FLOOR SPACE 11-4.24.5, AND EXPOSED PIPES
 AND SURFACES 11-4.24.6
 2) SHT P0.1 DOMESTIC WATER ISOMETRIC,
 THE WATER HAMMER ARRESTOR SHALL BE LOC-
 ATED NEAR THE FIXTURE NOT IN THE CEILING
 AS SHOWN. PDI-WH 201 & MANUF. INSTALL,
 INSTRUCTIONS
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]