Plan Review Details - Permit 04041949
Plan Review Stops For Permit 04041949
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-21 Cont ID  
Sent By lsmith Date 2004-06-21 Time 09:57 Rev Time 1.00
Received By lsmith Date 2004-06-21 Time 09:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-24 Cont ID  
Sent By jleech Date 2004-06-17 Time 20:07 Rev Time 3.00
Received By lsmith Date 2004-05-24 Time 08:47 Sent To  
Notes
2004-05-24 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2. SUBMIT MANUFACTURES INFORMATION ON
 THE GE2000 THAT IS SHOWN FOR THE BUTT
 GLASS WINDOW INSTALLATION.
  
 3. NOTE: PLEASE SEE FBC 104.4.1.3 AND
 FS 471.003. PLANS REQ'D TO BE SIGNED,
 DATED AND SEALED BY A PE. PLEASE ALSO
 INCLUDE REQ'D TITLE BLOCK(S) FOR
 ENGINEER OF RECORD. INITIALS ARE NOT
 ACCEPTED. NO PHOTO COPIES OF SEALS ON
 REPORTS ACCEPTED.
 FS 471.023, FAC 61G15-23.002
  
 4. PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 2001 FBC 2406.2. MUST
 HAVE ORIGINAL SIGNATURE & SEAL FROM AN
 ENGINEER.A LETTER MUST BE SUBMITTED
 BY THE ENGINEER WHEN THE WINDOW
 ASSEMBLY HAS BEEN INSTALLED STATING IT
 IS INSTALLED AS PER HIS SPECIFICATIONS.
 A SITE SPECIFIC FORM HAS BEEN INCLUDED
 IN THE RETURNED PLANS FOR YOUR USE.
  
 5. THE APPLIED VALUE HAS BEEN ADJUSTED
 PER SBCCI VALUATION TABLE:ADDITIONAL
 FEES OF $773.56 ARE DUE BEFORE A PERMIT
 CAN BE ISSUED.
  
 6. THE APPLICATION ASKS FOR SQUARE
 FOOTAGE.THIS SHOULD BE THE TOTAL
 SQUARE FOOTAGE OF THE HOUSE INCLUDING
 ALL PORCHES, GARAGES, ETC.
 THE SBCCI VALUATION TABLE AT THIS TIME
 HAS A RATE AS FOLLOWS:
 A/C @ $76.96 PER SQ. FT.
 UNCONDITIONED @ $41.60 PER SQ. FT.
  
 7. THE THERMA-TRU "SERIES "FIBERCLASSIC"
 & "SMOOTH STAR" OUTSWING DOORS WILL
 REQUIRED HURRICANE PROTECTION ACCORDING
 TO THE MIAMI DADE PRODUCY APPROVAL.
 THE FLORIDA PRODUCT APPROVAL SUBMITTED
 IS NOT FOR THAT MODEL OF DOOR.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 17:53 Rev Time 0.10
Received By dpalmer Date 2005-03-08 Time 17:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-09 Cont ID  
Sent By dpalmer Date 2004-06-09 Time 10:51 Rev Time 0.33
Received By dpalmer Date 2004-06-09 Time 10:51 Sent To P
Notes
2004-06-09 00:00:00ALL OLD/VOIDED SHEETS NEED TO BE REMOVED
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-10 Cont ID  
Sent By csiegber Date 2004-06-02 Time 15:24 Rev Time 0.33
Received By dpalmer Date 2004-05-10 Time 06:29 Sent To M
Notes
2004-05-10 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR(S) FROM MAINS TO
 PANELS. 250.24, 250.110, SIZE PER 250.
 122.
  
 2)NOTE: PLEASE HAVE ARCH SIGN WITH
 SIGNATURE CONTAINING A MIN IF FIRST
 AND LAST NAME. FIRST NAME APPEARS TO BE
 INITIALS. PER FS 481.221.
 DBPR HAS MENTIONED INITIALS ARE NOT
 PERMITTED.
  
 3)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 4)NOTE: PLEASE SEE NFPA-72FOR LOCATION
 OF SD IN MASTER BEDROOM. TO BE LOCATED
 W/IN 3' OF POINT OF CEILING.
  
 5)NOTE: PLEASE SEE 210.52C 2, 4
 FOR SEPARATE COUNTERSPACES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 11:11 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 11:11 Sent To P
Notes
2005-03-23 00:00:00TO "KSTEVENS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 08:10 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 08:10 Sent To E
Notes
2005-03-07 00:00:00DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-02 Time 15:24 Rev Time 0.00
Received By csiegber Date 2004-06-02 Time 15:24 Sent To E
Notes
2004-06-02 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-24 Cont ID  
Sent By mmclean Date 2004-04-30 Time 17:57 Rev Time 0.00
Received By lsmith Date 2004-04-30 Time 11:37 Sent To  
Notes
2004-05-12 00:00:005/11/2004 "P" SUBMITTAL PUT IN PKG
2004-05-03 00:00:00TO SFD RACK/E
2004-04-30 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-14 Cont ID  
Sent By dpalmer Date 2004-05-10 Time 06:29 Rev Time 0.30
Received By pkrauss Date 2004-05-14 Time 11:31 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-04-09 Cont ID  
Sent By jleech Date 2005-04-09 Time 07:10 Rev Time 0.50
Received By jleech Date 2005-04-09 Time 07:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By jleech Date 2004-06-17 Time 20:07 Rev Time 0.33
Received By jleech Date 2004-06-17 Time 20:07 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By dpalmer Date 2004-06-09 Time 10:51 Rev Time 0.50
Received By kstevens Date 2004-05-19 Time 11:20 Sent To  
Notes
2004-05-19 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE PER DBPR.
 FAC 61G1-16.003 & FS 481.221
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 11:37 Rev Time 0.00
Received By mmclean Date 2004-04-30 Time 17:57 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy