Plan Review Details - Permit 04041947
Plan Review Stops For Permit 04041947
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-06-28 Cont ID  
Sent By nmccray Date 2004-06-28 Time 16:05 Rev Time 0.00
Received By nmccray Date 2004-06-28 Time 16:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-29 Cont ID  
Sent By csiegber Date 2004-06-28 Time 16:01 Rev Time 0.00
Received By nmccray Date 2004-04-29 Time 13:58 Sent To  
Notes
2004-04-29 00:00:00*************DENIED*********************
 1) UNDER SEQUENCE OF OPERATION THE DUCT
 DETECTORS SHALL ACTIVATE GENERAL FIRE
 ALARM SIGNAL NOT A SUPERVISORY AND
 REPORTED TO THE CENTRAL STATION FACILITY
 (PER FIRE MARSHAL OF WEST PALM BEACH).
  
 2) FIRE ALARM CIRCUITS AND DEVICES SHALL
 BE CLASS "A" OR FULLY ADDRESSABLE UNLESS
 EXISTING.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-28 Time 16:01 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 16:01 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 14:57 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 14:57 Sent To FIRE
Notes
***NONE***