| 2004-04-29 00:00:00 | *************DENIED********************* | | | 1) UNDER SEQUENCE OF OPERATION THE DUCT | | | DETECTORS SHALL ACTIVATE GENERAL FIRE | | | ALARM SIGNAL NOT A SUPERVISORY AND | | | REPORTED TO THE CENTRAL STATION FACILITY | | | (PER FIRE MARSHAL OF WEST PALM BEACH). | | | | | | 2) FIRE ALARM CIRCUITS AND DEVICES SHALL | | | BE CLASS "A" OR FULLY ADDRESSABLE UNLESS | | | EXISTING. | | | | | | NATE MCCRAY, CAPTAIN | | | 805-6722 OR 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-06-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-28 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-23 |
Time |
16:01 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-04-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-28 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-28 |
Time |
14:57 |
Sent To |
FIRE |
|
| Notes |
|
|
|