Plan Review Details - Permit 04041907
Plan Review Stops For Permit 04041907
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-18 Time 15:34 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 15:34 Sent To P
Notes
2004-05-18 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 11:51 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 11:51 Sent To P
Notes
2004-04-28 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-28 Cont ID  
Sent By kstevens Date 2004-05-28 Time 18:11 Rev Time 0.50
Received By kstevens Date 2004-05-28 Time 18:11 Sent To  
Notes
2004-05-28 00:00:00REVISION OK - CHANGED 3/4" TO 1/2" CSST
 TO 60K BTU RANGE
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
 Z

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-09 Cont ID  
Sent By csiegber Date 2004-05-18 Time 15:34 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2004-05-09 00:00:00PROVISO
 SHOW ALL PIPE SIZES,
 TABLES USED FOR SPECIFIC MATERIAL? CSST