Plan Review Details - Permit 04041833
Plan Review Stops For Permit 04041833
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-29 Cont ID  
Sent By dpalmer Date 2004-07-01 Time 09:32 Rev Time 1.50
Received By lsmith Date 2004-06-29 Time 14:04 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-21 Cont ID  
Sent By pkrauss Date 2004-06-29 Time 10:19 Rev Time 2.50
Received By lsmith Date 2004-05-21 Time 11:34 Sent To  
Notes
2004-05-21 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2. THE FLORIDA ENERGY EFFICIENCY CODE
 FORM STATES THE EXTERIOR CONCRETE WALLS
  
 HAVE AAN R-4.2 RATING.THE PLANS STATE
 R12.9.PLEASE CLARIFY.
  
 3. VERIFY THAT ALL USP & SIMPSON
 CONNECTORS ARE INSTALLED ACCORDING TO
 MANUFACTURERS SPECS. REVISE ON PAGE
 RF-1.
  
 4. ROYAL WALL: SUBMIT A LETTER FROM A
 LICENSED THRESHOLD INSPECTOR STATING
 THAT AN INSPECTION WILL BE MADE AT THE
 MANUFACTURED SITE OF THE JOB SPECIFIC
 COMPONENTS TO VERIFY CONSTRUCTION
 COMPLIANCE OF THE COMPONENTS WITH THE
 ENGINEERED DESIGN.
  
 5. THE PLANS SPECIFY AN IMACT S/H
 WINDOW IN THE DEN.IS IT A 701 IMPACT?
 IF SO YOU HAVE THE FLORIDA PRODUCT
 APPROVALS FOR IT.
  
 6. STATE STATUTE REQUIRED ARCHITECTS &
 ENGINEERS TO USE FULL SIGNATURES ON
 PLANS & ENGINEERING.INITIALS ARE NOT
 ACCEPTABLE.THEY HAVE TO BE ORIGINAL
 NOT PHOTO COPIES.
  
 7. ACCORDING TO SBCCI BUILDING
 VALUATIONTABLE THE VALUE FOR THE A/C
 SPACE IS $76.96.THE UNCONDITIONED
 SPACE REMAINS $41.60.THE NEW ADJUSTED
 FEE REMAINING TO BE PAID BEFORE
 PERMITTING IS $60.75.
  
 8. SUBMIT THE FLORIDA PRODUCT APPROVALS
 FOR THE WEATHERGUARD STORM PANELS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-01 Cont ID  
Sent By dpalmer Date 2004-07-01 Time 09:32 Rev Time 0.33
Received By dpalmer Date 2004-07-01 Time 09:32 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-07 Cont ID  
Sent By lsmith Date 2004-06-29 Time 14:06 Rev Time 0.33
Received By dpalmer Date 2004-05-07 Time 06:49 Sent To M
Notes
2004-05-07 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE HAVE ARCH SIGN PLANS WITH
 SIGNATURE AS REQ'D UNDER FS 481.221.
 MUST CONTAIN A MIN OF FIRST AND LAST
 NAME. CONVERSATION W/ BOARD, INITIALS
 ARE NOT PERMITTED.
 PLEASE ALSO BE SURE SEAL IS RAISED/CLEAR
 IN ORDER TO BE ABLE TOVIEW INFORMATION
 ON SEAL.
  
 2)NOTE: PLEASE SEE MISSING SDIN WHAT
 APPEARS TO BE A BEDRM.
 ROOM DESIGNATIONS ARE NOT ON ELECTRICAL
 PLAN, UNABLE TO VERIFY RM. PLEASE SEE
 REDLINED COPY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:42 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 10:42 Sent To M
Notes
2004-06-23 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-21 Cont ID  
Sent By mmclean Date 2004-04-28 Time 17:43 Rev Time 0.00
Received By lsmith Date 2004-04-27 Time 14:26 Sent To  
Notes
2004-04-30 00:00:00TO SFD RACK/E
2004-04-27 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-29 Cont ID  
Sent By pkrauss Date 2004-06-29 Time 10:19 Rev Time 0.30
Received By pkrauss Date 2004-06-29 Time 09:33 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:42 Rev Time 0.35
Received By pkrauss Date 2004-05-11 Time 08:57 Sent To B
Notes
2004-05-11 00:00:00DENIED:
 RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.PLEASE REVISE PLANS PER THE
 REVISED 2001 FBC(M) 601.4 EFFECTIVE
 JUNE 30,2003:
  
 GUEST BEDROOM #2 RETURN AIR JUMPER =
 12"GUEST BEDROOM #3 RETURN AIR JUMPER =
 12"MASTER SUITE RETURN AIR = 14"
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-08 Cont ID  
Sent By jleech Date 2004-05-08 Time 10:32 Rev Time 0.33
Received By jleech Date 2004-05-08 Time 10:32 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-04-28 Time 17:43 Rev Time 0.00
Received By mmclean Date 2004-04-28 Time 17:43 Sent To I
Notes
***NONE***