Plan Review Details - Permit 04041636
Plan Review Stops For Permit 04041636
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-28 Cont ID  
Sent By alange Date 2004-06-28 Time 11:05 Rev Time 1.25
Received By alange Date 2004-06-28 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-21 Cont ID  
Sent By pkrauss Date 2004-06-25 Time 10:43 Rev Time 2.75
Received By alange Date 2004-05-21 Time 15:10 Sent To  
Notes
2004-05-21 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2."R" VALUE FOR WALL INSULATION ON
 ENERGY CALCS DOES NOT MATCH PLANS.
  
 3.ACCORDING TO SBCCI BUILDING
 VALUATION DATA THE VALUATION HAS BEEN
 REVISED TO $262,163.THE CURRENT
 SQUARE FOOT PRICE IS $76.96.
  
 4.FULL SIGNATURE REQIRED BY ARCHITECT
 ON PLANS FS. 481.221
 ALSO ORIGONAL ENGINEERS SIGNATURE
 REQUIRED ON STRUCTURAL CALCULATIONS.
  
 5.NOTE:TRUSS DRAWINGS NOT REQUIRED
 FOR REVIEW.PLEASE HAVE ONE COPY ON
 SITE FOR INSPECTOR.
  
 6. PRODUCT APPROVAL FOR CLOPLAY DOORS
 NOT LISTED ON THE DCA SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 SUBMIT SECOND COPY OF PRODUCT APPROVALS
 FORUNITED STEEL PRODUCTS AND
 SIMPSON STRONG TIE
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLAN REVIEW
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 21:24 Rev Time 0.33
Received By dpalmer Date 2004-06-23 Time 21:24 Sent To M
Notes
2004-06-23 00:00:00REMOVED OLD/VOIDED ELECTRICAL SHEET,
 INSERTED NEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:57 Rev Time 0.33
Received By dpalmer Date 2004-05-07 Time 08:25 Sent To M
Notes
2004-05-07 00:00:00** UNSAT **
  
 1)NOTE: PLEASE HAVE ARCH SIGN PLANS W/
 SIGNATURE INCLUDING FRIST NAME.
 INITIALS ARE NOT PERMITTED. FS 481.221
 PLEASE MAKE SURE SEAL IS CLEAR AND
 VISBLE WITH ALL INFORMATION REQ'D ON
 SEAL.
  
 2)NOTE: PLEASE SEE MISSING SD IN BEDRM?
 RM DESIGNATION NOT SHOWN, UNABLE TO
 VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:57 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 10:57 Sent To E
Notes
2004-06-23 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-21 Cont ID  
Sent By mmclean Date 2004-04-28 Time 17:50 Rev Time 0.00
Received By alange Date 2004-04-27 Time 14:25 Sent To  
Notes
2004-04-30 00:00:00TO SFD RACK/E
2004-04-27 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-25 Cont ID  
Sent By pkrauss Date 2004-06-25 Time 10:43 Rev Time 0.35
Received By pkrauss Date 2004-06-25 Time 10:27 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-11 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 21:24 Rev Time 0.35
Received By pkrauss Date 2004-05-11 Time 10:27 Sent To B
Notes
2004-05-11 00:00:00DENIED:
 RETURN AIR FROM BEDROOM AREAS ARE NOT
 SIZED PROPERLY.PER THE REVISED 2001
 FBC(M) 601.4 EFFECTIVE JUNE 30, 2003,
 THE RETURN AIR SHALL BE AS FOLLOWS:
  
 BEDROOM SUITE #2 RETURN AIR JUMPER =
 12"BEDROOM SUITE #3 RETURN AIR JUMPER =
 12"MASTER SUITE = 14"
  
 PLEASE REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-08 Cont ID  
Sent By jleech Date 2004-05-08 Time 10:45 Rev Time 0.33
Received By jleech Date 2004-05-08 Time 10:45 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-04-28 Time 17:50 Rev Time 0.00
Received By mmclean Date 2004-04-28 Time 17:50 Sent To I
Notes
***NONE***