Plan Review Details - Permit 04041460
Plan Review Stops For Permit 04041460
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-05-04 Cont ID  
Sent By pkrauss Date 2004-05-03 Time 15:13 Rev Time 0.00
Received By nmccray Date 2004-05-04 Time 10:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 11:47 Rev Time 0.00
Received By alange Date 2004-04-22 Time 11:47 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-28 Cont ID  
Sent By pkrauss Date 2004-10-28 Time 16:13 Rev Time 0.35
Received By pkrauss Date 2004-10-28 Time 16:13 Sent To  
Notes
2004-10-28 00:00:00SUBMITTAL/DETAIL FOR HANGING THE HOOD.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-03 Cont ID  
Sent By pkrauss Date 2004-05-03 Time 15:12 Rev Time 0.40
Received By pkrauss Date 2004-05-03 Time 15:12 Sent To FIRE
Notes
2004-05-03 00:00:00PROVISO:
 1.EXHAUST OUTLETS SHALL BE A MINIMUM
 OF 10 FT HORIZONTALLY FROM ADJACENT
 PROPERTY LINES OR FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDING. 2001
 FBC(M) 506.3.14.3.
  
 2.PLEASE NOTE, AIR VELOCITY WITHIN THE
 DUCT SHALL BE NOT LESS THAN 1,500 FPM &
 NOT GREATER THAN 2,500 FPM.
  
 3.PROVIDE MANUFACTURER INSTALLATION
 DATA FOR THE 3M FASTWRAP+ THATIS
 INDICATED ON THE PLAN.
  
 4.ALL WELDS TO BE INSPECTED PRIOR TO
 COVERING.