Plan Review Details - Permit 04041387
Plan Review Stops For Permit 04041387
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-20 Cont ID  
Sent By alange Date 2004-05-20 Time 09:21 Rev Time 0.50
Received By alange Date 2004-05-20 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-19 Cont ID  
Sent By alange Date 2004-05-19 Time 11:36 Rev Time 0.66
Received By alange Date 2004-05-19 Time 11:36 Sent To  
Notes
2004-05-19 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.SUBMIT 2 COPIES OF WINDOW PRODUCT
 APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-06 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 17:00 Rev Time 1.00
Received By alange Date 2004-05-06 Time 11:11 Sent To  
Notes
2004-05-06 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.THE LOWEST BUILDING FLOOR ELEVATION
 AT HABITABLE AREAS SHALL BE A MINIMUM
 OF 4 INCHES ABOVE FINISHED GRADE.
 FBC AMMENDMENTS 1804.1.7
 SHOW ON PLAN HOW FLOOR WILL BE RAISED
 ABOVE GRADE.
  
 4.SUBMIT 2 COPIES OF ALL PRODUCT
 APPROVALS.SUBMIT DOOR PRODUCT APPROVAL
 THAT SUPPORTS SIDLITES AND MULLION.
 SUBMIT PRODUCT APPROVAL FOR WINDOW.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SHOW HEADER DETAIL INCLUDING STRAPS
 USED.
  
 ANY QUESTONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-18 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 17:00 Rev Time 0.33
Received By dpalmer Date 2004-05-18 Time 17:00 Sent To B
Notes
2004-05-18 00:00:00******NOTES REDLINED ************
  
 SOME NOTES FROM FIRST REVIEW NOT ADDRESS
 -ED.
  
 PLEASE SEE EXIST PANEL STILL SHOWN AS
 MLO. MEANS OF DISCONNECT REQ'D PER
 225.31
  
 RECEPTS PER 210.52
 SD PER NFPA-72

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-14 Time 11:42 Rev Time 0.33
Received By dpalmer Date 2004-05-03 Time 18:07 Sent To Z
Notes
2004-05-03 00:00:00*********** UNSAT ******************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 FS 481.219. PLEASE PROVIDE ALL REQ'D
 LICENSE #'S ON TITLE BLOCK AS REQ'D.
  
 2)NOTE: PLEASE PROVIDE EXIST PANEL
 SCHEDULE AND CLARIFY IF MCB? 225.31
  
 3)NOTE:PLEASE SEE 210.70 FOR REQ'D
 EGRESS LT.
  
 4)NOTE: PLEASE SEE 210.52 FOR REQ'D
 RECEPTS FOR WALL SPACE IN HABITABLE RM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-14 Time 11:42 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 11:42 Sent To E
Notes
2004-05-14 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 08:15 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 08:15 Sent To B
Notes
2004-05-06 00:00:00TO RES BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-29 Cont ID  
Sent By pkrauss Date 2004-04-29 Time 08:02 Rev Time 0.30
Received By pkrauss Date 2004-04-29 Time 08:01 Sent To E
Notes
2004-04-29 00:00:00PROVISO:
 PLAN INDICATE A/C WALL UNIT.PROVIDE
 MANUFACTURER SUBMITTAL DATA ON THE JOB
 SITE AT THE TIME OF THE INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-05-05 Cont ID  
Sent By dpalmer Date 2004-05-03 Time 18:07 Rev Time 0.00
Received By mmclean Date 2004-05-05 Time 16:07 Sent To I
Notes
***NONE***