Plan Review Details - Permit 04041317
Plan Review Stops For Permit 04041317
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By alange Date 2005-08-10 Time 12:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-10 Cont ID  
Sent By alange Date 2004-06-10 Time 09:37 Rev Time 1.00
Received By alange Date 2004-06-10 Time 09:37 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-20 Cont ID  
Sent By jleech Date 2004-06-08 Time 19:42 Rev Time 3.00
Received By alange Date 2004-05-20 Time 08:48 Sent To  
Notes
2004-05-20 00:00:00DENIED
 BUILDING VALUATION OF $403,950 IS TOO
 LOW BASED ON SBCCI BUILDING VALUATION
 DATA.
 A/C 4338 SF X 76.96 = $333,852
 1777 SF X 41.60 =$73,923
 REVISED VALUATION$407,775
 ADDITIONAL PERMIT FEES OF $60.05 ARE DUE
  
 2.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR FRONT ENTRY DOOR.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.FLORIDA STATUTE: 481.221WHEN
 PLANS ARE SIGNED BY THE ARCHITECT, THEY
 MUST ALSO BE DATED BY THE ARCHITECT.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-10-14 Cont ID  
Sent By dpalmer Date 2005-10-14 Time 16:40 Rev Time 1.00
Received By dpalmer Date 2005-10-14 Time 16:40 Sent To  
Notes
2005-10-14 00:00:00REDLINED LOAD CALCS ON PANEL "A". LOAD
 IS ACTUALLY LESS THAN SHOWN. SHOULD BE
 65% OF 7KW NOT 10KW.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-09-19 Cont ID  
Sent By dpalmer Date 2005-09-19 Time 11:18 Rev Time 0.40
Received By dpalmer Date 2005-09-19 Time 11:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-08-30 Cont ID  
Sent By dpalmer Date 2005-08-30 Time 08:04 Rev Time 0.50
Received By dpalmer Date 2005-08-30 Time 08:04 Sent To  
Notes
2005-08-30 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS HAVE BEEN
 REVISED WITH "WHITE-OUT" ANDHAND=DRAWN
 CHANGES. PLEASE SEE THAT ALL CHANGES ARE
 DONE BY ARCHITECT, REPRINTED AND SIGNED,
 DATED AND SEALED. FS 481.221
  
 2)NOTE: PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
 INFORMATION IN TITLE BLOCK.
 GFI RECEPTS PER 210.8
  
  
 3)NOTE: PLEASE SEE RISER DIAGRAM HAS NOW
 BEEN REVISED, HOWEVER PLANS STILL SHOW A
  
 MAIN OUTSIDE?
 PLEASE ALSO SEE PANELS ARE BEING SHOWN
 AS BEING FED OVERHEAD.??
 PLEASE SEE 230.70, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTOR MAY BE "INSIDE"
 HOUSE.
 PLEASE PROVIDE MAINS AND OVERCURRENT
 PROTECTION OUTSIDE IF INDEED SERVICE IS
 BEING FED OVERHEAD TO PANELS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 11:59 Rev Time 1.00
Received By dpalmer Date 2005-08-04 Time 10:56 Sent To  
Notes
2005-08-04 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE 250.6,250.24
 "EQUIPMENT GROUNDING" CONDUCTORS ARE NOT
 INSTALLED FROM METER TO THE FIRST MEANS
 OF DISCONNECT.
 PLEASE SEE THIS WAS NOTED ON ALL THREE
 PREVIOUS REVIEWS AND THIS IS STILL
 SHOWN.
 PLEASE SEE THE "EQUIPMENT GROUNDING"
 CONDUCTORS ARE MISSING FROM MIANS OT
 SUB-PANELS.
 250.110,250.24 SIZED PER 250.122
  
 2)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE GFI. COUNTERSPACE SHOWN IS
 MORE THAN 4'. 210.52C1
  
 3)NOTE: PLEASE SEE POOL SUB PANEL "C" IS
 NOT SHOWN ON PLANS?
 PLEASE ALSO CORRELATE PLANS AND RISER.
 PLANS ONLY INDICATEONE MAIN?
 215.5
  
 4)NOTE: PLEASE SEE POOL SUB PANEL IS
 SHOWN AS A 200A PANEL WITH A 80A FEED.
 PLEASE VERIFY IF INDEED PANEL INSTALLED
 IS A 42 CIRCUIT 200A RATED PANEL?
 PLEASE SEE RISER DIAGRAM SHOWS 8/0'S FOR
 FEEDERS AND A #2 EQUIPMENT GROUNDING
 CONDUCTOR?
 PLEASE SEE 8/0 IS NOT A WIRE SIZE, ETC
 240.4,310.16
 PLEASE SEE AWG SHOWN ON PANEL "A" FOR
 POOL PANEL IS SHOWN AS #4.
  
 5)NOTE: PLEASE CORRELATE LOAD SHOWN ON
 PANEL "A" FOR POOL SUB PANEL AND LOAD
 SHOWN ON POOL PANEL "C".
 215.5
  
 6)NOTE: PLEASE SEE MISSING GFI RECEPT
 REQUIRED W/ IN 3' OF "HIS BATH' LAV.
 210.52D
  
 7)NOTE: PLEASE SEE FAC 61G1-16.004,
 TITLE BLOCK SHALL CONTAIN THE PRINTED
 ANME AND LICENSE # (AR) OF THE ARCHITECT
 OF RECORD.
 THIS WAS NOT ON NOTES FROM REVIEWS LAST
 YEAR.
  
 8)NOTE: PLEASE SEE MANY ITMES ARE SHOWN
 AS OPTIONAL ON PLANS?PLEASE KNOW, IF
 THESE PLANS ARE FOR FINAL/CO, ALL ITEMS
 INSTALLED SHALL BE SHOWN, ALL ITMES NOT
 INSTALLED, SHALL BE DELETED.
  
 9)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT. PLEASE
 SHOW THIS LOAD IN ADDITION TO THE 3WATS
 PER SQ FT. PLEASE SEE THERE ARE OVER 80
 RECESSED LTS.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 08:51 Rev Time 0.75
Received By dpalmer Date 2004-06-17 Time 07:50 Sent To Z
Notes
2004-06-17 00:00:00********** REDLINED ***********
  
 PLANS/RISER STILL SHOW EQUIPMENT GROUND-
 -ING CONDUCTORS BEING INSTALLED FROM
 METER TO DISCONNECTS.
 THIS WAS NOTED ON PREVIOUS TWO REVIEWS,
 AN EQUIPMENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT. 250.24,250.6
 PLANS HAVE BEEN REDLINED.
 RECEPT SHOWN FOR DINING RM FLR, NOT AN
 OPTION, REQ'D PER 210.52
 ALL REVISIONS/OPTS ARE TO BE REVIEWED
 BEFORE ROUGH.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-04 Cont ID  
Sent By csiegber Date 2004-06-15 Time 14:52 Rev Time 0.75
Received By dpalmer Date 2004-06-04 Time 11:35 Sent To P
Notes
2004-06-04 00:00:00********** UNSAT ***********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 WERE NOT ADDRESSED.
  
 NOTES:
 NOTE #1 IS ONLY A NOTE: RISER/PLANS SHOW
 A MAIN DICONNECTS AND MCB PANELS. MCB
 PANELS ARE PERMITTED BUT NOT REQUIRED
 DUE TO HAVING MAIN DISCONNECTS OUTSIDE,
 HOWEVER IF SHOWN THEN MCB'SWILL BE
 REQ'D.
  
 NOTE #2 ?
 NOTE #3 NO.
 NOTE #4 OK
 NOTE #5 NO
 NOTE #6 NO
 NOTE #7 OK
 NOTE #8 OK
 NOTE #9 OK.
  
 PLEASE BE SURE TO REMOVE OLD/VOIDED
 SHEETS FROM SETS AND INSERT NEW SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SEE ATTACHED COPY OF FS 553.80(2)
 (B). THIS NOTICE IS GIVEN ON PLANS WITH
 SAME COMMENTS AS A NOTICE AFTER SECOND
 REVIEW. THIS IS ONLY A NOTICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-06-02 Time 09:52 Rev Time 0.50
Received By dpalmer Date 2004-05-07 Time 06:02 Sent To M
Notes
2004-05-07 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE RISER W/
 PANELS. PANELS ARE SHOWN AS MCB AND
 RISER SHOWS MLO?
  
 2)NOTE: PLEASE VERIFY 150A PANELS ARE
 SHOWN AS 42 CIRCUIT?
  
 3)NOTE: RISER SHOWS EQUIPMENT GROUNDING
 CONDUCTORS BEING INSTALLED BETWEEN METER
 AND MAINS/FIRST MEANS IF DISC.
 PLEASE SEE 250.6, 250.24. THIS IS NOT
 PERMITTED. ONLY AFTER THE FIRST MEANS OF
 DISC.
  
 4)NOTE:PLEASE SEE 210.52, 210.52C1 FOR
 RECEPT SPACING IN TWO RMS AND KITCHEN
 COUNTER/ DESK AREA.
  
 5)NOTE: PLEASE PROVIDE ROOM DISIGNATION
 ON PLANS.
  
 6)NOTE: PLEASE SEE AHU#3, SHOWS 8KW
 W/ 30A OCP. PLEASE SEE 424.3B, MIN OCP
 FOR HEAT 125% OF KW RATING.
  
 7)NOTE: PLEASE SEE FOYER IS SHOWN AS
 HAVING A J-BOX. A LT FIXTURE OF SOME
 SORT WILL BE REQ'D FOR EGRESS LT, 210.70
 LS 101 5-8
  
 8)NOTE: PLEASE SEE THAT SD IN MASTER
 BEDROOM AREA MUST BE MOVED INTO MASTER
 BEDRM. PLEASE SEE NFPA-72 FOR INSTALLA-
 -TION LOCATIONS. 8-1.4.2, 8-1
  
 9)NOTE: PLEASE SEE FS 481.221, WHEN PLAN
 -S A RE SIGNED BY THE ARCH, THEY MUST
 ALSO BE DATED BY ARCH.
  
 PLEASE ALSO SEE BLDG REVIEW COMMENTS
 FOR POSSIBLE BLDG VALUATION ADJUSTMENT.
 FBC 104.6.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 08:53 Sent To E
Notes
2005-09-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-25 Cont ID  
Sent By adarroug Date 2005-08-25 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-08-25 Time 08:53 Sent To E
Notes
2005-08-25 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-17 Cont ID  
Sent By adarroug Date 2005-08-17 Time 10:21 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 10:21 Sent To P
Notes
2005-08-17 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 10:56 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 10:56 Sent To B
Notes
2005-08-08 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 14:37 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 14:37 Sent To E
Notes
2005-08-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-06-15 Time 14:52 Rev Time 0.00
Received By csiegber Date 2004-06-15 Time 14:52 Sent To E
Notes
2004-06-15 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-02 Time 09:51 Rev Time 0.00
Received By csiegber Date 2004-06-02 Time 09:51 Sent To E
Notes
2004-06-02 00:00:00TO DP DESK/RESUB/

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-26 Cont ID  
Sent By alange Date 2004-05-26 Time 09:18 Rev Time 0.00
Received By alange Date 2004-05-26 Time 09:18 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-20 Cont ID  
Sent By alange Date 2004-05-20 Time 08:59 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:16 Sent To  
Notes
2004-05-06 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-24 Cont ID  
Sent By pkrauss Date 2005-01-24 Time 14:35 Rev Time 0.40
Received By pkrauss Date 2005-01-24 Time 13:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-05-10 Cont ID  
Sent By dpalmer Date 2004-05-07 Time 06:10 Rev Time 0.35
Received By pkrauss Date 2004-05-10 Time 16:40 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-08 Cont ID  
Sent By jleech Date 2004-06-08 Time 19:42 Rev Time 0.50
Received By jleech Date 2004-06-08 Time 19:42 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-18 Cont ID  
Sent By dpalmer Date 2004-06-04 Time 11:41 Rev Time 1.00
Received By kstevens Date 2004-05-18 Time 16:35 Sent To B
Notes
2004-05-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) LAUNDRY SINK AND WASH MACHINE SHALL
 NOT CONNECT TO THE STACK ON A DOUBLE
 SANITARY TEE. SECTION 706.3. CONNECT THE
 WASH MACHINE LOWER ON THE STACK THAN THE
 LAUNDRY SINK.
 B) CLEAN OUT REQUIRED 4' ABOVE THE
 FLOOR AT WASH MACHINE. SECTION 708.10
 C) TUB NOT VENTED IN BATH #2. SECTION
 901.2.1
 D) LAV ON RIGHT SIDE OF WATER CLOSET IN
 POWDER ROOM.
 E) BAR SINK NOT SHOWN ON FLOOR PLAN.
 SECTION 104.2.1
 F) SEE RED LINE CORRECTIONS ON RISER
 DIAGRAM. MAKE CORRECTIONS AND RESUBMIT
 FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-22 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 08:52 Rev Time 0.00
Received By gjoyce Date 2004-06-22 Time 15:10 Sent To  
Notes
2004-06-17 00:00:00DENIED, BY GRACE JOYCE, PLANNER 659-8031
 SEE NOTE 1 & 2.
2004-06-15 00:00:00DENIED, BY GRACE JOYCE, PLANNER 659-8031
 - THERE IS A PUBLIC SIDEWALK LOCATED ON
 PRIVATE PROPERTY.THE OWNER QUIT
 CLAIMED A PORTION OF THE GOLF COURSE
 INTO LOT 1.THE SIDE MUST BE MOVED TO
 APPROVAL AND A NEW SURVEY IS NEEDED. MM
2004-05-05 00:00:00THERE IS A PUBLIC SIDEWALK LOCATED ON
 PRIV. PROPERTY.THE OWNER QUIT CLAIMED
 A PORTION OF THE GOLF COURSE INTO LOT 1.
 THE SIDE MUST BE MOVED PRIOR TO
 APPROVAL