Plan Review Details - Permit 04041180
Plan Review Stops For Permit 04041180
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-16 Cont ID  
Sent By alange Date 2005-06-16 Time 14:09 Rev Time 1.00
Received By alange Date 2005-06-16 Time 14:09 Sent To  
Notes
2005-06-16 00:00:00REVISION OK FOR DOORS, WINDOWS AND
 ROOFING

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-15 Cont ID  
Sent By alange Date 2004-11-15 Time 13:10 Rev Time 1.25
Received By alange Date 2004-11-15 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-31 Cont ID  
Sent By alange Date 2004-08-31 Time 13:37 Rev Time 1.25
Received By alange Date 2004-08-31 Time 13:37 Sent To  
Notes
2004-08-31 00:00:00DENIED
  
 PREVIOUS COMMENTS:
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5. SHOW SIZE OF ATTIC ACCESS COMPLYING
 WITH FBC 2309.6
  
 7.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ART LANGE
 BUILDING PLAN REVIEW
 TEL: (561)805-6672
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-29 Cont ID  
Sent By pkrauss Date 2004-08-26 Time 15:39 Rev Time 1.33
Received By alange Date 2004-04-29 Time 09:36 Sent To  
Notes
2004-04-29 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BUILDING VALUATION OF $30,000 IS TO
 LOW BASED UPON SBCCI BUILDING VALUATION
 DATA.
 SQUARE FOOTAGE HAS BEEN CORRECTED TO
 1032 SQ. FT..
 1032SF X $76.96 PER SF = $79,422.00.
 ADDITIONAL PERMIT FEES OF $701.16 ARE
 DUE.
  
 4.SHOW SIZE OF EMERGENCY ESCAPE
 WINDOW ON EXISTING GUEST ROOM.
  
 5.SHOW LOCATION AND SIZE OF ATTIC
 ACCESS FBC 2309.6
  
 6.SHOW METHOD OF ATTACHMENT OF NEW
 SLAB INTO THE EXISTING SLAB.
  
 7.PRODUCT APPROVAL FOR JM METALS ROOF
 SYSTEM IS NOT LISTED ON THE DCA
 PRODUCT APPROVAL WEB SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.WORK SHALL COMPLY WITH
 FBC 3401.8.2.3.1 SEE ATTACHED CODE
 SECTION.SHOW HOW EXISTING STRUCTURE
 WILL COMPLY TO THIS SECTION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-06-14 Cont ID  
Sent By dpalmer Date 2005-06-14 Time 13:30 Rev Time 0.75
Received By dpalmer Date 2005-06-14 Time 13:23 Sent To B
Notes
2005-06-14 00:00:00************* UNSAT ****************
  
 PLEASE SEE THE FOLLOWING NOTES FOR THE
 GENERATOR WHICH CAME IN AS A REVISIONS
 UNDER THE MAIN BLDG PERMIT..
  
  
 1)NOTE: PLEASE SUBMIT FOR SEPARATE
 GENERATOR PERMIT.
 PLEASE SUPPLY A COMPLETE RISER DIAGRAM
 ON HOW GENERATOR WILL BE WIRED INOT NEW
 ELECTRICAL SERVICE. WIRING DIAGRAM FROM
 MANUFACTURE SUBMITED DOES NOT MEET NEC.
  
 PLEASE SEE 225.31-225.36
  
 2)NOTE: PLEASE SUBMIT LOAD CALCAULTIONS
 FOR SERVICE. PLEASE SEE 702.5 AND
 220.31B FOR SIZING OF GEN FOR SERVICE.
  
 3)NOTE: PLEASE SEE PLANS ARE NOT
 REQUIRED TO BE DONE BY AND ARCH OR
 ENGINEER BUT HOWEVER THEY MAY BE DONE BY
 THEM ALSO.
 PLEASE SEE FBC 104.2.1 WHICH REQUIRES
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 PLEASE NOTE: PLANS FOR EXISTING HOUSE
 ADDITION PERMIT WILL BE REQUIRED TO BE
 REVISED TO INCLUDE GEN WORK, HOWEVER
 THIS REVSION OF WORK MUST BE DONE BY THE
 ARCH OR ENGINEER OF RECORD.
 PER FS 481,471
 PLEASE SEE "PROVISO" GIVEN UPON ISSUANCE
 OF PERMIT HAS NOT BEEN REVISED AND OR
 CORRECTED AS OF THIS REVIEW.
  
 4)NOTE: PLEASE BE SURE THE GAS PERMIT IS
 EITHER APPLIED FOR OR REVISED IF ONE
 ALREADY EXISTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-02 Cont ID  
Sent By dpalmer Date 2004-11-02 Time 13:13 Rev Time 0.50
Received By dpalmer Date 2004-11-02 Time 13:12 Sent To B
Notes
2004-11-02 00:00:00******** PROVISO/REVISION **********
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEWS. NOTE#2 FROM BOTH PREVIOUS
 REVIEWS.
 PLEASE SUBMIT A PANEL SCHEDULE WITH ALL
 NEW MIN REQUIRED CIRCUITS. PLEASE ALSO
 INCLUDE ALL EXISTING.
 PLEASE SEE 210.52D,210.11C3
 PLEASE SEE 210.12 2002 NEC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION. IF OTHER REVISIONS ARE MADE
 BEFORE ROUGH, PLEASE INCLUDE ABOVE AT
 THAT TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-19 Cont ID  
Sent By dpalmer Date 2004-08-19 Time 14:11 Rev Time 0.50
Received By dpalmer Date 2004-08-19 Time 14:11 Sent To P
Notes
2004-08-19 00:00:00********** UNSAT **************
  
 ** PLEASE SEE SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.**
  
 1)NOTE: NOTE#1 NO.
 PLEASE SEE LOAD CALCULATIONS WERE
 SUBMITTED HOWEVER THEY DO NOT MEET NEC
 220.31B.
 PLEASE ALSO SEE A/C LOAD IS BEING FIG
 AS LIGHTING LOAD?
 PLEASE SEE LOAD CALCS ONLY INCLUDE
 NEW A/C AND NOT NEW AND EXSITING??
  
 2)NOTE: NOTE #2 NO. NO PANEL SCHEDULE
 SUBMITTED SHOWING MIN CIRCUITS.
 NOTES WERE SUBMITTED FOR NEW CIRCUITS,
 HOWEVER PLEASE SEE THE FOLLOWING FOR
 CORRECT LOADS, OCP AND AWG.
 210.52D,210.11C3 FOR BATHS.REQUIRED TO
 BE 20A #12 ETC.
 PLEASE SEE 210.12 FROM 2002 NEC FOR ARC-
 -FAULT PROTECTION. PLANS INDICATE LIGHT-
 -ING TO BE PROTECTED.?? SD'S RECEPTS,
 LTS.
 PLEASE SEE NO OCP/AWG FOR NEW A/C SHOWN?
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO. PLEASE SEE FBC
 CHAPTER 34. 3401.7.1.1.2,3401.7.1.2.1
 PLEASE SHOW ALL EXISTING AREAS TO MEET
 ABOVE PER ABOVE REQUIREMENTS.
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME
  
 6)NOTE: PLEASE SEE 210.63 FOR LT REQ'D
 FOR AHU IN MECH CLOSET.(NEW NOTE)
  
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF EACH "OLD" SETS SHOULD BE
 SUBMITTED FOR REFERENCE. ****
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-21 Cont ID  
Sent By csiegber Date 2004-08-16 Time 16:38 Rev Time 0.00
Received By alange Date 2004-11-15 Time 13:09 Sent To P
Notes
2004-04-21 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE 220.3C1, PLEASE
 PROVIDE COMPLETE LOAD CALCAULTIONS FOR
 NEW AND EXSITING.
 PLEASE CORRELATE SQ FT BEING ADDED,
 THERE ARE MORE THEN ONE PLACE ON PLANS
 WHERE SQ FT #'S DO NOT CORRELATE.
  
 2)NOTE: PLEASE SHOW/LIST PANEL SCHEDULE
 AND SHOW MIN CIRCUIT(S) FOR BATH AND
 ARC FAULT PROTECTED CIRCUIT(S) 210.12
  
 3)NOTE: PLEASE SEE RISER DIAGRAM, NOTES
 MENTIONS: 150A PANEL W/ 150A MCB, YET
 PANEL IS SHOWN AT 200A'S WITH 3/0'S
 AS SEC'S. PLEASE VERIFY.
  
 4)NOTE: PLEASE SEE FBC CHAPTER 34
 PLEASE SUBMIT ELECTRICAL PLANS SHOWING
 ALL EXISTING MEETING CODE AND OR ELEC-
 -TRICAL TO MEET CODE COMPLIANCE TO THE
 2002 NEC. PLEASE ALSO SEE NFPA-72
 FOR SD'S.
 ADDITIONS OF MORE THAN 25%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 17:21 Rev Time 0.00
Received By shill Date 2005-06-10 Time 17:21 Sent To E
Notes
2005-06-10 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 08:18 Rev Time 0.00
Received By shill Date 2005-06-08 Time 08:18 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 12:19 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 12:19 Sent To  
Notes
2004-11-01 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 16:38 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 16:38 Sent To E
Notes
2004-08-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 15:19 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-15 Cont ID  
Sent By mmclean Date 2004-04-20 Time 10:35 Rev Time 0.00
Received By csiegber Date 2004-04-15 Time 14:07 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-08-26 Cont ID  
Sent By kstevens Date 2004-08-21 Time 13:49 Rev Time 0.15
Received By pkrauss Date 2004-08-26 Time 15:37 Sent To B
Notes
2004-08-26 00:00:00NO CHANGES TO ORIGIANL PLANS THAT WERE
 APPROVED 4-27-04

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-27 Cont ID  
Sent By pschmitz Date 2004-04-26 Time 10:49 Rev Time 0.30
Received By pkrauss Date 2004-04-27 Time 06:52 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2004-08-21 Cont ID  
Sent By dpalmer Date 2004-08-19 Time 14:11 Rev Time 0.25
Received By kstevens Date 2004-08-21 Time 13:49 Sent To M
Notes
2004-08-21 00:00:00NO PLUMBING PLANS SUBMITTED, ALL WORK
 PER CITY CODES SUBJECT TO FIELD INSPECT-
 OR'S APPROVAL

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-04-26 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 10:12 Rev Time 2.00
Received By pschmitz Date   Time   Sent To M
Notes
2004-04-24 00:00:00PROVISO: PLUMBING.
 NO PLANS, ALL WORK TO CITY CODE.
 SUBJECT TO FIELD INSPECTOR APPROVAL.
 END OF COMMENTS 561-805-9992

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-10 Cont ID  
Sent By mmclean Date 2005-06-10 Time 11:40 Rev Time 0.00
Received By mmclean Date 2005-06-10 Time 11:40 Sent To I
Notes
2005-06-10 00:00:00DENIED,
 1. MUST HAVE THE SETBACK OF THE
 GENERATOR ON TWO COPY OF SURVEYS.
 2. SETBACKS MUST SHOW FROM THE STRUCTURE
 AND PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-15 Time 14:08 Rev Time 0.00
Received By mmclean Date 2004-04-20 Time 10:35 Sent To I
Notes
***NONE***