Plan Review Details - Permit 04041179
Plan Review Stops For Permit 04041179
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-23 Cont ID  
Sent By shill Date 2004-08-23 Time 14:11 Rev Time 0.50
Received By shill Date 2004-08-23 Time 14:11 Sent To  
Notes
2004-08-23 00:00:00REVISED SHEETS A2.0, A2.1, A3.0, A6.1
 DATED 8/13/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By shill Date 2004-06-17 Time 16:09 Rev Time 1.00
Received By shill Date 2004-06-17 Time 15:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By jwitmer Date 2004-05-14 Time 10:19 Rev Time 3.00
Received By jwitmer Date 2004-05-14 Time 10:19 Sent To PC
Notes
2004-05-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041179
 ADD: 515 N FLAGLER DR# 1200
 CONT: HOLT LEE CONSTRUCTION
 TEL: (954)725-4881
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS DO NOT INDICAE AN ELEVATOR
 LOBBY. HIGH RISE REQUIRES ALL ROOMS AND
 ENCLOSURES SHALL HAVE AT LEAST ONE
 REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL
 THROUGH THE ELEVATOR LOBBY.EXIT STAIRWAY
 CHUTES, JANITOR CLOSETS, GUEST ROOMS,
 SERVICE ROOMS, ETC, SHALL NOT OPEN INTO
 THE ELEVATOR LOBBY.
 SEE 412.6.3 FOR SMOKE DETETORS.
  
 3) ENTRY DOORS TO THE RECEPTION AREA
 BLOCK THE EGRESS
 CORRIDOR(1200),1012.1.4DURING ITS
 SWING, ANY DOOR IN A MEANS OFEGRESS
 SHALL LEAVE UNOBSTRUCTED AT LEAST1/2 OF
 THE REQUIRED WIDTH OF THE CORRIDOR. MINI
 MUM CLEAR WIDTH OF 22" IS REQUIRED.
  
 4) TYPE I/II BUILDING REQUIRES ALL WOOD
 BACKING OR BLOCKING TO BE FIRE RESISTANT
 TREATED WOOD, 609.1.2.
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 DOOR TO OFFICE 1220 REQUIRES 12" ON THE
 PUSH SIDE, CAGED AREA AND OFICE 1231
 REQUIRE 18" PULL SIDE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-08-26 Cont ID  
Sent By dpalmer Date 2004-08-26 Time 13:18 Rev Time 0.50
Received By dpalmer Date 2004-08-26 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-22 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 07:59 Rev Time 0.25
Received By dpalmer Date 2004-06-22 Time 07:55 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-24 Cont ID  
Sent By dpalmer Date 2004-05-24 Time 08:32 Rev Time 0.33
Received By dpalmer Date 2004-05-24 Time 08:32 Sent To  
Notes
2004-05-24 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE ATTACHED COPY PRINT/
 OUT FROM DBPR. SHOWS LICENSE AS BEING
 DELINQUENT FOR FIRM.
 EXPIRED FEB/2003
  
 2)NOTE: PLEASE PROVIDE A SIGNED, DATED
 AND SEALED NOTORIZED LETTER FOR
 SIGNATURE TO HAVE ON FILE. ONCE THIS
 LETTER IS ON FILE WE WILL NO LONGER NEED
 LETTER FOR FUTURE REVIEWS.
  
  
 PLEASE SEE FS 471.025 REQUIRES A FULL
 SIGNATURE CONTAINING A MIN OF FIRST
 AND LAST NAME. PLEASE SEE THIS IS REQ'D
 FOR ALL TRADES WHEATHER OR NOT COMMENT
 IS MADE FROM OTHER REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-21 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 06:22 Rev Time 0.50
Received By dpalmer Date 2004-04-21 Time 06:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-09-14 Cont ID  
Sent By nmccray Date 2004-09-14 Time 10:55 Rev Time 0.00
Received By nmccray Date 2004-09-14 Time 10:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-20 Cont ID  
Sent By mcarsill Date 2004-05-20 Time 13:20 Rev Time 0.00
Received By mcarsill Date 2004-05-20 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-16 Cont ID  
Sent By mcarsill Date 2004-04-16 Time 14:37 Rev Time 0.00
Received By mcarsill Date 2004-04-16 Time 14:37 Sent To  
Notes
2004-04-16 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION SHALL COMPLY WITH
 NFPA 241.
  
 2) DEMOLITION DEBRIS SHALL BE
 REMOVED FROM THE BUILDING DAILY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 11:00 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 11:00 Sent To M
Notes
2004-08-31 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 11:57 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 11:57 Sent To  
Notes
2004-08-16 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-05-19 Time 14:15 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 14:15 Sent To  
Notes
2004-05-19 00:00:00TO COMM BD#33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-14 Cont ID  
Sent By jwitmer Date 2004-05-14 Time 12:18 Rev Time 0.00
Received By jwitmer Date 2004-04-16 Time 08:51 Sent To PC
Notes
2004-04-16 00:00:00TO COMM BD#2

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-09-01 Cont ID  
Sent By pkrauss Date 2004-09-01 Time 15:15 Rev Time 0.00
Received By pkrauss Date 2004-09-01 Time 14:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-08-31 Time 11:00 Rev Time 0.45
Received By pkrauss Date 2004-08-30 Time 06:50 Sent To  
Notes
2004-08-30 00:00:00DENIED:
 ONLY ONE COPY OF MECHANICAL REVISION
 SUBMITTED PER 2001 FBC 104.2.1, A
 MINIMUM OF 2 COPIES ARE REQUIRED FOR
 SUBMITTAL.
  
 PLEASE NOTE, PLAN SHEETS M-1 & M-3 WERE
 SUBMITTED FOR REVISION.PLAN WAS CODE
 COMPLIANT.CITY WILL RETAIN THE ONE
 APPROVED COPY FOR OUR RECORDS.RESUBMIT
 ADDITIONAL COPY FOR APPROVAL FOR
 CONTRACTOR'S COPY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-08 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 07:59 Rev Time 0.40
Received By pkrauss Date 2004-06-08 Time 11:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-27 Cont ID  
Sent By pkrauss Date 2004-04-27 Time 07:54 Rev Time 0.55
Received By pkrauss Date 2004-04-27 Time 07:31 Sent To  
Notes
2004-04-27 00:00:00DENIED:
 PLAN SHEET M-2 INDICATES NEW PVC
 CONENSATE LINES TO RISER.PVC IS NOT
 PERMITTED IN THE RETURN AIR PLENUM PER
 2001 FBC(M) 602.2.1.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-08-26 Cont ID  
Sent By kstevens Date 2004-08-26 Time 18:52 Rev Time 0.50
Received By kstevens Date 2004-08-26 Time 18:52 Sent To  
Notes
2004-08-26 00:00:00REVISION OK - CHANGED LOCATION OF SINK
 IN BREAKROOM - CHANGED ROUTING OF SANT.
 AND WATER LINES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-06-21 Cont ID  
Sent By kstevens Date 2004-06-21 Time 18:33 Rev Time 0.33
Received By kstevens Date 2004-06-21 Time 18:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 17:19 Rev Time 0.33
Received By kstevens Date 2004-06-05 Time 17:19 Sent To  
Notes
2004-06-05 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 CERTIFICATE OF AUTHORIZATION IS DELIN-
 QUENT. UPDATE CA AND RESUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By kstevens Date 2004-04-28 Time 10:57 Rev Time 0.75
Received By kstevens Date 2004-04-28 Time 10:57 Sent To  
Notes
2004-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1.0 ALL CAPPED AND DEMO'D PIP-
 ING SHALL BE INSPECTED PRIOR TO COVERING
 2) SHTS A-2.1 AND A-3.0 FLOOR PLAN INDI-
 CATES DETAIL DETAIL 08 BUT NO DETAIL
 08 SHOWN ON SHT A-3O. BREAK ROOM SINK
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAIL SHOWING
 CLEAR FLOOR SPACE, HEIGHT AND CLEARANCES
 EXPOSED PIPES AND SURFACES, ECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]