Plan Review Details - Permit 04041174
Plan Review Stops For Permit 04041174
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-01 Cont ID  
Sent By alange Date 2005-08-01 Time 13:38 Rev Time 1.00
Received By alange Date 2005-08-01 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By alange Date 2005-03-08 Time 13:53 Rev Time 1.25
Received By alange Date 2005-03-08 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-11-04 Cont ID  
Sent By alange Date 2004-11-04 Time 09:34 Rev Time 1.00
Received By alange Date 2004-11-04 Time 09:34 Sent To  
Notes
2004-11-04 00:00:00DENIED
 PRODUCT APPROVALS MISSING FOR WINDOWS.
 SUBMIT 2 COPIES.TWO DIFFERENT DOOR
 APPROVALS SUBMITTED, SPECIFY APPROVAL
 YOU ARE USEING.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.PRODUCT APPROVALS SUBMITTED REQUIRE
 A HISTORICAL REVIEW. PLEASE SUBMIT TO
 HISTORICAL FOR REVIEW PRIOR TO
 SUBMITTING TO BUILDING DEPARTMENT FOR
 REVIEW.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-02 Cont ID  
Sent By alange Date 2004-07-02 Time 13:34 Rev Time 0.66
Received By alange Date 2004-07-02 Time 13:34 Sent To  
Notes
2004-07-02 00:00:00DENIED
 SEE NOTES ATTACHED FROM PREVIOUS REVIEW.
 NONE OF THE COMMENTS HAVE BEEN ADDRESSED
 SEE OTHER REVIEWERS NOTES.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-29 Cont ID  
Sent By dpalmer Date 2004-07-02 Time 09:51 Rev Time 0.75
Received By alange Date 2004-04-29 Time 08:01 Sent To  
Notes
2004-04-29 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.NO PRODUCT APPROVALS SUBMITTED.
 SUBMIT 2 COPIES FOR, EXTERIOR DOORS,
 WINDOWS, IMPACT PROTECTION AND ROOFING.
  
 4.ENERGY CALCS NOT SIGNED BY OWNER/AGENT
  
 5.BUILDING VALUATION OF $4,000 IS TOO
 LOW BASED UPON SBCCI BUIDING VALUATION
 DATA.VALUE HAS BEEN ADJUSTED AND
 ADDITIONAL PERMIT FEES ARE DUE.
 A/C LIVING AREA 150 SF X 76.96=$11,544
 OTHER 50SF. X $41.60 = $2080
 TOTAL REVISED VALUATION IS $13,642
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-07-20 Cont ID  
Sent By dpalmer Date 2005-07-20 Time 16:23 Rev Time 0.33
Received By dpalmer Date 2005-07-20 Time 16:23 Sent To P
Notes
2005-07-20 00:00:00PLANS REDLINED 210.11C3
 20A,#12
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 16:32 Rev Time 0.40
Received By dpalmer Date 2005-04-11 Time 16:17 Sent To P
Notes
2005-04-11 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SEE FS 471.025 AND FAC
 61G15-23.002, WHICH REQUIRES PLANSTO
 BE SIGNED WITH AN ORIGINAL SIGNATURE.
 PLEASE SEE PLANS AHVE NOW COME BACK IN
 WITH A "RUBBER STAMP" FOR ENGINEER'S
 SIGNATURE.
 PLEASE SEE ONE SET IS ONCE AGAIN
 RETAINED FOR FILE AND WILL NOW BE TURNED
 OVER TO THE FBPE'S FOR REVIEW OF SAID
 VIOLATIONS. PLEASE SEE THESE PLANS WILL
 ALSO BE SENT WITH PREVIOUS RETAINED
 PLANS AND PLANS FROM OTHER PROJECTS WITH
 THE SAME COMMENTS.
  
 2)NOTE: PLEASE SEE TITLE BLOCK SHOWS 304
 37TH =ST AND THE ADDRESS IS INDEED, 904
 37TH ST.
  
 3)NOTE: PLEASE SEE THE 4X FEE WHICH WAS
 ACCESSED ON PREVIOUS REVIEW DUE TO
 REPEATED CODE COMPLIANCE VIOLATIONS WAS
 NOT PAID WHEN PLANS WERE RE-SUBMITTED.
 PLEASE SEE FS 553.80(2)(B) WHICH
 REQUIRES THIS FEE TO BE PAID "BEFORE"
 PLANS MAY BE RE-SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-02-24 Cont ID  
Sent By dpalmer Date 2005-02-24 Time 07:20 Rev Time 0.25
Received By dpalmer Date 2005-02-24 Time 07:19 Sent To P
Notes
2005-02-24 00:00:00************ UNSAT 3RD REVIEW *********
  
 1)NOTE: PLEASE SEE PLANS HAVE COME BACK
 IN W/OUT ANY CHNAGES MADE TO PLANS FOR
 PREVIOUS COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE A NOTICE WAS GIVEN FOR FS
 553.80(2)(B) ON PREVIOUS REVIEW.
 THIS 4X FEE FOR PLAN REVIEWHAS NOW
 BEEN ACCESSSED TO THE DESIGN
 PROFESSIONAL. THIS AMOUNT OF $327.40
 MUST BE PAID BEFORE PLANS ARE
 RESUBMITTED.
 PLEASE SEE ONE SET OF PLANS ARE NOW
 BEING RETAINED FOR FILE FOR POSSIBLE
 REVIEW BY THE FBPE'S.
  
 PLEASE SEE THE FS 553..80(2)(B) IS NOW
 ATTACHED ONCE MORE. IFPLANS COME BACK
 IN AGAIN WITH THE SAME COMMENTS THEN AN
 ADDITIONAL 4X FEE BE ACCESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-10-27 Cont ID  
Sent By dpalmer Date 2004-10-27 Time 06:13 Rev Time 0.25
Received By dpalmer Date 2004-10-27 Time 06:11 Sent To P
Notes
2004-10-27 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE SAME PLANS WERE
 SUBMITTED BACK WITHOUT AN CORRECTIONS
 MADE. SHEETS HAVE BEEN VOIDED.
 **PLEASE SEE COMMENTS FROM PREVIOUS
 REVIEW.
  
 2)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. THIS IS A NOTICE GIVEN
 AT THIS TIME. IF PLANS COME BACK IN
 WITH ANY OF THE SAME CODE COMMENTS,
 A 4X FEE SHALL BE ISSUED FOR PLAN
 REVIEW PORTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:40 Rev Time 0.33
Received By dpalmer Date 2004-07-02 Time 09:51 Sent To B
Notes
2004-07-02 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS NOW HAVE WHITE-
 -OUT ON PLANS MAKING CHANGES TO SIGNED
 AND SEALED PLANS . FS 471.025
  
 2)NOTE: PLEASE SEE REDLINES FROM PRE-
 -VIOUS PLANS THAT NOW NEED TO BE CORRECT
 -ED SINCE PLANS ARE GOING BACK OUT.
  
 3)NOTE: PLEASE VERIFY IF SERVICE SHOWN
 IS NEW OR EXISTING?
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 IF SERVICE IS NEW.
  
 4)NOTE: PLEASE SEE OCP FOR 10KW 424.3B
  
 5)NOTE: PLEASE SEE 210.11C3, 210.70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-23 Cont ID  
Sent By alange Date 2004-04-22 Time 13:28 Rev Time 0.25
Received By dpalmer Date 2004-04-23 Time 19:20 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-06-16 Cont ID  
Sent By adarroug Date 2006-06-16 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 15:09 Sent To P
Notes
2006-06-16 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 09:40 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 09:40 Sent To E
Notes
2005-07-20 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 09:12 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 09:12 Sent To E
Notes
2005-04-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 10:09 Sent To E
Notes
2005-02-22 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date   Time 13:39 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 13:39 Sent To E
Notes
2004-10-25 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 09:01 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 09:01 Sent To P
Notes
2004-06-23 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 13:28 Rev Time 0.00
Received By alange Date 2004-04-22 Time 13:28 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-16 Time 08:56 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 15:26 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-27 Cont ID  
Sent By pschmitz Date 2004-04-26 Time 10:48 Rev Time 0.10
Received By pkrauss Date 2004-04-27 Time 06:46 Sent To B
Notes
2004-04-27 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 FORM 600C INDICATES NO HVAC.

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-07-30 Cont ID  
Sent By jleech Date 2005-07-30 Time 14:10 Rev Time 0.33
Received By jleech Date 2005-07-30 Time 14:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-04-14 Cont ID  
Sent By kstevens Date 2005-04-14 Time 06:53 Rev Time 0.25
Received By kstevens Date 2005-04-14 Time 06:53 Sent To B
Notes
2005-04-14 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ENGINEER SHALL SIGN HIS SIGNATURE.
 THE SIGNATURE IS A STAMP WHICH IS NOT
 APPROVED. SEE ELECTRICAL REVIEW.
 FAC 61G15-23.002 & FS 471.025
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-03-05 Cont ID  
Sent By kstevens Date 2005-03-05 Time 07:44 Rev Time 0.25
Received By kstevens Date 2005-03-05 Time 07:44 Sent To B1
Notes
2005-03-05 00:00:00DENIED
  
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 1) COMMENT FROM PREVIOUS REVIEW HAS NOT
 BEEN ADDRESSED. THIS THE THIRD TIME FOR
 THE SAME COMMENT AND PER FS 553.80(2)(B)
 AN ADDITIONAL 4 TIMES THE FEE FOR PLAN
 REVIEW HAS BEEN ADDED FOR THE DESIGN
 PROFESSIONAL. (ALSO SEE ELECTRICAL
 REVIEWERS COMMENTS). NO WHITE OUT IS
 ALLOWED ON THE SIGNED/SEALED/DATED PLANS
 PER SECTION 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-11-03 Cont ID  
Sent By kstevens Date 2004-11-03 Time 07:56 Rev Time 0.25
Received By kstevens Date 2004-11-03 Time 07:56 Sent To B
Notes
2004-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) COMMENT FROM PREVIOUS REVIEW NOT
 ADDRESSED. - WHITE OUT IS NOT APPROVED
 ON PLANS SUBMITTED FOR PUBLIC RECORD AND
 ON SIGNED AND SEALED PLANS. SECTION
 104.2.1.3.
 2) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-01 Cont ID  
Sent By dpalmer Date 2004-10-27 Time 06:13 Rev Time 0.75
Received By jleech Date 2004-07-01 Time 17:52 Sent To B
Notes
2004-07-01 00:00:00SIGNED AND SEALED DRAWINGS CANNOT BE
 ALTERED WITH WHITEOUT.SEE WPB
 ADMINASTATION CODE SEC.104.2.1.3.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-06-23 Time 09:01 Rev Time 1.00
Received By pschmitz Date 2004-04-24 Time 11:27 Sent To M
Notes
2004-04-24 00:00:00PLNBING PLAN REVIEW: DENIED FPC 2001
 SHOWER COMPARTMENT MINIMUM 30" ,SIDE OF
 RECTANGLE, INSIDE DEMINSION, SEC 417.4
 BATH ROOM: INSIDE DEMINSIONS COMPLY
 WITH SEC 405,FIXTURE SPACING.
 ROOM NEEDS TO BE AT LEAST 4" WIDER FOR
 PROPER SPACING OF PLUMBING FIXTURES.
 END OF COMMENTS 561-805-6692

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-22 Cont ID  
Sent By csiegber Date 2004-04-20 Time 15:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***