Plan Review Details - Permit 04041127
Plan Review Stops For Permit 04041127
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-05-05 Cont ID  
Sent By rmcdouga Date 2005-05-05 Time 10:22 Rev Time 0.00
Received By rmcdouga Date 2005-05-05 Time 10:22 Sent To  
Notes
2005-05-05 00:00:00REVISION TO SHEETS A6,A11 AND A12 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-03-01 Cont ID  
Sent By rmcdouga Date 2005-03-01 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2005-03-01 Time 09:26 Sent To  
Notes
2005-03-01 00:00:00REVISED SHEETS A1,A6,A7,A8,A9,A10,A11
 AND A12 ARE OK. ALL BUILDINGS
 CONSTRUCTED UNDER THIS MASTER ARE
 REQUIRED TO MATCH THE PLANS AS REVISED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status N Date 2004-12-20 Cont ID  
Sent By rmcdouga Date 2004-12-20 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2004-12-20 Time 14:13 Sent To  
Notes
2004-12-20 00:00:00BUILDING REVISIONS DENIED
  
 1) ON SHEET A8 DETAIL 11 ON A11 IS
 SPECIFIED FOR THE TRUSS CONNECTION. THE
 CONNECTOR THAT IS SPECIFIED IS A USP
 HLPA 75, WHICH WAS DELETED FROM THE
 REVISED CONNECTOR SCHEDULE. ON SHEET A10
 A TC-2 CONNECTOR IS SPECIFIED FOR AT THE
 SAME TRUSS LOCATION. PLEASE CLARIFY.
  
 2) IN SEVERAL LOCATIONS ON SHEET A10 THE
 LISTED UPLIFT EXCEEDS THE CAPACITY OF
 THE SPECIFIED TRUSS CONNECTOR. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status N Date 2004-11-17 Cont ID  
Sent By rmcdouga Date 2004-11-17 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2004-11-17 Time 07:01 Sent To  
Notes
2004-11-17 00:00:00SHOP DRAWINGS FOR FILIGREE FLOOR SYSTEM
 ARE OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status N Date 2004-11-09 Cont ID  
Sent By rmcdouga Date 2004-11-09 Time 12:57 Rev Time 0.00
Received By rmcdouga Date 2004-11-09 Time 12:57 Sent To  
Notes
2004-11-09 00:00:00DENIED
  
 1) THE LIVE LOAD FOR THE BALCONY AREAS
 CAN NOT BE LESS THAN 60 PSF PER FBC
 TABLE 1604.1.
  
 2) REDLINE CHANGES TO SIGNED AND SEALED
 DRAWINGS ARE REQUIRED TO BE INITIALED
 AND DATED BY THE DESIGNER OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-08-26 Cont ID  
Sent By rmcdouga Date 2004-08-26 Time 09:01 Rev Time 0.00
Received By rmcdouga Date 2004-08-26 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-19 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2004-08-11 Time 15:35 Sent To  
Notes
2004-08-11 00:00:00DENIED
  
 1) ON SHEET A-9 THE LOWER ROOF PLAN, THE
 LEFT SIDE OF THE PLAN DOES NOT MATCH THE
 TRUSS LAYOUT DRAWING.
  
 2) ON SHEET A-9 THE B7 TRUSS ON THE LEFT
 SIDE HAS CONNECTORS SPECIFIED THAT DO
 NOT MEET THE UPLIFTS ON THE TRUSS
 DRAWINGS.
  
 3) TRUSSES B22, B23, B24 AND B28 ON THE
 RIGHT SIDE OF SHEET A-9 DO NOT HAVE
 ADEQUATE CONNECTORS.
  
 4) ON THE SECOND FLOOR ROOF PLAN ON
 SHEET A-10, THE PLANS INDICATE ONE HIP
 AND ONE GABLE AT THE FRONT OF THE
 BUILDING. THE TRUSS LAYOUT SHOWS BOTH AS
 HIP ROOFS. PLEASE CORRECT.
  
 5) ON A-10 TRUSS A29 HAS AN UPLIFT OF
 5345# ON THE TRUSS DRAWINGS AND 5070# ON
 THE PLANS.
  
 6) THE CONNECTOR FOR TRUSS A12 ON THE
 RIGHT SIDE OF SHEET A-10, HAS THE WRONG
 TAG. IT SHOULD BE A TC-8 NOT TC-3.
  
 7) ON A-10 TRUSS A8 HAS A CONNECTOR THAT
 DOES NOT MEET THE UPLIFT SPECIFIED ON
 THE TRUSS DRAWINGS.
  
 8) ON A-10 TRUSS A29 HAS AN UPLIFT OF
 5070# SPECIFIED AND THE TRUSS DRAWINGS
 LIST AN UPLIFT OF 5345#.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-08-10 Time 10:43 Rev Time 2.00
Received By rmcdouga Date 2004-08-05 Time 11:07 Sent To  
Notes
2004-08-05 00:00:00TRUSSES DENIED
  
 1) LOWER ROOF PLAN HAS THE CONNECTOR FOR
 THE AT4 GIRDER TRUSS SPECIFIED IN THE
 WRONG LOCATION ON SHEET A9.
  
 2) THE UPLIFT IN THE TRUSS DRAWINGS FOR
 TRUSSES AT16, AT19 AND AT20 EXCEED THE
 CONNECTORS SPECIFIED FOR THEM ON SHEET
 A9.
  
 3) THE UPPER ROOF PLAN ON SHEET A10 DOES
 NOT CORRESPOND TO THE TRUSS LAYOUT. SEE
 TRUSSES BT 12 AND BT 20 ON LAYOUT. TRUSS
 BT20 REQUIRES A CENTER BEARING POINT
 THAT IS NOT SHOWN ON THE PLANS.
  
 4) THE CONNECTORS SPECIFIED FOR TRUSS
 BT 48 DOES NOT MEET THE REQUIRED UPLIFTS
 ON THE TRUSS DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-27 Cont ID  
Sent By rmcdouga Date 2004-07-27 Time 13:26 Rev Time 2.00
Received By rmcdouga Date 2004-07-27 Time 13:26 Sent To  
Notes
2004-07-27 00:00:00DENIED
  
 1) NO TRUSS DRAWINGS WERE SUBMITTED.
  
 2) THE WRONG PRODUCT APPROVAL WAS
 SUBMITTED FOR THE ENTRY DOORS. THE ONE
 SUBMITTED HAS A NON-IMPACT RATED GLAZED
 STEEL DOOR WITH SIDELITES. THIS DOOR
 AND SIDELITES ARE REQUIRED TO BE
 SHUTTERED.
  
 3) IMPACT FEES AND NOTICES OF
 COMMENCEMENT WILL BE RTEQUIRED FOR EACH
 PERMIT UNDER THE MASTER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-29 Cont ID  
Sent By rmcdouga Date 2004-06-29 Time 14:05 Rev Time 4.00
Received By rmcdouga Date 2004-06-29 Time 07:27 Sent To  
Notes
2004-06-29 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. PLEASE
 SUBMIT THE STATE PRODUCT APPROVAL COVER
 SHEET WITH THE FL# FOR THE CORRESPONDING
 NOA. LOCAL OR STATE PRODUCT APPROVAL IS
 REQUIRED PER FLORIDA STATUES AND RULE 9B
 -72. NOTE: I PRINTED OUT AND ATTACHED
 THE STATE COVERSHEETS FOR THE STORM
 PANELS AND (SGD-9200) SLIDING GLASS DOOR
 AS AN EXAMPLE.
  
 4) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS FOR EACH
 OF THE 4 UNITS.
  
 5) THE LETTER FROM PALM BEACH LIFTS HAS
 THE WRONG PERMIT NUMBER. PLEASE CORRECT.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-19 Cont ID  
Sent By rmcdouga Date 2004-05-19 Time 12:53 Rev Time 6.00
Received By rmcdouga Date 2004-05-19 Time 12:53 Sent To  
Notes
2004-05-19 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) REVISE PLAN NOTE 10 ON C1. IMPACT
 PROTECTION IS REQUIRED IN WIND BORNE
 DEBRIS REGIONS PER FBC 1606.1.4.
  
 4) SPECIFY THAT THE DOORS FROM THE
 GARAGE TO THE UNITS ARE REQUIRED TO BE
 3/4 HOUR FIRE RATED DOORS WITH CLOSERS.
 SEE FBC 705.1.3.
  
 5) THE WALLS BETWEEN THE GARAGES AND THE
 HABITABLE SPACE ARE REQUIRED TO BE ONE
 HOUR FIRE RATED PER FBC 411.2.6 AND 704.
  
 6) THE WALLS BETWEEN THE GARAGES AND THE
 CONDITIONED SPACE IS REQUIRED TO BE
 INSULATED PER FBC CHAPTER 13.
  
 7) THE TITLE BLOCKS ON THE PLANS CONTAIN
 INCORRECT INFORMATION. THE BUILDING
 NUMBER IS 22 NOT THE LOT NUMBER. THESE
 PLANS ARE NOT MASTERED.
  
 8) SHOW COMPLIANCE WITH FAIR HOUSING ACT
 DESIGN MANUAL. SHOW MINIMUM CLEAR FLOOR
 SPACE AT TOILET OF 48" X 56". CENTER OF
 TOLIET TO BE 18" OFF WALL. SEE PG.7.43.
  
 9) ALL DOORS IN THE UNITS OTHER THAN THE
 ENTRY DOOR, PANTRY DOOR AND MECH. ROOM
 DOOR ARE REQUIRED TO BE USABLE WITH A
 32" NOMINAL CLEAR OPENING OF AT LEAST
 31-5/8 INCH CLEAR. THIRTY-FOUR INCH DOOR
 IS REQUIRED FOR DOORS THAT OPEN LESS
 THAN 180 DEGREES. WALK-IN CLOSET DOORS
 MUST COMPLY. SEE FHADM PG. 3.5.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 STATE OR LOCAL PRODUCT APPROVALS FOR
 EXTERIOR WINDOWS, DOORS, ROOFING, GARAGE
 DOORS, STORM PANELS, TRUSS CONNECTORS,
 ETC.
  
 11) PRODUCT APPROVAL FOR IMPACT SLIDING
 GLASS DOOR IS LIMITED TO MAXIMUM WIDTH
 OF 8' AND DOES NOT WORK FOR 10'WIDE DOOR
 SPECIFIED ON THE PLANS.
  
 12) SUBMIT KEY PLANS AND INSTALLATION
 SCHEDULES FOR THE STORM PANLES.
  
 13) THE MISSLE IMPACT PROTECTION
 INSTALLATION PLAN NEEDS TO BE SIGNED AND
 NOTARIZED. IT MUST ALSO BE APPROVED BY
 THE BUILDING OFFICIAL.
  
 14) THE ENGINEERING SUBMITTED FOR THE
 BALCONY RAILS AND SCREEN DO NOT MATCH
 THE PLANS.
  
 15) THE LETTER FROM PALM BEACH LIFTS
 NEEDS TO HAVE AN ORIGINAL SIGNATURE.
  
 16) PLEASE SUBMIT TWO COPIES OF ALL
 ITEMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By dpalmer Date 2004-08-02 Time 13:14 Rev Time 0.25
Received By dpalmer Date 2004-08-02 Time 13:13 Sent To  
Notes
2004-08-02 00:00:00REDLINED EQUIPMENT GRNDS MISSING.
 250.24,250.110

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-21 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 06:47 Rev Time 0.50
Received By dpalmer Date 2004-04-21 Time 06:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-08-02 Cont ID  
Sent By mamini Date 2004-08-02 Time 13:49 Rev Time 0.50
Received By mamini Date 2004-08-02 Time 13:49 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-04-19 Cont ID  
Sent By mamini Date 2004-04-19 Time 15:00 Rev Time 1.00
Received By mamini Date 2004-04-19 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-08-10 Cont ID  
Sent By mcarsill Date 2004-08-10 Time 14:27 Rev Time 0.00
Received By mcarsill Date 2004-08-10 Time 14:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By mcarsill Date 2004-06-22 Time 10:26 Rev Time 0.00
Received By mcarsill Date 2004-06-22 Time 10:26 Sent To  
Notes
2004-06-22 00:00:001) BUILDING ADDRESSES ARE REQUIRED TO
 BE POSTED SO POLICE, FIRE AND
 PARAMEDICAL EQUIPMENT CAN LOCATE THE
 PROPERTIES IN THE EVENT OF AN
 EMERGENCY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By mcarsill Date 2004-04-28 Time 10:08 Rev Time 0.00
Received By mcarsill Date 2004-04-28 Time 10:08 Sent To  
Notes
2004-04-28 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) EGRESS WINDOWS ARE REQUIRED.
  
 4) BUILDING ADDRESSES ARE REQUIRED.
  
 5) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED IN THE MASTER SUITES
 LOCATED ON THE SECOND FLOOR ELECTRICAL
 PLAN.
  
 6) SMOKE DETECTORS ARE REQUIRED IN
 FIRST FLOOR MASTER SUITES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 11:28 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 11:28 Sent To B
Notes
2005-04-12 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-17 Time 14:33 Rev Time 0.00
Received By adarroug Date 2005-02-17 Time 16:55 Sent To B
Notes
2005-02-17 00:00:00TO RMCDOUGAL DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 16:41 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 16:41 Sent To B
Notes
2005-02-14 00:00:00TO RMCDOUGAL/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 14:31 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 14:31 Sent To B
Notes
2004-12-14 00:00:00SENT TO "ROB MCD" DESK./REV.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 16:47 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 16:47 Sent To B
Notes
2004-11-12 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 11:37 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 11:37 Sent To B
Notes
2004-11-09 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-19 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-08-19 Time 16:52 Sent To B
Notes
2004-08-19 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-10 Cont ID  
Sent By csiegber Date 2004-08-10 Time 10:43 Rev Time 0.00
Received By csiegber Date 2004-08-10 Time 10:43 Sent To B
Notes
2004-08-10 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 11:32 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 11:32 Sent To  
Notes
2004-07-21 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 12:04 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 12:04 Sent To  
Notes
2004-06-16 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-19 Cont ID  
Sent By mmclean Date 2004-04-30 Time 15:42 Rev Time 0.00
Received By rmcdouga Date 2004-04-16 Time 15:14 Sent To  
Notes
2004-04-16 00:00:00TO COMM BD#48

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-03 Cont ID  
Sent By pkrauss Date 2005-03-03 Time 14:03 Rev Time 0.35
Received By pkrauss Date 2005-03-03 Time 13:50 Sent To  
Notes
2005-03-03 00:00:00PROVISO:
 DRYER EXHAUST SHALL COMPLY WITH 2001
 FBC(M)504.6 AND TERMINATE IN SUCH A
 MANNER AS NOT TO BE RECIRCULATED INTO
 FRESH AIR INTAKES OR CREATE A NUISANCE
 (2001 FBC(M)401.5.2 & 501.3).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-01 Cont ID  
Sent By pkrauss Date 2004-07-01 Time 08:46 Rev Time 0.40
Received By pkrauss Date 2004-07-01 Time 07:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-24 Cont ID  
Sent By pkrauss Date 2004-04-24 Time 09:51 Rev Time 0.40
Received By pkrauss Date 2004-04-24 Time 09:42 Sent To  
Notes
2004-04-24 00:00:00DENIED:
 1.PER 2001 FBC(M) 403.3, OUTSIDE AIR
 REQUIRED FOR MULTI-FAMILY DWELLINGS IN
 ACCORDANCE WITH TABLE 403.3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M) 307.
 2.3.
  
 3.MECHANICAL PLAN INDICATES AHU
 LOCATED IN THE LAUNDRY ROOM.PLEASE
 CLARIFY THE FOLLOWING. (A) DRYER -
 ELECTRIC OR GAS. (B) IS THERE A DOOR
 SEPARATING THE AHU FROM THE DRYER (C) IS
 THE RETURN TO THE AHU DUCTED OR IS THE
 CLOSET AREA A PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-07-31 Cont ID  
Sent By kstevens Date 2004-07-31 Time 13:52 Rev Time 1.00
Received By kstevens Date 2004-07-31 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-03 Cont ID  
Sent By kstevens Date 2004-07-03 Time 12:20 Rev Time 1.00
Received By kstevens Date 2004-07-03 Time 12:20 Sent To  
Notes
2004-07-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DO NOT MEET
 CODE REQUIREMENTS, NOR DO THE RISERS
 REFLECT THE FLOOR PLANS.SHT A-14
 - CLEANOUTS SHALL BE INSTALLED AT EACH
 CHANGE OF DIRECTION OF THE BLDG. DRAIN
 GREATER THAN 45 DEGREES. SECTION 708.3.3
 - THERE SHALL BE A CLEANOUT NEAR THE
 JUNCTION OF THE BLDG. DRAIN AND BLDG.
 SEWER. (EACH TIME THE BLDG. DRAIN EXITS
 THE BLDG. - AT KITCHEN AND WHERE THE
 BATHROOMS EXIT SEPARATELY). SECTION
 708.3.5
 - RISERS A & B THE SHOWERS ARE NOT VEN-
 TED IN SECOND BATH. SECTION 901.2.1
 - PLUMBING RISERS C & D SHOWER IS NOT
 TO THE RIGHT OF THE LAV IN BATH #2 AS
 SHOWN ON THE RISER.
 - WATER CLOSET IN MASTER BATH DOES NOT
 SET TO THE RIGHT OF THE TUB AS SHOWN
 ON RISER.
 (SUGGESTION: THE PLUMBING CONTRACTOR CAN
 POSSIBLY INDICATE HOW IT WILL BE INST-
 ALLED AND DRAW A RISER THAT REFLECTS THE
 INSTALLATION).
 2) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By kstevens Date 2004-04-28 Time 14:09 Rev Time 1.25
Received By kstevens Date 2004-04-28 Time 13:42 Sent To  
Notes
2004-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 DESIGN MANUAL
  
 1) SHT A-2 SHOW CLEAR FLOOR SPACE OF THE
 WATER CLOSETS AS SHOWN ON PAGE 7.43. -
 EIGHER 48"X66", 48"X56", OR 60"X56".
 2) SHT A-2 WATER CLOSETS IN BATHROOMS
 SHALL BE 18" OFF WALL. SEE PAGE 7.43,
 EXAMPLES 1, 2, OR 3. SHOW ON FLOOR PLAN.
 3) SHT A-14 PLUMBING RISERS A & B. CLEAN
 OUTS ARE REQUIRED WHERE BLDG DRAIN EXITS
 BUILDING AT KITCHEN AND AFTER WASH
 MACHINE. - SANITARY CROSS FITTINGS ARE
 NOT APPROVED ON HORIZONTAL BUILDING
 DRAINS.
 4) SHT A-14 PLUMBING RISERS C & D DO NOT
 REFLECT THE FLOOR PLAN. SHOWER IS NOT TO
 THE RIGHT OF THE LAV IN BATH #2. KITCHEN
 SINK IS NOT TO THE RIGHT OF BATH #2.
 WATER CLOSET IN MASTER BATH DOES NOT SET
 TO THE RIGHT OF THE TUB.
 5) SHT A-14 PLUMBING RISERS C & D. THE
 WASH MACHINE AND KITCHEN SINK SHALL NOT
 DRAIN THROUGH THE WET VENTED HORIZONTAL
 DRAIN FOR BATH #2. SECTION 909.1.
 THE W/M AND KITCHEN SINK SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT HORIZONTAL
 DRAIN LINE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-30 Cont ID  
Sent By mmclean Date 2004-04-30 Time 15:42 Rev Time 0.00
Received By mmclean Date 2004-04-30 Time 15:42 Sent To I
Notes
2004-04-30 00:00:00OK PER GRACE JOYCE, PLANNER 659-8031