| Plan Review Stops For Permit 04041087 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-10-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-10-22 |
Time |
13:20 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-10-22 |
Time |
13:20 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2004-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-10-22 |
Time |
11:57 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-10-05 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2004-10-05 00:00:00 | ****CORRECTIONS**** | | | REVISION DATED 9/23/04 | | | | | | 1.)CHANGES MADE IN INK BY THE | | | ARCHITECT WERE NOT ON SHEET A1.THE | | | PLAN AS SUBMITTED IS NOT CODE COMPLIANT; | | | SEE APPROVED PERMIT SET. | | | | | | 2.)WHAT CHANGES WERE DONE?NO CHANGES | | | WERE INDICATED ON A1; NO NUMBER ASSIGNED | | | TO "AS-BUILT CONDITIONS 8/31/04". | | | | | | 3.)SEE PLUMBING PROVISO REQUIRING A | | | REVISION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-06-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-06-14 |
Time |
10:04 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-06-14 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-06-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-06-10 |
Time |
10:20 |
Rev Time |
1.50 |
| Received By |
shill |
Date |
2004-06-10 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2004-06-10 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PLEASE CLOUD ALL CHANGES.THE NOTE | | | IN REGARDS TO THE RAILING,RAISED | | | CONFERENCE AREA, SECTION 3-A1 WERE | | | MODIFIED AND NOT INDICATED. | | | | | | 2.)THE RAMP HANDRAILS ARE TO COMPLY | | | WITH FBC1013.7, SHALL EXTEND AT LEAST | | | 18" BEYOND THE TOP AND BOTTOM OF THE | | | RAMP SEGMENT AND SHALL BE PARALLEL WITH | | | THE FLOOR OR GROUND SURFACE.EXTENSION | | | CANNOT ENCROACH UPON 60"X60" LANDING | | | SIZE REQUIRED BY FBC11-4.8.4(3). | | | | | | 3.)SEE PREVIOUS LIST, ITEM #7, IN | | | REGARDS TO FIRE RATED WALLS.THE WALL | | | INDICATED DOES NOT APPEAR TO BE | | | REQUIRED FIRE RATED WALL, SEE PLAN. | | | REVISE. | | | | | | 4.)SEE PLUMBING PROVISO.PLEASE | | | ADDRESS AT THIS TIME. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-05-14 |
Time |
16:23 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2004-05-14 |
Time |
13:44 |
Sent To |
PC |
|
| Notes |
| 2004-05-14 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04041087 | | | ADD: 201 S NARCISSUS AV# 1 | | | CONT: WELLINGTON REMODELING INC | | | TEL: (561)722-7195 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) 11-4.8.2 SLOPE & RISE. THE LEAST | | | POSSIBLE SLOPE SHALL BE USED FOR ANY | | | RAMP. THE MAXIMUM SLOPE FOR A RAMP IN | | | NEW CONSTRUCTION SHALL BE 1 TO 12. THE | | | MAXIMUM RISE FOR RUN SHALL BE 30" (SEE | | | FIGURE 16). | | | | | | 3)11-4.8.3. CLEAR WIDTH. THE MINIMUM | | | CLEAR WIDTH OF A RAMP SHALL BE 36". | | | EXCEPTION: RAMPS THAT ARE PART OF A | | | REQUIRED MEANS OF EGRESS SHALL NOT BE | | | LESS THAN 44 INCHES WIDE. | | | | | | 4)11-4.8.4.(2) LANDINGS. ALL LANDINGS | | | ON RAMPS SHALL NOT BE LESS THAN 60" | | | CLEAR, & THE BOTTOM OF EACH RAMP SHALL | | | HAVE NOT LESS THAN 72" OF STRAIGHT & | | | LEVEL CLEARENCE. | | | | | | 5)11-4.8.4(3) IF RAMPS CHANGE DIREC- | | | TION AT LANDINGS, THE MINIMUM LANDING | | | SIZE SHALL BE 60" X 60". | | | | | | 6)11.4.8.5. HANDRAILS: IF A RAMP HAS | | | A RISE GREATER THAN 6" OR A HORIZONTAL | | | PROJECTION GREATER THAN 72", THEN IT | | | SHALL HAVE HANDRAILS ON BOTH SIDES. | | | | | | 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 8) STORAGE UNDER PLATFORM, INDICATE HOW | | | 1 HR SEPERATION WILL BE ACCOMPLISHED. | | | SEE 403.2.4.1. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-09-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2004-09-24 |
Time |
07:18 |
Rev Time |
0.15 |
| Received By |
jleahy |
Date |
2004-09-24 |
Time |
07:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-09-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-09-21 |
Time |
20:16 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-09-21 |
Time |
20:14 |
Sent To |
|
|
| Notes |
| 2004-09-21 00:00:00 | ********** UNSAT ******** | | | | | | PLEASE SEE NOTES ON PREVIOUS REDLINE. | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, STILL | | | MISSING EQUIPMENT GROUNDING AFTER THE | | | FIRST MEANS OF DISCONNECT. 250.24 | | | | | | 2)NOTE: PLEASE SEE ADDRESS IN TITLE | | | BLOCK IS STILL SHOWN W/ WRONG ADDRESS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-02 |
Time |
15:41 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-06-02 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2004-06-02 00:00:00 | ********* NOTES REDLINED ********** | | | | | | 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING | | | STILL NOT SHOWN AFTER THE FIRST MEANS | | | OF DISCONNECT PER 250.24. | | | | | | PLANS STILL ALSO SHOW ADDRESS AS 210 | | | NARCISSUS. SEE BLDG REVIEW COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-04-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-21 |
Time |
06:58 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-04-21 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2004-04-21 00:00:00 | ************ UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | | | | 2)NOTE: PLEASE SUBMIT MORE INFORMATION | | | ON WHAT IS SHOWN AS EXISTING TO BE | | | DETERMINED FOR FEED TO NEW 200A MAIN. | | | THE 200A MAIN SHOWN AS EXSITING DOES | | | NOT SEEM TO BE SHOWN ON BASE BLDG PLANS. | | | MORE INFORMATION/LOAD IS NEEDED. 215.5 | | | | | | 3)NOTE: PLEASE SEE 250.24/ 250.110 ETC | | | FOR EQUIPMENT GROUNDING AFTER FIRST | | | MEANS OF DISC.. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | THIS EQUIPMENT IS NOT ON BASE PLANS | | | FOR NEW EQUIPMENT. | | | | | | 5)NOTE: PLEASE SEE 210.62 FOR MIN REQ'D | | | SHOW WINDOW RECEPTS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING | | | ONE SET OF OLD MAY BE REQ'D TO BE RE- | | | -SUBMITTED BY OTHER REVIEWERS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2004-10-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-10-20 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-10-20 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-10-06 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-10-06 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-10-06 |
Time |
10:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-05-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-21 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-21 |
Time |
12:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-04-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-04-16 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-04-16 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2004-04-16 00:00:00 | 1) WHERE DOES THE REAR EXIT LEAD TO. | | | | | | 2) IF STORAGE IS PLANNED FOR UNDERNEATH | | | THE PLATFORM, IT WILL BE REQUIRED TO | | | BE FIRE SPRINKLER PROTECTED. | | | | | | 3) ALL RAMPS AND STAIRS SHALL HAVE | | | HANDRAILS ON BOTH SIDES. | | | | | | 4) PLANS DO NOT INDICATE ANY FIRE | | | ALARM EQUIPMENT. | | | | | | 5) NO INFORMATION PROVIDED REGARDING | | | THE REMODELING OF THE FIRE SPRINKLER | | | SYSTEM. | | | | | | 6) NO INFORMATION REGARDING THE | | | INTERIOR FINISH CLASSIFICATION | | | FOR WALLS AND CEILINGS. | | | | | | 7) NO INFORMATION REGARDING PORTABLE | | | FIRE EXTINGUISHERS. | | | | | | 8) PLEASE INDICATE LOCATIONS AND | | | RATINGS OF ALL TENANT SEPARATION | | | WALLS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-10-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-10-22 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2004-10-22 |
Time |
11:57 |
Sent To |
B |
|
| Notes |
| 2004-10-22 00:00:00 | OLD SET NEVER PICKED UP; STILL ON THE | | | BOARD #5.PASSED ALL REVIEWS.TOOK | | | BOTH OFF OF BOARD (#5 AND #49) AND | | | PUT ON SMH DESK.SHEETS NEED TO BE | | | SWAPPED AND ISSUED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-10-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-14 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-14 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2004-10-14 00:00:00 | TO COMM BD#49 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-09-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-17 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-17 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2004-09-17 00:00:00 | TO COMM BD#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-05-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-20 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-20 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2004-05-20 00:00:00 | TO COMM BD#20 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-20 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-14 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2004-04-14 00:00:00 | TO COMM BD#51 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-06-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-01 |
Time |
11:31 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-06-01 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-04-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-24 |
Time |
10:10 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-04-24 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2004-04-24 00:00:00 | DENIED: | | | PLEASE INDICATE IF THE SYSTEM IS TIED | | | INTO THE BUILDING FIRE ALARM SYSTEM. | | | | | | SEE ALSO COMMENTS BY ASSST FIRE MARSHAL, | | | MIKE CARSILLO. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-10-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-14 |
Time |
14:14 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-10-14 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2004-10-14 00:00:00 | REVISION/PASSED | | | | | | DELETED BREAK ROOM SINK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-06-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-05 |
Time |
16:50 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-06-05 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2004-06-05 00:00:00 | PASSED/PROVISO | | | | | | REVISION REQUIRED SHOWING A 30"X48" | | | PARALLED APPROACH CLEAR FLOOR SPACE | | | FOR LOUNGE SINK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-04-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-27 |
Time |
19:26 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-04-27 |
Time |
19:20 |
Sent To |
|
|
| Notes |
| 2004-04-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) INDICATE USE FOR NEW SINK. IF SINK | | | IS IN A BREAK ROOM/KITCHENETTE IT SHALL | | | COMPLY WITH 11-4.24 AND ALL SUBSECTIONS. | | | A DETAIL WILL BE REQUIRED. | | | 2) SUBMIT A WATER RISER DIAGRAM REQUIRED | | | PER SECTION 104.3.1.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|