Plan Review Details - Permit 04041087
Plan Review Stops For Permit 04041087
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-10-22 Cont ID  
Sent By shill Date 2004-10-22 Time 13:20 Rev Time 1.00
Received By shill Date 2004-10-22 Time 13:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-10-05 Cont ID  
Sent By shill Date 2004-10-22 Time 11:57 Rev Time 0.50
Received By shill Date 2004-10-05 Time 16:38 Sent To  
Notes
2004-10-05 00:00:00****CORRECTIONS****
 REVISION DATED 9/23/04
  
 1.)CHANGES MADE IN INK BY THE
 ARCHITECT WERE NOT ON SHEET A1.THE
 PLAN AS SUBMITTED IS NOT CODE COMPLIANT;
 SEE APPROVED PERMIT SET.
  
 2.)WHAT CHANGES WERE DONE?NO CHANGES
 WERE INDICATED ON A1; NO NUMBER ASSIGNED
 TO "AS-BUILT CONDITIONS 8/31/04".
  
 3.)SEE PLUMBING PROVISO REQUIRING A
 REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-14 Cont ID  
Sent By shill Date 2004-06-14 Time 10:04 Rev Time 0.50
Received By shill Date 2004-06-14 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-10 Cont ID  
Sent By shill Date 2004-06-10 Time 10:20 Rev Time 1.50
Received By shill Date 2004-06-10 Time 10:20 Sent To  
Notes
2004-06-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE CLOUD ALL CHANGES.THE NOTE
 IN REGARDS TO THE RAILING,RAISED
 CONFERENCE AREA, SECTION 3-A1 WERE
 MODIFIED AND NOT INDICATED.
  
 2.)THE RAMP HANDRAILS ARE TO COMPLY
 WITH FBC1013.7, SHALL EXTEND AT LEAST
 18" BEYOND THE TOP AND BOTTOM OF THE
 RAMP SEGMENT AND SHALL BE PARALLEL WITH
 THE FLOOR OR GROUND SURFACE.EXTENSION
 CANNOT ENCROACH UPON 60"X60" LANDING
 SIZE REQUIRED BY FBC11-4.8.4(3).
  
 3.)SEE PREVIOUS LIST, ITEM #7, IN
 REGARDS TO FIRE RATED WALLS.THE WALL
 INDICATED DOES NOT APPEAR TO BE
 REQUIRED FIRE RATED WALL, SEE PLAN.
 REVISE.
  
 4.)SEE PLUMBING PROVISO.PLEASE
 ADDRESS AT THIS TIME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-14 Cont ID  
Sent By jwitmer Date 2004-05-14 Time 16:23 Rev Time 1.22
Received By jwitmer Date 2004-05-14 Time 13:44 Sent To PC
Notes
2004-05-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041087
 ADD: 201 S NARCISSUS AV# 1
 CONT: WELLINGTON REMODELING INC
 TEL: (561)722-7195
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
  
 3)11-4.8.3. CLEAR WIDTH. THE MINIMUM
 CLEAR WIDTH OF A RAMP SHALL BE 36".
 EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
  
 4)11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
  
 5)11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60".
  
 6)11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 8) STORAGE UNDER PLATFORM, INDICATE HOW
 1 HR SEPERATION WILL BE ACCOMPLISHED.
 SEE 403.2.4.1.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-09-24 Cont ID  
Sent By jleahy Date 2004-09-24 Time 07:18 Rev Time 0.15
Received By jleahy Date 2004-09-24 Time 07:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 20:16 Rev Time 0.25
Received By dpalmer Date 2004-09-21 Time 20:14 Sent To  
Notes
2004-09-21 00:00:00********** UNSAT ********
  
 PLEASE SEE NOTES ON PREVIOUS REDLINE.
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, STILL
 MISSING EQUIPMENT GROUNDING AFTER THE
 FIRST MEANS OF DISCONNECT. 250.24
  
 2)NOTE: PLEASE SEE ADDRESS IN TITLE
 BLOCK IS STILL SHOWN W/ WRONG ADDRESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-02 Cont ID  
Sent By dpalmer Date 2004-06-02 Time 15:41 Rev Time 0.33
Received By dpalmer Date 2004-06-02 Time 15:40 Sent To  
Notes
2004-06-02 00:00:00********* NOTES REDLINED **********
  
 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 STILL NOT SHOWN AFTER THE FIRST MEANS
 OF DISCONNECT PER 250.24.
  
 PLANS STILL ALSO SHOW ADDRESS AS 210
 NARCISSUS. SEE BLDG REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-21 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 06:58 Rev Time 0.33
Received By dpalmer Date 2004-04-21 Time 06:58 Sent To  
Notes
2004-04-21 00:00:00************ UNSAT *********
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
  
 2)NOTE: PLEASE SUBMIT MORE INFORMATION
 ON WHAT IS SHOWN AS EXISTING TO BE
 DETERMINED FOR FEED TO NEW 200A MAIN.
 THE 200A MAIN SHOWN AS EXSITING DOES
 NOT SEEM TO BE SHOWN ON BASE BLDG PLANS.
 MORE INFORMATION/LOAD IS NEEDED. 215.5
  
 3)NOTE: PLEASE SEE 250.24/ 250.110 ETC
 FOR EQUIPMENT GROUNDING AFTER FIRST
 MEANS OF DISC..
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 THIS EQUIPMENT IS NOT ON BASE PLANS
 FOR NEW EQUIPMENT.
  
 5)NOTE: PLEASE SEE 210.62 FOR MIN REQ'D
 SHOW WINDOW RECEPTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING
 ONE SET OF OLD MAY BE REQ'D TO BE RE-
 -SUBMITTED BY OTHER REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-10-20 Cont ID  
Sent By mcarsill Date 2004-10-20 Time 16:26 Rev Time 0.00
Received By mcarsill Date 2004-10-20 Time 16:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-10-06 Cont ID  
Sent By nmccray Date 2004-10-06 Time 10:42 Rev Time 0.00
Received By nmccray Date 2004-10-06 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-21 Cont ID  
Sent By mcarsill Date 2004-05-21 Time 12:36 Rev Time 0.00
Received By mcarsill Date 2004-05-21 Time 12:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-16 Cont ID  
Sent By mcarsill Date 2004-04-16 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2004-04-16 Time 15:47 Sent To  
Notes
2004-04-16 00:00:001) WHERE DOES THE REAR EXIT LEAD TO.
  
 2) IF STORAGE IS PLANNED FOR UNDERNEATH
 THE PLATFORM, IT WILL BE REQUIRED TO
 BE FIRE SPRINKLER PROTECTED.
  
 3) ALL RAMPS AND STAIRS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 4) PLANS DO NOT INDICATE ANY FIRE
 ALARM EQUIPMENT.
  
 5) NO INFORMATION PROVIDED REGARDING
 THE REMODELING OF THE FIRE SPRINKLER
 SYSTEM.
  
 6) NO INFORMATION REGARDING THE
 INTERIOR FINISH CLASSIFICATION
 FOR WALLS AND CEILINGS.
  
 7) NO INFORMATION REGARDING PORTABLE
 FIRE EXTINGUISHERS.
  
 8) PLEASE INDICATE LOCATIONS AND
 RATINGS OF ALL TENANT SEPARATION
 WALLS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-22 Cont ID  
Sent By shill Date 2004-10-22 Time 11:57 Rev Time 0.00
Received By shill Date 2004-10-22 Time 11:57 Sent To B
Notes
2004-10-22 00:00:00OLD SET NEVER PICKED UP; STILL ON THE
 BOARD #5.PASSED ALL REVIEWS.TOOK
 BOTH OFF OF BOARD (#5 AND #49) AND
 PUT ON SMH DESK.SHEETS NEED TO BE
 SWAPPED AND ISSUED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-14 Cont ID  
Sent By csiegber Date 2004-10-14 Time 14:44 Rev Time 0.00
Received By csiegber Date 2004-10-14 Time 14:44 Sent To  
Notes
2004-10-14 00:00:00TO COMM BD#49

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-17 Cont ID  
Sent By csiegber Date 2004-09-17 Time 08:52 Rev Time 0.00
Received By csiegber Date 2004-09-17 Time 08:51 Sent To  
Notes
2004-09-17 00:00:00TO COMM BD#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 09:17 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 09:17 Sent To  
Notes
2004-05-20 00:00:00TO COMM BD#20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-20 Time 09:16 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 11:58 Sent To  
Notes
2004-04-14 00:00:00TO COMM BD#51

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-01 Cont ID  
Sent By pkrauss Date 2004-06-01 Time 11:31 Rev Time 0.35
Received By pkrauss Date 2004-06-01 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-24 Cont ID  
Sent By pkrauss Date 2004-04-24 Time 10:10 Rev Time 0.40
Received By pkrauss Date 2004-04-24 Time 10:08 Sent To  
Notes
2004-04-24 00:00:00DENIED:
 PLEASE INDICATE IF THE SYSTEM IS TIED
 INTO THE BUILDING FIRE ALARM SYSTEM.
  
 SEE ALSO COMMENTS BY ASSST FIRE MARSHAL,
 MIKE CARSILLO.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-10-14 Cont ID  
Sent By kstevens Date 2004-10-14 Time 14:14 Rev Time 0.50
Received By kstevens Date 2004-10-14 Time 14:14 Sent To  
Notes
2004-10-14 00:00:00REVISION/PASSED
  
 DELETED BREAK ROOM SINK

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-05 Cont ID  
Sent By kstevens Date 2004-06-05 Time 16:50 Rev Time 0.50
Received By kstevens Date 2004-06-05 Time 16:50 Sent To  
Notes
2004-06-05 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED SHOWING A 30"X48"
 PARALLED APPROACH CLEAR FLOOR SPACE
 FOR LOUNGE SINK.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-27 Cont ID  
Sent By kstevens Date 2004-04-27 Time 19:26 Rev Time 0.50
Received By kstevens Date 2004-04-27 Time 19:20 Sent To  
Notes
2004-04-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) INDICATE USE FOR NEW SINK. IF SINK
 IS IN A BREAK ROOM/KITCHENETTE IT SHALL
 COMPLY WITH 11-4.24 AND ALL SUBSECTIONS.
 A DETAIL WILL BE REQUIRED.
 2) SUBMIT A WATER RISER DIAGRAM REQUIRED
 PER SECTION 104.3.1.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]