Plan Review Details - Permit 04040778
Plan Review Stops For Permit 04040778
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-18 Cont ID  
Sent By jwitmer Date 2004-05-18 Time 15:45 Rev Time 0.55
Received By jwitmer Date 2004-05-18 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-13 Cont ID  
Sent By jwitmer Date 2004-05-13 Time 13:54 Rev Time 1.22
Received By jwitmer Date 2004-05-13 Time 13:54 Sent To PC
Notes
2004-05-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 040407781)
 ADD: 201 S NARCISSUS AV
 CONT: MC LAREN CONST
 TEL: (561)686-6500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 803.4 FOAM PLASTICS. FOAM PLASTICS SHALL
 NOT BE USED AS INTERIOR FINISH.
 EXCEPTION:
 A) THE MINIMUM DENSITY IS 20LB/CU FT .
 B) THE MAXIMUM THICKNESS OF THE TRIM IS
 1/2" AND THE MAXIMUM WIDTH IS 4".
 C) THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE AREA OF ANY WALL OR
 CEILING.
 D) THE FLAMESPREAD RATING DOES NOT EX-
 CEED 75 WHEN TESTED PER ASTM E 84.
  
 2) MARBLE FIREPLACE:
 PROVIDE ADDITIONAL INFORMATION:
 IS THIS A ACTIVE FIREPLACE WITH A MARBLE
 SURROUND?
 FALSE FIREPLACES, 2807, FALSE FIREPLACES
 MAY BE USED IN CONNECTION WITH LISTED
 GAS OR ELECTRIC HEATERS, PROVIDED SUCH
 FIREPLACES ARE CONSTRUCTED OF NONCOMBUST
 IBLE MATERIALS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-18 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 17:08 Rev Time 0.25
Received By dpalmer Date 2004-05-18 Time 17:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-18 Cont ID  
Sent By csiegber Date 2004-05-17 Time 12:28 Rev Time 0.25
Received By dpalmer Date 2004-04-18 Time 11:29 Sent To  
Notes
2004-04-18 00:00:00***** UNSAT ****
  
 1)NOTE: NO ELECTRICAL DETAILS/PLAN
 SUBMITTED.
 PLAN/DRAWING CAN BE DONE BY CONT.
 NOT REQ'D TO BE DONE BY ARCH/ ENG.
 104.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-19 Cont ID  
Sent By mcarsill Date 2004-05-19 Time 11:28 Rev Time 0.00
Received By mcarsill Date 2004-05-19 Time 11:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By mcarsill Date 2004-04-28 Time 12:28 Rev Time 0.00
Received By mcarsill Date 2004-04-28 Time 12:28 Sent To  
Notes
2004-04-28 00:00:001) NO DETAILS PROVIDED ON MARBLE
 FIREPLACE. PLEASE PROVIDE MORE DETAILS
 ON PROPOSED FIREPLACE.
  
 2) IT IS ASSUMED THAT REQUIRED
 ELECTRIC POWERED SMOKE DETECTORS
 ARE PRESENT WITHIN THE APARTMENT. NONE
 WERE SHOWN ON THE PLAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 12:28 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 12:27 Sent To E
Notes
2004-05-17 00:00:00TO COMM BD#27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-13 Cont ID  
Sent By csiegber Date 2004-04-19 Time 08:24 Rev Time 0.00
Received By jwitmer Date 2004-04-19 Time 08:24 Sent To PC
Notes
2004-04-19 00:00:00TO COMM BD#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 10:23 Sent To E
Notes
***NONE***