Plan Review Details - Permit 04040773
Plan Review Stops For Permit 04040773
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-21 Cont ID  
Sent By csiegber Date 2004-04-13 Time 10:18 Rev Time 1.50
Received By shill Date 2004-04-21 Time 17:20 Sent To  
Notes
2004-04-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT PROTECTION REQUIRED FBC
 1606.1.4.PROVIDEINFORMATION, EITHER
 AS A PRODUCT APPROVAL OR ENGINEERING,
 TO SHOW THAT EXISTING SHUTTERS COMPLY
 WITH FBC.
  
 2.)PROVIDE PRODUCT APPROVALS FOR THE
 HORIZONTAL ROLLERS.
  
 3.)OPENING 12 SHOWS A DOOR.IS THIS A
 NEW DOOR?PROVIDE A PRODUCT APPROVAL.
  
 4.)IF OPENING 12 IS GLAZED, SHOW
 COMPLIANCE WITH FBC1005.4.5, MEANS OF
 ESCAPE (HURRICANE PROTECTIVE DEVICES).
  
 5.)ADDITIONAL FEES DUE (VALUE
 INCREASE).
  
 6.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 7.)THE PERMIT APPLICATION INDICATES
 REPAIR WORK.PROVIDE A DETAIL.
  
 8.)FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVALS REQUIRED
 EFFECTIVE OCTOBER 1, 2003.
 WWW.FLORIDABUILDING.ORG (PRODUCT
 APPROVAL, PRODUCT APPROVAL SEARCH).
 PRINT THE FLORIDA PRODUCT APPROVAL FOR
 EACH PRODUCT AND PROVIDE WITH THE
 TEST REPORT.
  
 9.)PROVIDE A COPY OF THE PLAN WITHOUT
 THE CITY STAMPS ON IT FROM THE PREVIOUS
 PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 10:18 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 10:18 Sent To B
Notes
2004-04-13 00:00:00TO MISC BOX

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved