Plan Review Details - Permit 04040671
Plan Review Stops For Permit 04040671
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-10 Cont ID  
Sent By jwitmer Date 2004-06-10 Time 12:12 Rev Time 2.22
Received By jwitmer Date 2004-06-10 Time 11:25 Sent To PC
Notes
2004-06-10 00:00:00BUILDING PROVISO:
 905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-09 Cont ID  
Sent By jleech Date 2004-06-08 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2004-06-09 Time 13:50 Sent To  
Notes
2004-06-09 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE IMPACT FEES.
  
 2) THE STATE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE SKYLIGHTS IS FOR A
 SUNDOME AND NOT FOR THE 2'X 4' SKYLIGHTS
 THAT ARE SHOWN ON THE PLANS. PLEASE
 REVISE PLANS OR SUBMIT CORRECT PRODUCT
 APPROVAL.
  
 3) THE PRODUCT APPROVALS SUBMITTED FOR
 THE OVERHEAD GARAGE DOORS DO NOT HAVE
 DESIGN PRESSURES THAT MEET THE REQUIRE-
 MENTS OF THE PLANS.
  
 4) AN H10 CONNECTOR (WOOD TO WOOD) IS
 SEPCIFIED FOR A SECTION OF THE
 CONNECTING HALL THAT HAS A CONCRETE TIE
 BEAM. PLEASE SPECIFY AN APPROPIATE
 CONNECTOR (WOOD TO CONCRETE) FOR THIS
 AREA. SEE NOTES ON SHEET A7 OF PLANS.
  
 5) A SEPARATE PERMIT WILL BE REQUIRED
 FOR ROOFING.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-12 Cont ID  
Sent By pkrauss Date 2004-05-26 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2004-05-12 Time 07:19 Sent To  
Notes
2004-05-12 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 MUST ACTUALLY COMMENCE WITHIN 90 DAYS
 AFTER RECORDING OR THE NOTICE IS VOID.
 FS 713.13
  
 3) SUBMIT A SIGNED AND SEALED COPY OF
 THE SURVEY.
  
 4) THE SUBSURFACE SOIL REPORT IS FOR LOT
 9A. THE UNITY OF TITLE IS FOR LOTS 10A
 AND 12. THE ADDITION WILL BE THE LOT 10A
 PORTION OF THE UNIFIED LOTS.
  
 5) FAC 61G1 REQUIRES THE FIRM LICENSE
 NUMBER AND THE LICENSE NUMBER OF THE
 ARCHITECT SIGNING AND SEALING THE PLANS.
  
 6) PLEASE CORRECT THE CONSTRUCTION TYPE
 LISTED ON A1. IT IS TYPE VI CONSTRUCTION
 SEE FBC 608.
  
 7) ON SHEET A1 UNDER MASONRY REVISE #8
 (D) TO REFERENCE FBC SEC 2112, NOT SBCCI
 AND UPDATE THE SPECIFIED MASONRY
 STANDARDS TO COMPLY WITH THE 2001 FBC
 REFERENCED STANDARDS.
  
 8) SPECIFY ON THE PLANS THAT THE WWF IN
 THE SLAB IS TO BE SUPPORTED AS REQUIRED
 BY FBC 1909.3.
  
 9) SPECIFY IF THE STRUCTURE IS DESIGNED
 AS OPEN OR ENCLOSED AS REQUIRED BY FBC
 1606.1.7. IF DESIGNED USING ASCE 7-98,
 SPECIFY INTERNAL PRESSURE COEIFFICENT.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT STATE OR LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING ITEMS:
 - SKYLIGHTS
 - CASEMENT WINDOWS
 - OVERHEAD GARAGE DOORS
  
 11) NOAS WERE SUBMITTED FOR A PROJECTED
 WINDOW, SINGLE HUNG WINDOW AND FRENCH
 DOOR WITH SIDELITES WHICH ARE NOT SHOWN
 ON THE PLANS. PLEASE SUBMIT ONLY THE
 PRODUCT APPROVALS FOR ITEMS SHOWN ON THE
 PLANS.
  
 12) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE ROOFING.
  
 13) REVISE THE ROOF SHEATHING NAILING
 INFO ON A8. FOR A MEAN ROOF HEIGHT OF
 MORE THAN 25 FEET 8D RING SHANK NAILS
 ARE REQUIRED IN ZONE 3 AND NAIL SPACING
 IS 4"OC AT EDGES AND 6"OC INTERMEDIATE.
 SEE CITY AMENDMENTS TO FBC TABLE 2306.1.
  
 14) IN THE CONNECTOR SCHEDULE ON A8
 THERE IS NO CONNECTOR LISTED FOR MARK(K)
 AND NO FL PRODUCT APPROVAL NUMBER IS
 LISTED FOR MARK(M). PLEASE CORRECT.
  
 15) THE UPLIFT FOR MARK (I) HETA 16 IS
 1810#. PLEASE CORRECT.
  
 16) TWO CONFLICTING BUCK DETAILS ARE
 LISTED ON A8. PLEASE REMOVE ONE OF THEM.
  
 17) ON SHEET A7 A MARK FOR DETAIL E ON
 A8 IS SPECIFIED. THERE IS NO DETAIL E ON
 A8. PLEASE CORRECT.
  
 18) SPECIFY THE CONNECTION OF THE 2X6
 WALLS TO THE 72" DEEP GIRDERS AT THE
 ENTRY TOWER.
  
 19) MARK (M) AN H10 CONNECTOR IS
 SPECIFIED FOR A PORTION OF THE HALL
 CONNECTING THE ADDITION TO EXISTING THAT
 IS MASONRY AND CONCRETE. A HM9 OR EMBED
 STRAP CONNECTOR SHOULD BE USED IN THIS
 LOCATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2004-06-10 Cont ID  
Sent By jwitmer Date 2004-06-10 Time 11:23 Rev Time 0.00
Received By jwitmer Date 2004-06-10 Time 11:23 Sent To  
Notes
2004-06-10 00:00:00CRIBB CONST PULLED ELEC PERMIT & PLAN
 SEPERATE PERMIT AND PLANS REQUIRED. JW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-28 Cont ID  
Sent By dpalmer Date 2004-05-28 Time 16:02 Rev Time 1.00
Received By dpalmer Date 2004-05-28 Time 15:43 Sent To P
Notes
2004-05-28 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE SEE SHUNT TRIP MAY NOT
 BE USED AS THE MEANS OF DISCONNECT
 GROUPED WITH EXISTING.
 PLEASE SEE GROUPING OF MAINS, 230.72,
 RATING OF DISCONNECT AND MANUALS MEANS
 230.76,230.79. ETC.
  
 2)NOTE: PLEASE INDICATE FULL LOAD FOR
 SERVICE. EXISTING SEC'S ARE RATED FOR
 400A'S. PLEASE VERIFY LOAD FOR NEW
 AND EXSITING.
  
 3)NOTE: PLEASE SEE CHAPTER 34FBC
 3401.7.1.2.1PLEASE VERIFY EITHER
 EXISTING OR NEW SD'S TO CURRENT CODE
 AND ALL GFI'S REQ'D PER 2002 NEC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-08 Cont ID  
Sent By csiegber Date 2004-05-06 Time 12:06 Rev Time 1.00
Received By dpalmer Date 2004-05-07 Time 17:40 Sent To P
Notes
2004-05-08 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ARCH'S CA# ON
 TITLE BLOCK AS REQ'D UNDER FS 481.219
 FAC 61G1-16.004.
 THIS IS REQ'D ON ALL SHEETS AND FOR ALL
 TRADES SHEETS, WEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE THAT CHANGES MADE
 TO PLANS W/ BLACK MARKER ARE NOT PERMIT-
 -TED TO SIGNED AND SEALED PLANS.
  
 3)NOTE: PLEASE CLARIFY IF NEW MAIN IS
 GROUPED WITH THE OTHER TWO MCB PANELS
 PER 230.72
  
 4)NOTE: PLEASE PROVIDE LOAD COMPLETE
 LOAD CALCULATIONS FOR SERVICE SHOWING
 NEW AND EXISTING.
  
 5)NOTE: PLEASE SEE 210.12 2002 NEC,
 PLEASE LIST THE REQ'D ARC FAULT CIRCUIT(
 S).
  
 6)NOTE: PLEASE SEE OCP FOR AHU'S .
 SHOWS 60A OCP FOR 5KW HEAT>
 424.3B.
  
 7)NOTE: PLEASE VERIFY ANY REQ'MENTS FOR
 CHAPTER 34 FBC.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE SUBMITT-
 -ED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-05-07 00:00:00************** UNSAT *************
  
 NOTES TO FOLLOW.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 16:17 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 16:17 Sent To E
Notes
2005-01-31 00:00:00TO "DP" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-24 Cont ID  
Sent By mmclean Date 2004-05-26 Time 12:24 Rev Time 0.00
Received By alange Date 2004-05-24 Time 13:01 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 12:06 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 12:06 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-03 Cont ID  
Sent By mmclean Date 2004-05-05 Time 16:10 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 15:18 Sent To Z
Notes
2004-05-03 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 09:40 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 09:40 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-26 Cont ID  
Sent By pkrauss Date 2004-05-26 Time 16:32 Rev Time 0.30
Received By pkrauss Date 2004-05-26 Time 16:32 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-10 Cont ID  
Sent By dpalmer Date 2004-05-07 Time 17:47 Rev Time 0.55
Received By pkrauss Date 2004-05-10 Time 12:24 Sent To B
Notes
2004-05-10 00:00:00DENIED:
 MECHANICAL PLAN INDICATES AHU #2
 SERVINGTHE GARAGE, AIR FROM THE GARAGE
 AREA SHALL NOT BE RECIRULATED, OUTSIDE
 AIR REQUIRED AT A RATE OF 100 CFN PER
 VEHICLE, PER 2001 FBC(M) TABLE 403.3.
  
 UNITS FOR DE-HUMIDIFACATION PUPOSES
 SHALL BE CONTROLLED BY A HUMIDISTAT PER
 2001 FBC CHAPTER 13 607.1.ABC.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-08 Cont ID  
Sent By jleech Date 2004-06-08 Time 18:48 Rev Time 0.33
Received By jleech Date 2004-06-08 Time 18:48 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-05-10 Cont ID  
Sent By dpalmer Date 2004-05-28 Time 16:02 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-05-10 00:00:00 
 PROVISO
  
  
 PLUMBING TECHNICAL REVIEW IS APPROVED
 BY JOHN LEECH.
  
 DRAWINGS WITH COMPANY TITLE BLOCK SHALL
 INCLUDE CA#
  
  
  
 LUIS MARTINEZ
 805-6710

Review Stop Z ZONING
Rev No 3 Status P Date 2004-05-26 Cont ID  
Sent By mmclean Date 2004-05-26 Time 12:24 Rev Time 0.00
Received By mmclean Date 2004-05-26 Time 12:24 Sent To I
Notes
2004-05-26 00:00:00MUST PROVIDE CORRECT COPY OF SURVEY
 BEFORE PERMIT IS ISSUED.CONTRACTOR
 CALLED, MESSAGE LEFT ON VOICE MAIL.
 APPROVED BY GRACE JOYCE, PLANNER
 659-8031 MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-05-05 Cont ID  
Sent By alange Date 2004-05-24 Time 13:01 Rev Time 0.00
Received By mmclean Date 2004-05-05 Time 16:09 Sent To I
Notes
2004-05-05 00:00:00DENIED, PROVIDE A MUCH CLEARER SITE OF
 EXISITING PROPERTY.NEED TO REMOVE
 KITCHEN OFF PLAN (NO KITCHEN ALLOWED).
 GRACE CALLED CONTR FILE C

Review Stop Z ZONING
Rev No 1 Status F Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-05-03 Time 16:25 Rev Time 0.00
Received By mmclean Date 2004-04-16 Time 11:19 Sent To  
Notes
2004-04-16 00:00:00DENIED, NEED TO SEE/SPEAK WITH GRACE
 JOYCE, PLANNER 659-8031.CALLED CONTR
 FILE C.
 *NEED TO PROVIDE A UNITY OF TITLE
 *PROVIDE A MUCH CLEARER SITE OR SURVEY
 OF EXISITING PROPERTY
 *CANNOT HAVE ADDITIONAL KITCHEN
 *NEED TO SEE GRACE, PLANNER MM