Plan Review Details - Permit 04040636
Plan Review Stops For Permit 04040636
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-17 Cont ID  
Sent By alange Date 2004-05-17 Time 15:31 Rev Time 0.50
Received By alange Date 2004-05-17 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-10 Cont ID  
Sent By dpalmer Date 2004-05-17 Time 10:44 Rev Time 0.50
Received By alange Date 2004-05-07 Time 15:34 Sent To E
Notes
2004-05-10 00:00:00 
 DENIED
 1.BUILDING SHALL COMPLY WITH SEC.
 3401.7.2.6 OF THE FBC.
 SHOW HOW EXISTING STRUCTURE WILL
 COMPLY WITH THIS SECTION.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
2004-05-07 00:00:00TO DP DESK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-27 Cont ID  
Sent By dpalmer Date 2004-05-07 Time 14:32 Rev Time 0.75
Received By alange Date 2004-04-27 Time 08:09 Sent To  
Notes
2004-04-27 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. ENERGY CALCS REQUIRE SIGNATURE OF
 OWNER/ AGENT.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 13:03 Rev Time 0.33
Received By dpalmer Date 2004-09-21 Time 13:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-09-14 Time 11:40 Rev Time 0.33
Received By dpalmer Date 2004-05-17 Time 10:43 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-17 Time 10:01 Rev Time 0.75
Received By dpalmer Date 2004-05-07 Time 14:31 Sent To B
Notes
2004-05-07 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. NO CORRECTIONS WERE MADE TO
 ARCH PLANS.
 ARCH HAS NOW SIGNED AND SEALED PLANS
 DRAWN BY THE ELECTRICAL CONTRACTOR
 WHICH IS NOT PERMITTED UNDER FS 481
 ARCH SHALL NOT AFFIX HIS SIGNATURE AND
 SEAL TO WORK HE HAS NOT DONE.
  
 2)NOTE: PLEASE MAKE CORRECTIONS FOR
 NEC ON PLANS.
  
 3)NOTE: PLEASE SEE FBC CHAPTER 34.
 PLEASE SEE 3401.7.2.6
 PLEASE SHOW ALL EXSITING MEETING 2002
 NEC AND/OR NEW ELECTRICAL TO MEET
 CODE. INCLUDING NFPA-72
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-17 Cont ID  
Sent By pkrauss Date 2004-05-06 Time 11:06 Rev Time 0.50
Received By dpalmer Date 2004-04-17 Time 19:54 Sent To P
Notes
2004-04-17 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE NOTES AND
 DETAILS FOR SERVICE. ONE LINE MENTIONS
 150A PANEL. NEW /EXISTING?RISER SHOWS
 EXISTING 200A SERVICE?
 PLEASE ALSO SEE SEC'S ARE ONLY RATED
 FOR 150A'S? 310.15B6
  
 2)NOTE: PLEASE CLARIFY LOCATION OF PANEL
 EXISTING OR NEW. IF MORE THAN 8' OF
 UNPROTECTED CONDUCTORS ARE INSIDE BLDG,
 A MAIN IS REQ'D OUTSIDE PROVIDING OCP.
 230.70 NEC/ LOCAL AMENDMENTS.
  
 3)NOTE: PLEASE REVISE LOAD CALCULATIONS
 TO NEC 220. THERE ARE MANY ITEMS SHOWN
 ON PANEL SCHEDULE WHICH SHOWS AN "NA"
 NEXT TO LOAD? IF THESE ITEMS ARE NOT
 GOING TO BE INSTALLED, PLEASE REMOVE
 FROM PANEL SCHEDULE. IF THEY ARE, PLEASE
 SEE NEC 220 FOR ALL MIN LOADS REQD'.
 PLEASE ALSO SEE NO LOAD SHOWN FOR 2ND
 A/C AHU HEAT?? THIS IS REQ'D.
 PLEASE CORRELATE W/ MECH PLANS.MECH PLAN
 -S SHOW TWO UNITS.
  
 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2,
 FOR REQ'D SD'S THROUGH-OUT RESIDENCE,
 INCLUDING EXISTING BEDRMS AND OUTSIDE
 THE EXSITNG TWO BEDROOMS.IF THESE ARE
 EXISTING, THEN THEY ARE REQ'D TO BE
 WIRED INLINE WITH ALL NEW SD'S.
 PLEASE SEE NFPA-72 8-1.4.2, REQ'D SD'S
 TO BE A MIN OF 3' FROM BATH DRS. ETC
  
 5)NOTE: PLEASE SEE PLANS SHOULD REFER-
 -ENCE THE 2002 NEC.
  
 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 2002 NEC 210.12
  
 7)NOTE: PLEASE CLARIFY IF NEW OR EXIST-
 -ING REAR RECEPT PER 210.52E
  
 8)NOTE: PLEASE VERIFY KW AND OCP SHOWN
 FOR WATER HEATER. MIN OCP IS 125% OF
 LOAD, HOWEVER, MAX OCP FOR LOAD IS 150%
 422.13/ 422.11E3
  
 9)NOTE: PLEASE PLACE AN "E" NEXT TO
 PANEL SCHEDULE FOR EXISTING CIRCUITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 11:40 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 11:40 Sent To E
Notes
2004-09-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 10:01 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 10:01 Sent To E
Notes
2004-05-17 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-12 Cont ID  
Sent By mmclean Date 2004-05-14 Time 11:50 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 09:33 Sent To Z
Notes
2004-05-12 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-29 Cont ID  
Sent By csiegber Date 2004-04-29 Time 09:27 Rev Time 0.00
Received By csiegber Date 2004-04-29 Time 09:26 Sent To M
Notes
2004-04-29 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 15:52 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-12 Cont ID  
Sent By mmclean Date 2004-04-15 Time 16:06 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 10:36 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-06 Cont ID  
Sent By pkrauss Date 2004-05-06 Time 11:04 Rev Time 0.30
Received By pkrauss Date 2004-05-06 Time 11:04 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-04-29 Time 09:27 Rev Time 0.30
Received By pkrauss Date 2004-04-23 Time 07:17 Sent To B
Notes
2004-04-23 00:00:00DENIED:
 1.RETURN AIR FROM BEDROOM #1 SHALL BE
 A MINIMUM OF 10".ALL AIR INTO THE
 MASTER SUITE IS TO BE INCLUDED FOR A
 TOTAL OF SUPPLY AIR INTO THAT AREA.
 REVISED 2001 FBC(M) 601.4 EXCEPTION #3.
  
 2.10" RETURN REQUIRED FROM THE NEW
 FAMILY ROOM PER 2001 FBC(M) 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-04-20 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 19:54 Rev Time 0.33
Received By kstevens Date 2004-04-20 Time 12:52 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-05-14 Cont ID  
Sent By mmclean Date 2004-05-14 Time 11:50 Rev Time 0.00
Received By mmclean Date 2004-05-14 Time 11:50 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-05-12 Time 09:33 Rev Time 0.00
Received By mmclean Date 2004-04-15 Time 16:06 Sent To I
Notes
2004-04-15 00:00:00DENIED, NEED TO PROVIDE 2 COPY OF SURVEY
 SHOWING THE ADDITION WITH SETBACKS &
 EASEMENT RELEASE FOR NEW FENCE.CALLED
 CONTR MM
 PER CONTRACTOR HE DID NOT INCLUDE THE
 FENCE AS APART OF PERMIT.