| 2004-04-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW |
| | 1) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER. |
| | 2) FBC-2001 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 3) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| | 4) PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 - SIGNATURE IS A COPY AND THE |
| | SEAL IS REQUIRED ON BOTH SETS OF PLANS. |
| | |