Plan Review Details - Permit 04040499
Plan Review Stops For Permit 04040499
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-02-04 Cont ID  
Sent By alange Date 2005-02-04 Time 10:09 Rev Time 0.50
Received By alange Date 2005-02-04 Time 10:09 Sent To  
Notes
2005-02-04 00:00:00REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-02-02 Cont ID  
Sent By alange Date 2005-02-02 Time 09:38 Rev Time 0.50
Received By alange Date 2005-02-02 Time 09:38 Sent To  
Notes
2005-02-02 00:00:00DENIED
 PRODUCT APPROVALS FOR FIXED WINDOW NOT
 APPROVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-09 Cont ID  
Sent By alange Date 2004-06-09 Time 16:24 Rev Time 0.50
Received By alange Date 2004-06-09 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-19 Cont ID  
Sent By dpalmer Date 2004-06-01 Time 13:16 Rev Time 0.50
Received By alange Date 2004-05-19 Time 08:54 Sent To  
Notes
2004-05-19 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. SHOW ON SITE PLAN LOCATION OF NEW
 ROOM ADDITION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-26 Cont ID  
Sent By dpalmer Date 2004-05-17 Time 15:33 Rev Time 1.00
Received By alange Date 2004-04-26 Time 10:16 Sent To  
Notes
2004-04-26 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW ON SITE PLAN LOCATION OF NEW
 ROOM ADDITION.
  
 4.PLANS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE ARCHITECT OF
 RECORD, FS 481.221
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 09:53 Rev Time 0.30
Received By dpalmer Date 2005-01-24 Time 09:53 Sent To B
Notes
2005-01-24 00:00:00RISER DIAGRAM TO CORRELATE WITH 04030953

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-01 Cont ID  
Sent By dpalmer Date 2004-06-01 Time 13:16 Rev Time 0.33
Received By dpalmer Date 2004-06-01 Time 13:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-17 Cont ID  
Sent By alange Date 2004-05-25 Time 16:26 Rev Time 1.00
Received By dpalmer Date 2004-05-17 Time 15:32 Sent To B
Notes
2004-05-17 00:00:00*********** UNSAT *******************
  
 1)NOTE: PLEASE SEE A COMPLETELY NEW
 RISER IS NOW SUBMITTED AND DOES NOT
 INCLUDE ALL PANELS AS ORIG SHOWN.
 RISER DIAGRAM AND PANELS DO NOT CORRE-
 -LATE.
  
 PLEASE SUBMIT CORRECTED RISER DIAGRAM W/
 PANELS SCHEDULES..
 225.31,250.32.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-17 Cont ID  
Sent By csiegber Date 2004-04-12 Time 09:42 Rev Time 0.50
Received By dpalmer Date 2004-04-17 Time 13:56 Sent To B
Notes
2004-04-17 00:00:00******* UNSAT **********
  
 1)NOTE: PLANS ARE REQ'D TO BE SIGNED,
 DATED AND SEALED BY THE ARCH OF RECORD.
 FS481.221
  
 2)NOTE: PLANS SHOW A NEW PANEL FOR
 GAZEBO, YET PLANS ALSO MENTIONS TO BE
 UNDER SEPARATE PERMIT??
 RISER DOES SEEM TO INDICATE THIS GAZEBO
 PANEL??
  
 3)NOTE: PLEASE SEE 225.31 FOR GAZEBO
 AND PANEL FOR GUESTHOUSE.
  
 4)NOTE: PLEASE SHOW LOCATION FOR SERVICE
 AND ALL SERVICE EQUIPMENT.
  
 5)NOTE: RISER SHOWS NEW 400A SERVICE
 BEING INSTALLED, PLEASE SHOW.
 PLEASE INCLUDE NEW SEC'S IN RISER.
 215.5 310.15B6
  
 5)NOTE: PLEASE SHOW LOCATIONS OF SD'S
 REQ'D UNDER NFPA-72 8-1.4.1.6.2 AND
 FBC
  
  
 6)NOTE: PLEASE SHOW ALL NEW AND/OR
 GROUNDING ELECTRODE SYSTEM. 250.50
 PLEASE SHOW ALL GROUNDING FOR DETACHED
 BLDGS. 250.32
  
 7)NOTE: PLEASE SEE 210.12 OF THE 2002
 NEC. ARC FAULT PROTECTION.
  
 8) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 9)NOTE: PLEASE SHOW MEANS OF CONTROL FOR
 EGRESS LIGHTING INTO LIV RM FROM BED RM.
 210.70
  
 10)NOTE: PLEASE SHOW ALL A/C EQUIPMENT
 DISC MEANS, GFI RECEPT. 440.11, 210.63
  
 11)NOTE: PLEASE SHOW REQ'D OUTSIDE GFI
 RECEPTS PER 210.52E
  
 12)NOTE: PLEASE SEE PANEL SCHEDULE,
 THERE ARE MANY ITEMS SHOWN ON PANEL
 SCHEDULE THAT ARE NOT SHOWN ON PLANS??
 SM APPL CIRCUITS, WATER HEATER LOCATION,
 EXHAUST HOOD.
  
 13)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULE(S).
 PANEL SCHEDULE "B" DOES NOT SHOW ANY
 FEEDS FOR OTHER PANELS AS SHOWN ON
 RISER.
  
 PLEASE SUBMIT PLANS TO NEC 2002 EDITION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-03 Cont ID  
Sent By mjacobs Date 2005-02-03 Time 07:51 Rev Time 0.00
Received By mjacobs Date 2005-02-03 Time 07:51 Sent To B
Notes
2005-02-03 00:00:00TO "AL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 09:27 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 09:27 Sent To E
Notes
2005-01-14 00:00:00TO "DP" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-25 Cont ID  
Sent By alange Date 2004-05-25 Time 16:25 Rev Time 0.00
Received By alange Date 2004-05-25 Time 16:25 Sent To E
Notes
2004-05-25 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 14:48 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 14:48 Sent To  
Notes
2004-05-12 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 09:42 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 09:42 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-04-09 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 14:32 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-28 Cont ID  
Sent By pschmitz Date 2005-01-28 Time 15:14 Rev Time 0.00
Received By pschmitz Date 2005-01-28 Time 15:14 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-09 Cont ID  
Sent By csiegber Date 2004-04-06 Time 14:32 Rev Time 0.00
Received By mmclean Date 2004-04-09 Time 16:17 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy