Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-15 Cont ID  
Sent By dpalmer Date 2004-04-15 Time 11:37 Rev Time 0.33
Received By dpalmer Date 2004-04-15 Time 11:37 Sent To  
Notes
2004-04-15 00:00:00INFORMATION SENT IN OVER PHONE NEEDED
 FOR RISER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-06 Time 14:26 Rev Time 0.33
Received By dpalmer Date 2004-04-13 Time 16:44 Sent To  
Notes
2004-04-13 00:00:00**** UNSAT ***
  
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]