| Plan Review Stops For Permit 04040494 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-04-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-15 |
Time |
11:37 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-04-15 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2004-04-15 00:00:00 | INFORMATION SENT IN OVER PHONE NEEDED | | | FOR RISER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-04-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-06 |
Time |
14:26 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-04-13 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2004-04-13 00:00:00 | **** UNSAT *** | | | | | | | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-04-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-06 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-06 |
Time |
14:25 |
Sent To |
E |
|
| Notes |
|
|
|