Plan Review Details - Permit 04040450
Plan Review Stops For Permit 04040450
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-19 Cont ID  
Sent By dpalmer Date 2004-04-19 Time 11:57 Rev Time 0.33
Received By dpalmer Date 2004-04-19 Time 11:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-06 Time 15:49 Rev Time 0.33
Received By dpalmer Date 2004-04-13 Time 15:28 Sent To  
Notes
2004-04-13 00:00:00***** UNSAT ***
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN/ SERVICE PER 110.9.
 MAINS/BRKRS AND PANEL ARE REQ'D TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: PLEASE PROVIDE MORE INFORMATION
 FOR FEED TO HOUSE PANEL AS NOTED ON
 RISER. DETACHED? GROUNDING? MEANS OF
 DISC? 225.31,250.32 ETC. 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-06 Time 15:49 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 15:49 Sent To E
Notes
***NONE***