| Plan Review Stops For Permit 04031748 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-03-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-03-29 |
Time |
16:48 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2005-03-29 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2005-03-29 00:00:00 | REVISION 3-29-05 REVISED TO A 2'-8" | | | DOOR OPENING NO DOOR.OKJW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-03-12 |
Time |
09:00 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2005-03-12 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2005-03-12 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04031748 | | | ADD: 900 S DIXIE HWY | | | CONT:FORTUNE CONSTRUCTION | | | TEL: (561)716-2996 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISIONS SHEET #1 | | | | | | ACTION: DENIED | | | | | | 1) DOOR #2 INTO OFFICE #9: | | | 11-4.13.5 DOORWAYS, MINIMUM | | | CLEAR WIDTH: DOORWAY SHALL HAVE A MINI- | | | MUM CLEAR OPENING OF 32" WITH THE DOOR | | | OPEN 90 DEGREES, MEASURED BETWEEN THE | | | FACE OF THE DOOR AND THE OPPOSITE STOP. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-07-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-07-26 |
Time |
11:09 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2004-07-26 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-06-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-06-15 |
Time |
16:44 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2004-06-15 |
Time |
16:44 |
Sent To |
PC |
|
| Notes |
| 2004-06-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04031748 | | | ADD: 900 S DIXIE HWY | | | CONT: CONSTRUCTION QUALITY CONTROL | | | TEL: (786)229-3111 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | ********NOTE********* | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | 1) PLANS INDICATE "CONSTRUCTION OFFICE/ | | | TEMP SALES", IF THIS A TEMP SALES OFFICE | | | THE TRAILER WILL NEED A PERMIT. NO INFOR | | | MATION SUBMITTED UNDER THIS PERMIT FOR | | | THE SECOND REVIEW!!!!!!!NOTE FOR A SALES | | | OFFICE WILL REQUIRE ACCESSIBILITY. | | | | | | 2) THIS SITE IS IN THE "FIRE DISTRICT", | | | NO TYPE VI CONSTRUCTION ALLOWED. | | | | | | 3) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-04-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-04-27 |
Time |
14:03 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2004-04-27 |
Time |
14:03 |
Sent To |
PC |
|
| Notes |
| 2004-04-27 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04031748 | | | ADD: 900 S DIXIE HWY | | | CONT: CONSTRUCTION QUALITY CONTROL | | | TEL: (786)229-3111 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) PLANS INDICATE"CONSTRUCTION OFFICES/ | | | TEMP SALES", IS THIS A TEMORARY TRAILER? | | | IF SO HOW LONG WILL THIS UNIT BE THERE? | | | | | | 3) THIS SITE IS PART OF THE "FIRE DIS- | | | TRICT", NO TYPE VI CONSTRUCTION ALLOWED. | | | | | | 4) IF THE TEMP SALES TRAILER IS TO BE | | | OPEN TO THE PUBLIC INDICATE THE ACCESS- | | | IBLE ROUTE. | | | | | | 5) THE OPERATING KITCHEN ROOM# 10, THE | | | COUNTERTOP OR RIM OF SINK TO BE NO HIGH- | | | ER THAN 34". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-08 |
Time |
18:31 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-03-08 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2005-03-08 00:00:00 | REDLINED 110.15 FOR MARKING OF HIGH-LEG | | | ON SERVICE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-07-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-13 |
Time |
16:14 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-07-13 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2004-07-13 00:00:00 | 4X FEE ACCESSED PER RICHARD CORDOVEZ | | | WAS REMOVED. | | | VALUE WAS INCREASED ON APPLICATION, | | | OWES FOR ADDITIONAL FEES. | | | | | | ALL INSPECTIONS MUST BE COMPLETED, | | | INCLUDING ROUGHS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-05-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-25 |
Time |
08:07 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-05-25 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2004-05-25 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: ELECTRICAL PLANS OK. | | | 1999 NEC STILL SHOWN ON E-1, THIS CAN | | | BE REDLINED. | | | PREVIOUS PLUMB COMMENTS REFERENCED | | | FS 471.025/ 61G15-23.002 ETC. ENGINEER | | | SHALL ALSO DATE PLANS ALONG WITH HIS | | | SIGNATURE AT ON SAID SEAL, SOME SHEETS | | | DO NOT REFLECT THIS. | | | | | | 2)NOTE: PLEASE SEE COMMENTS FROM OTHER | | | REVIEWERS. | | | | | | PLEASE REMOVE ALL OLD VOIDED SHEETS AND | | | INSERT NEW SHEETS FOR TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-04-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-16 |
Time |
19:55 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-04-16 |
Time |
19:55 |
Sent To |
|
|
| Notes |
| 2004-04-16 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE FBC ADMIN 104.6.5 | | | VALUE OF WORK APPLIED FOR APPLICATION | | | IS SHOWN AS $10K. PLEASE ADJUST VALUE | | | FOR SCOPE OF WORK SHOWN ON PLANS. | | | ADJUSTMENT MAY BE DONE BY PLANS REVIEW | | | TO VALUES SET FORTH BY MARSHAL/SWIFT. | | | | | | 2)NOTE: PLEASE HAVE ENGINEER SIGN PLANS | | | WITH COMPLETE SIGNATURE AS SHOWN ON | | | LICENSE. FS 471.025. INITALS ARE NOT | | | ACCEPTABLE PER FBPE'S. | | | | | | 3)NOTE: PLEASE IDENTIFY LOAD CALCS FOR | | | TRK LT PER 220.12B | | | | | | 4)NOTE: PLEASE VERIFY NEW /OR EXISTING | | | SIGN CIRCUIT. 600.5 | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWS | | | THAT MAY OR MAY NOT HAVE AN AFFECT ON | | | ELECTRICAL PLANS? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-03-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-03-28 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-03-28 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2005-03-28 00:00:00 | 1) PASSED, SEE LAST REVIEW BY NM. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-07-12 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-07-12 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-07-12 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2004-05-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-20 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-20 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2004-05-20 00:00:00 | 1) PREVIOUS COMMENTS NOT ADDRESSED. | | | MORE INFORMATION IS REQUIRED. FIRE | | | LIMITS, TYPE VI CONSTRUCTION NOT | | | ALLOWED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-04-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-04-06 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-04-06 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2004-04-06 00:00:00 | 1) BUILDING ADDRESS REQUIRED. | | | | | | 2) PLEASE INDICATE IN WRITING HOW | | | LONG THE SALES CENTER WILL BE IN | | | OPERATION. | | | | | | 3) THE BUILDING MAY BE LOCATED IN THE | | | CITY FIRE LIMITS. CERTAIN RESTRICTIONS | | | MAY APPLY. TYPE VI CONSTRUCTION IS | | | NOT ALLOWED IN THE FIRE LIMITS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-03-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-29 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-29 |
Time |
13:27 |
Sent To |
B |
|
| Notes |
| 2005-03-29 00:00:00 | TO "JWITMER" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-03-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-03-02 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-03-02 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2005-03-02 00:00:00 | TO "COMM BD" #27 REV. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-07-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-07 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-07 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2004-07-07 00:00:00 | TO COMM BD#17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-05-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-19 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-19 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2004-05-19 00:00:00 | TO COMM BD#1 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-04-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-04-27 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2004-04-01 |
Time |
13:05 |
Sent To |
PC |
|
| Notes |
| 2004-04-01 00:00:00 | TO COMM BD#16 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-03-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-03-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-03-29 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2005-03-28 00:00:00 | PRIVISO | | | 1) PLAESE SHOW THE LOCATION OF THE | | | RETURN AIR FOR THE NEW SPLIT SYSTEM. | | | 2) PLEASE REFER TO SECTION 601.4 | | | BALANCED RETURN AIR FBC.(M) | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-27 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2004-06-03 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2004-07-27 00:00:00 | OK - PER PKRAUSS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-04-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-10 |
Time |
11:59 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-04-10 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2004-04-10 00:00:00 | PROVISO: | | | CONDENSING UNIT STAND SHALL COMPLY WITH | | | 2001 FBC 1511.7: |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-07-27 |
Time |
13:08 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-07-27 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2004-07-27 00:00:00 | PASSED/PROVISO: 607.3.2 THERMAL EXPANS- | | | ION CONTROL REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-06-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-03 |
Time |
17:59 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-06-03 |
Time |
17:59 |
Sent To |
|
|
| Notes |
| 2004-06-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) FROM PREVIOUS REVIEW: #5 - SHT P-2 | | | WATER HEATER DETAIL. THERMAL EXPANSION | | | CONTROL REQUIRED. SECTION 607.3.2 | | | 2) SEE COMMENT #6 FROM PREVIOUS REVIEW. | | | THE DATE THAT THE SIGNATURE AND SEAL IS | | | AFFIXED SHALL BE ENTERED ON PLANS. | | | FAC 61G15-23.002(1) & FS 471.025 - THIS | | | IS REQUIRED ON ALL SHEETS. | | | 3) NEW COMMENT: SHT P-2 WATER RISER DIA- | | | GRAM. AIR CHAMBERS ARE NOT APPROVED AND | | | SHALL BE DELETED FROM RISER. WATER HAMM- | | | ER ARRESTORS ARE REQUIRED AT THE DISH | | | WASHER AND ICE MAKER IN REFRIG. PER SEC. | | | 604.9 AND LOCATED NEXT TO THE FIXTURE, | | | NOT IN THE CEILING. | | | 4) NEW COMMENT: REMOVE ALL OLD/VOIDED | | | SHEETS FROM PLANS. - SUBMIT ONE SET OF | | | OLD/VOIDED SHEETS SEPARATE FROM SET FOR | | | COMPAIRSON. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-04-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-06 |
Time |
06:45 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2004-04-05 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2004-04-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT A-1 KITCHEN SINK SHALL BE ACCESS- | | | IBLE ROOM #10. SUBMIT A DETAIL SHOWING | | | COMPLIANCE WITH 11-4.24 AND ALL SUBSECT- | | | IONS. | | | 2) SHT A-1 TURNING AREA REQUIRED IN KIT- | | | CHEN AREA ROOM #10. SECTION 11-4.2.3 | | | SHOW ON FLOOR PLAN. | | | 3) TABLE 403.1 A DRINKING FOUNTAIN IS | | | REQUIRED. ALSO SEE SECTION 410.1 | | | 4) SHT P-1 RPZ BACKFLOW SHALL BE LOCATED | | | 4' ABOVE FLOOR MAX. FOR SERVICING AND | | | CERTIFICATION. DRAIN TO INDIRECT WASTE. | | | 5) SHT P-1 WATER HEATER DETAIL. THERMAL | | | EXPANSION CONTROL REQUIRED. SECTION | | | 607.3.2 - P/T RELIEF DISCHARGE SHALL NOT | | | HAVE ANY TRAPPED SECTIONS. 504.7.1 | | | 6)A PROFESSIONAL ENGINEER SHALL SIGN HIS | | | NAME AND AFFIX HIS SEAL TO ALL PLANS, | | | SPECIFICATIONS, REPORTS AND FINAL BID | | | DOCUMENTS PROVIDED TO THE OWNER OR THE | | | OWNER'S REPRESENTATIVE, OR OTHER DOCU- | | | MENTS PREPARED OR ISSUED BY SAID REGIS- | | | TRANT AND BEING FILED FOR PUBLIC RECORD. | | | THE DATE THAT THE SIGNATURE AND SEAL IS | | | AFFIXED AS PROVIDED HEREIN SHALL BE EN- | | | TERED ON SAID PLANS, SPECIFICATIONS, RE- | | | PORTS, OR OTHER DOCUMENTS IMMEDIATELY | | | UNDER THE SIGNATURE OF THE PROFESSIONAL | | | ENGINEER, FAC 61G15-23.002(1) | | | FS 471.025 | | | EACH SHEET OF PLANS AND PRINTS WHICH | | | MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 471 SHALL BE SEALED, SIGNED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) | | | FS 471.025 - PER FBPE'S RULING INITIALS | | | ARE NOT ACCEPTABLE. FULL SIGNATURE REQ'D | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2) - FS 471.025 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|