| Plan Review Stops For Permit 04031743 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-02-23 |
Time |
12:54 |
Rev Time |
0.66 |
| Received By |
alange |
Date |
2005-02-17 |
Time |
08:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-01-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-01-20 |
Time |
13:45 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2005-01-20 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2005-01-20 00:00:00 | DENIED | | | THIRD REVIEW FOR THESE SAME COMMENTS: | | | | | | 3. PRODUCT APPROVALS: | | | MISSING FOR ROOFING AND FIXED GLASS. | | | PLEASE SUBMIT 2 COPIES, WITH ATTACHED | | | STATE APPROVAL. | | | PC ALUMINUM DOOR HAS WRONG STATE | | | APPROVAL ATTACHED. | | | | | | 4. C) PERMIT VALUATION HAS BEEN REVISED | | | TO $650,000 AND ADDITIONAL PERMIT FEES | | | OF $7162.56 ARE DUE. | | | | | | 5. SHOW DETAILS FOR THE FOLLOWING: | | | | | | 1015.2 HEIGHT. GUARDRAILS SHALL | | | FORM A VERTICAL PROTECTIVE BARRIER NOT | | | LESS THAN 42" HIGH. | | | 1015.3 OPENINGS. OPEN GUARDRAILS | | | SHALL HAVE INTERMEDIATE RAILS OR ORNA- | | | MENTAL PATTERNS SUCH AS A 4" DIAMETER | | | SPHERE CAN NOT PASS THROUGH. A BOTTOM | | | RAIL OR CURB SHALL BE PROVIDED THAT | | | WILL | | | REJECT THE PASSAGE OF 2" DIAMETER | | | SPHERE. | | | | | | 7.SHOW ROOF DRAIN CALCULATIONS | | | INCLUDING SCUPPER SIZE HEIGHT OF | | | PARAPET | | | WALL AND SQUARE FOOT AREA IN EACH DRAIN | | | AREA. | | | | | | 10. SEE ELECTICAL NOTES #5 REGARDING | | | SMOKE DETECTORS.FBC 905.2 | | | | | | NEW COMMENT: | | | CHANGES MADE TO PLANS MUST BE SIGNED BY | | | THE DESIGNER OF RECORD. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT | | | NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR | | | SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-12-14 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-12-14 |
Time |
13:05 |
Rev Time |
1.66 |
| Received By |
alange |
Date |
2004-12-14 |
Time |
11:22 |
Sent To |
Z |
|
| Notes |
| 2004-12-14 00:00:00 | DENIED | | | | | | 1. 713.13 F.S.A NOTICE OF | | | COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST | | | BE | | | RE-RECORDED IF THE DESCRIBED | | | IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 3. PRODUCT APPROVALS: | | | MISSING FOR ROOFING AND FIXED GLASS. | | | PLEASE SUBMIT 2 COPIES, WITH ATTACHED | | | STATE APPROVAL. | | | PC ALUMINUM DOOR HAS WRONG STATE | | | APPROVAL ATTACHED. | | | | | | 4. C) PERMIT VALUATION HAS BEEN REVISED | | | TO $650,000 AND ADDITIONAL PERMIT FEES | | | OF $7162.56 ARE DUE. | | | | | | 5. SHOW DETAILS FOR THE FOLLOWING: | | | | | | | | | 1015.2 HEIGHT. GUARDRAILS SHALL | | | FORM A VERTICAL PROTECTIVE BARRIER NOT | | | LESS THAN 42" HIGH. | | | 1015.3 OPENINGS. OPEN GUARDRAILS | | | SHALL HAVE INTERMEDIATE RAILS OR ORNA- | | | MENTAL PATTERNS SUCH AS A 4" DIAMETER | | | SPHERE CAN NOT PASS THROUGH. A BOTTOM | | | RAIL OR CURB SHALL BE PROVIDED THAT WILL | | | REJECT THE PASSAGE OF 2" DIAMETER | | | SPHERE. | | | | | | 6.SHOW ATTIC ACCESS SIZE AND LOCATION | | | COMPLYING WITH FBC 2309.6 | | | | | | 7.SHOW ROOF DRAIN CALCULATIONS | | | INCLUDING SCUPPER SIZE HEIGHT OF PARAPET | | | WALL AND SQUARE FOOT AREA IN EACH DRAIN | | | AREA. | | | | | | 9.ENERGY CALCS NOT SIGNED BY | | | OWNER/AGENT. | | | | | | 10. SEE ELECTICAL NOTES #5 REGARDING | | | SMOKE DETECTORS.FBC 905.2 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-10-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2004-08-28 |
Time |
09:56 |
Rev Time |
3.25 |
| Received By |
alange |
Date |
2004-10-06 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2004-10-06 00:00:00 | DENIED | | | | | | 1. THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY | | | COURTHOUSEAND A COPY SUBMITTED TO THIS | | | OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | | | 2. BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.MANY PRODUCT APPROVALS MISSING | | | SUBMIT 2 COPIES OF THE FOLLOWING: | | | ROOFING, STRAPS AND TIEDOWNS, ALL | | | EXTERIOR WINDOWS AND DOORS, GARAGE DOORS | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATIONPLEASE SEE THE STATE WEBSITE | | | AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4.PLEASE VERIFY THE FOLLOWING: | | | A) WILL YOU BE TIEING INTO EXISTING | | | BUILDING OR DEMOLISHING EXISTING. IF | | | TIEING IN SHOW TIEIN DETAIL. | | | B)SHOW ON PLAN EXISTING SQUARE | | | FOOTAGE ALONG WITH NEW SQUARE FOOTAGE. | | | C)BUILDING VALUATION IS TOO LAOW AND | | | WILL BE CALCULATED ONCE FOOTAGE IS | | | CALCULATED. | | | | | | 5.1015.2 HEIGHT. GUARDRAILS SHALL | | | FORM A VERTICAL PROTECTIVE BARRIER NOT | | | LESS THAN 42" HIGH. | | | 1015.3 OPENINGS. OPEN GUARDRAILS | | | SHALL HAVE INTERMEDIATE RAILS OR ORNA- | | | MENTAL PATTERNS SUCH AS A 4" DIAMETER | | | SPHERE CAN NOT PASS THROUGH. A BOTTOM | | | RAIL OR CURB SHALL BE PROVIDED THAT | | | WILLREJECT THE PASSAGE OF 2" DIAMETER | | | SPHERE. | | | | | | 6.ATTIC ACCESS SHALL COMPLY WITH FBC | | | 2309.6 SHOW SIZE ON PLAN. | | | | | | 7.SHOW ROOF DRAINAGE CALCULATIONS | | | SHOWING SIZE OF SCUPPERS AND SLOPEING. | | | | | | 8.SUBMIT 2 COPIES OF SITE PLAN | | | SHOWINGNEW AND EXISTING BUILDINGS ON | | | PLAN. | | | | | | 9. SUBMIT 2 COPIES OF ENERGY CALS. | | | | | | 10.905.2.1 APPROVED SINGLE-STATION OR | | | MULTIPLE STATION SMOKE DETECTORS SHALL | | | BE INSTALLED IN ACCORDANCE WITH NFPA | | | 72,CHAPTER 2, WITHIN EVERY DWELLING | | | UNITWITHIN AN APARTMENT HOUSE, | | | CONDOMINIMUM,OR TOWNHOUSE AND EVERY | | | GUEST OR SLEEPINGROOM IN A MOTEL, | | | HOTEL, OR DORMITORY & | | | SLEEPING ROOMS IN RESIDENTIAL CARE/ | | | ASSISTED LIVING OCCUPANCIES. WHERE MORE | | | THAN ONE DETECTOR IS REQUIRED TO BE | | | INSTALLED WITHIN INDIVIDUAL DWELLING | | | UNIT, THE DETECTOR SHALL BE WIRED IN | | | SUCH A MANNER THAT THE ACTUATION OF ONE | | | ALARM WILL ACTIVATE ALL THE ALARMS IN | | | THE INDIVIDUAL UNIT. | | | | | | 11.SUBMIT SCHEDULE FOR STRAPS AND | | | TIE-DOWNS INCLUDING UPLIFTS AND | | | FASTENERS USED. | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | ART LANGE | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6672 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-02-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-22 |
Time |
17:48 |
Rev Time |
0.60 |
| Received By |
dpalmer |
Date |
2005-02-22 |
Time |
17:26 |
Sent To |
M |
|
| Notes |
| 2005-02-22 00:00:00 | ********** NOTES REDLINED ********* | | | | | | 1)NOTE: PLEASE SEE CIRCUITING FOR SD'S, | | | ALL ARE SHOWN ON MULTIPLE CIRCUITS, | | | HOWEVER SD'S ARE REQUIRED TO BE WIRED | | | "INLINE". MULTIPLE CIRCUITS WILL NOT | | | WORK. | | | | | | 2)NOTE: PLEASE CORRELATE LOADS FOR POOL | | | PUMP AND HEAT. LOAD CALCS/ PANEL | | | SCHEDULE LOAD. | | | | | | | | | | | | | | | REVISE CIRCUTING AND PANEL SCHEDULE | | | BEFORE FINAL. | | | | | | ALL OTHER REVISIONS TO BE SUBMITTED FOR | | | REVIEW BEFORE ROUGH. | | | CORRECT SD CIRCUTING AT THAT TIME. | | | | | | PLANS TO GO TO BLDG REVIEW ALSO, DUE TO | | | HAND-DRAWN CHNAGES TO SIGNED AND SEALED | | | PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2005-02-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-07 |
Time |
16:22 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-02-07 |
Time |
14:47 |
Sent To |
M |
|
| Notes |
| 2005-02-07 00:00:00 | ************** UNSAT 4TH REVIEW ****** | | | | | | PLEASE SEE THE FOLLOWING NOTES: | | | | | | 1)NOTE: PLEASE SEE RISER HAS NOW COME | | | BACK SHOWING WHAT APPEARS TO BE | | | 2-METERS? PLEASE SEE THIS IS A SF HOUSE | | | AND IS ONLY PERMITTED TO HAVE ONE | | | METER. | | | | | | 2)NOTE: PLEASE THE TITLE BLOCK IS NOW | | | CONTAINING THE NAME OF "WALTER KARPINA" | | | AS ONE OF THE ENGINEER'S OF RECORD? | | | PLEASE REMOVE FROM TITLE BLOCK. | | | | | | 3)NOTE: PLEASE SEE ONLY ONE SET OF | | | ELECTRICAL PLANS WERE SUBMITTED FOR | | | REVIEW. | | | | | | 4)NOTE: ** PLEASE SEE BATH CIRCUITS ARE | | | NOW BEING SHOWN AS "ARC-FAULT" | | | PROTECTED?? | | | | | | 5)NOTE: PLEASE SEE HANDDRAWN CHANGES | | | MADE TO SIGNED AND SEALED PLANS. | | | FS 471 | | | | | | PLEASE SEE THE ONE COPY OF ELECTRICAL | | | PLANS SUBMITTED IS BEING RETAINED FOR | | | FILE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-01-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-12 |
Time |
17:07 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-01-12 |
Time |
16:37 |
Sent To |
P |
|
| Notes |
| 2005-01-12 00:00:00 | *********** UNSAT 3RD REVIEW | | | *********** | | | | | | PLEASE SEE ALMOST ALL NOTES FROM FIRST | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE NOTES #'S | | | 1,4,5,6,7,8,9,10,13 | | | | | | | | | | | | 1)NOTE: PLEASE SEE PLANS ARE NOW COMING | | | BACK WITHOUT ANY RISER DIAGRAM, PANEL | | | SCHEDULES, LOAD CALCUALTIONS ETC. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE THERE IS NOW GFI | | | RECEPTS SHOWN ON PLANS IN FAMILY RM IN | | | MIDDLE OF DOORWAY??? | | | | | | **NOTE: PLANS STILL INDICATE NUMEROUS | | | GFI'S AND RECEPTS IN MANY PLACES NOT | | | REQUIRED. THIS IS ONLY A NOTE: IF SHOWN | | | ON PLANS, THEN THEY WILL BE REQUIRED TO | | | BE INSTALLED.** | | | | | | | | | | | | *** PLEASE NOTE THESE PLANS HAVE NOW | | | BEEN REVIEW THREE TIMES FOR 2002 NEC | | | CODE COMPLIANCEAND CODE COMPLIANCE HAS | | | NOT BEEN ACHIEVED. | | | PLEASE SEE ONE SET OF ELECTRICAL PLANS | | | ARE NOW BEING RETAINED FOR POSSIBLE | | | REVIEW BY THE STATE BOARD. | | | PLEASE BE SURE ALL COMMENTS ARE | | | ADDRESSED. | | | | | | | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-11-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-17 |
Time |
06:53 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-11-17 |
Time |
06:52 |
Sent To |
P |
|
| Notes |
| 2004-11-17 00:00:00 | *********** UNSAT ***************** | | | | | | **PLANS NEED TO BE SUBMITTED FOR 2002 | | | NEC CODE COMPLIANCE. | | | PLEASE SEE THE FOLLOWING COMMENTS. | | | | | | 1)NOTE: PLEASE SUBMIT A COMPLETED RISER | | | DIAGRAM TO MEET CODE COMPLIANCE. | | | 215.5, 240.4,310.15B6/310.16, 240.4, | | | 250.24, 250.122 ETC | | | PLEASE SHOW A ON-LINE DIAGRAM FOR | | | SERVICE AS IF LOOKING AT FRONT ELEVATION | | | OF RISER. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | | | | 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | | | | 4)NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | | | | 5)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | | | | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | TO MEET 220.31. | | | PLEASE SEE LIGHTING LOAD FOR HOUSE, THIS | | | DOES NOT CORRELATE WITH PLANS FOR SQ FT | | | AND ALSO THE AMOUNT OF CIRCUITS NEEDED. | | | SHOWS ALL 15A, #14. | | | PLEASE SEE ALL CONTINUOUS LOADS (POOL | | | PUMP, HEAT PUMP ARE TO BE SHOWN AT | | | 125%. | | | 230.42,215.3 ETC. | | | | | | 7)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52D IN MASTER BATH, YET AREA FOR | | | ROMAN TUB SHOWS 7-GFI RECEPTS?? | | | | | | 8)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | 9)NOTE: PLEAS LIST ARC FAULT PROTECTED | | | CIRCUITS ON PANEL SCHEDULE. 210.12 2002 | | | NEC. | | | | | | 10)NOTE: PLEASE SHOW LOCATION OF ALL | | | SERVICE EQUIPMENT. PLANS ONLY SHOW PANEL | | | IN STORAGE RM.215.5 | | | | | | 11)NOTE: PLEASE SEE 104.2.1 OF THE FBC | | | FOR REQUIREMENTS OF PLANS. | | | | | | 12)NOTE: PLEASE SHOW ALL A/C EUIPMENT | | | AND LOCATIONS OF THAT EQUIP. PLEASE | | | INCLUDE DISCONNETS REQUIRED FOR THIS. | | | 440.11 (COND UNITS). | | | PLEASE SHOW ANNY POSSIBLE GFI'S REQUIRED | | | FOR A/C EQUIPMENT. 210.63 | | | | | | 13)NOTE: PLEASE CORRELATE ALL A/C | | | EQUIPMENT WITH MECHNICAL PLANS. | | | PLEASE CORRELATE LOAD CALCULATIONS WITH | | | MECH PLANS ALSO. 215.5 | | | | | | ** PLEASE SEE RECEPT SPACING ON PLANS, | | | MOST RECEPT SPACING IS WAY ABOVE WHAT IS | | | NEED FOR 210.52, THESE ARE PERMITTED | | | YET SEEM TO BE MORE THAN NEEDED.** | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-08-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-23 |
Time |
13:56 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-08-23 |
Time |
13:42 |
Sent To |
M |
|
| Notes |
| 2004-08-23 00:00:00 | ********** UNSAT*************** | | | | | | 1)NOTE: PLEASE SEE NO PLANS WERE | | | SUBMITTED FOR REVIEW. | | | PLEASE SUBMIT TWO SETS OF ELECTRICAL | | | PLANS SHOWING ALL MIN ELECTRICAL | | | REQUIRED UNDER 2002 NEC.210.52,210.11, | | | 220, 210.8 ETC. | | | PLEASE SUBMIT PANEL SCHEDULE SHOWING MIN | | | REQUIRED CIRCUITS. | | | PLEASE SUBMIT RISER DIAGRAM AND LOAD | | | CALCULATIONS. | | | 220.31,215.5 ETC. | | | FBC 101.4.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-02-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-18 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-18 |
Time |
15:28 |
Sent To |
E |
|
| Notes |
| 2005-02-18 00:00:00 | TO DPALMER DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-02-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-03 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-03 |
Time |
09:49 |
Sent To |
E |
|
| Notes |
| 2005-02-03 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-07 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-07 |
Time |
15:22 |
Sent To |
E |
|
| Notes |
| 2005-01-07 00:00:00 | TO "DP:DESK./RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-12 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-12 |
Time |
11:10 |
Sent To |
E |
|
| Notes |
| 2004-11-12 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-12 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-08-12 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-05-12 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-05-12 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2004-04-05 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2004-08-20 00:00:00 | TO SFD RACK/E | | 2004-08-12 00:00:00 | TO Z/RESUB | | 2004-04-05 00:00:00 | TO Z |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-02-23 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-02-23 |
Time |
12:31 |
Rev Time |
1.00 |
| Received By |
prafter |
Date |
2005-02-23 |
Time |
12:54 |
Sent To |
B |
|
| Notes |
| 2005-02-23 00:00:00 | MECH.REVIEW CHECK LIST 02/14/05 | | | ANSEWERED SATIFACTORY. | | | PAT RAFTER 561/805/6728. | | | PLEASE CALL IF THEAR ENY QUESTIONS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2005-02-14 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-02-14 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
prafter |
Date |
2005-02-23 |
Time |
12:21 |
Sent To |
B |
|
| Notes |
| 2005-02-23 00:00:00 | MECH. NOTES 1.AND 2.WERE ANSEWERED, | | | A/C OK. | | | PAT RAFTER 561/805/6728 | | | PLEASE CALL IF ENY QUESTIONS. | | 2005-02-14 00:00:00 | 1. A.H.U. #3R/A FROM LIBRARY NOT | | | REFLECTED ON PLAN .2001 FBC/M 601.4 | | | BALANCED RETURN AIR. | | | | | | 2. A.H.U. #1 AND #2 REQUIRE DUCTED R/A | | | THROUGH NON LIVING AREA TO A.H.U. AND | | | SECONT FLOOR PLAN REFLECTS DOORS | | | SEPERATING LIVING ROOM/LOGGIA ROOM FROM | | | HALL WAY. | | | PLEASE CLEARFIE R/A ROUTING. | | | PAT RAFTER 561/805/6728. | | | IF THEAR ENY QUISTION PLEASE CALL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-12-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2004-12-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2004-12-04 |
Time |
|
Sent To |
B |
|
| Notes |
| 2004-12-04 00:00:00 | PLAN DENIED | | | 1) REFER TO SECTION 610.ABC.3.5.2 | | | FL.ENERGY CODE | | | 2) REFER TO SECTION 601.4 BALANCED | | | RETURN AIR | | | 3) NEED MORE INFORMATION ON RETURN AIR | | | OFF AIRHANDLERS | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-23 |
Time |
13:56 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2004-08-25 |
Time |
08:48 |
Sent To |
P |
|
| Notes |
| 2004-08-25 00:00:00 | DENIED: | | | NO MECHANICAL PLANS, ENERGY & MANUAL J | | | CALCULATIONS, OR EQUIPMENT SCHEDULE | | | PROVIDE WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-01-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-01-15 |
Time |
14:35 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-01-15 |
Time |
14:35 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-11-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-24 |
Time |
17:18 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-11-24 |
Time |
17:18 |
Sent To |
M |
|
| Notes |
| 2004-11-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS, NOR DOES IT REFLECT | | | THE FLOOR PLAN. | | | A) THE WASH MACHINE REQUIRES A CLEANOUT | | | 4 FEET ABOVE THE FLOOR FOR ACCESS, AND A | | | STANDPIPE. SECTIONS 708.10, & 1002.1 | | | B) THE FIRST FLOOR BATHROOM SHOWS THE | | | TUB AND LAV ON THE SAME WALL AND THE LAV | | | ON THE LEFT OF THE W/C ON THE RISER | | | DIAGRAM, BUT ON THE FLOOR PLAN THE TUB | | | AND LAV ARE ON DIFFERENT WALLS. SECTION | | | 104.2.1. | | | C) THE FIRST FLOOR W/C SHALL NOT BE | | | DOUBLE TRAPPED. SECTION 1002.1. THE W/C | | | HAS AN INTEGRAL TRAP. | | | D) TWO BIDETS SHOWN ON THE FLOOR PLAN | | | ARE NOT SHOWN ON THE RISER DIAGRAM. | | | SECTION 104.2.1 | | | E) ALL W/C'S SHALL NOT BE DOUBLE | | | TRAPPED. SECTION 1002.1 | | | F) THE BATHROOM LAYOUTS ON THE RISER | | | DIAGRAM DO NOT REFLECT THE FLOOR PLAN. | | | SECTION 104.2.1 | | | G) NO HORIZONTAL DRY VENTS AS SHOWN | | | PAST ALL THE SHOWERS ON THE SECOND FLOOR | | | ON THE RISER DIAGRAM. SECTION 905.3. | | | 2) SEE RED LINE EXAMPLE OF A RISER | | | DIAGRAM THAT REFLECTS THE FLOOR PLAN AND | | | MEETS THE CODE REQUIREMENTS. | | | 3) ALL DRAWING SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DOCUMENT. SECTION 104.2.1 | | | | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-08-25 |
Time |
09:13 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2004-08-28 |
Time |
09:56 |
Sent To |
B |
|
| Notes |
| 2004-08-28 00:00:00 | NO RISER DIAGRAM. NOT ENOUGH INFORMATION | | | TO DO A PLUMBING PLAN REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-12-15 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-12-15 |
Time |
15:30 |
Sent To |
I |
|
| Notes |
| 2004-12-15 00:00:00 | NEED TO PULL SEPERATE FOR RETAINING WALL | | | WITH UTILITY EASEMENT APPROVAL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2004-08-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-08-19 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-08-19 |
Time |
09:17 |
Sent To |
I |
|
| Notes |
| 2004-08-19 00:00:00 | DENIED, NEED TO PROVIDE TWO COPY OF | | | SURVEY OR SITEPLAN TO SCALE SHOWING THE | | | TWO STORY RESIDENCE.CALLED KEITH | | | CONTRACTOR MM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-04-09 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-04-09 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-04-09 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2004-04-09 00:00:00 | DENIED, NEED TO MEET 25FT IN FRONT SET | | | BACK OR REMOVE THE GARAGES.WILL GET | | | WITH ANGELLA JONES-VANN ON WHAT WAS | | | DISCUSSED BEFORE. FILE K MM |
|
|