Plan Review Details - Permit 04031701
Plan Review Stops For Permit 04031701
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-08 Cont ID  
Sent By jwitmer Date 2004-12-08 Time 08:28 Rev Time 0.55
Received By jwitmer Date 2004-12-08 Time 08:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-19 Cont ID  
Sent By jwitmer Date 2004-06-19 Time 13:07 Rev Time 0.55
Received By jwitmer Date 2004-06-19 Time 13:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By jwitmer Date 2004-04-28 Time 07:26 Rev Time 1.40
Received By jwitmer Date 2004-04-28 Time 07:26 Sent To PC
Notes
2004-04-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031701
 ADD: 633 10TH ST
 CONT: RICHARD BUEU
 TEL: (754)422-6896
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PRIMARY ENTRY DOOR OF COVERED
 DWELLING UNITS IS PART OF PUBLIC AND
 COMMON USE SPACES, THEREFORE, IT MUST BE
 ON AN ACCESSIBLE ROUTE & BE ACCESSIBLE,
 I.E., MEET THE ANSI REQUIREMENTS OF
 4.13 DOORS. ANSI 4.13.9 LEVER OR OTHER
 EASY USE DOOR HARDWARE.
  
 3) PRIMARY ENTRY DOORS TO COVERED
 UNITS MUST BE ON AN ACCESSIBLE ROUTE,
 THRESHOLDS AT THESE DOORS MUST BE NO
 HIGHER THAN 3/4" AND MUST BE BEVELED
 WITH A SLOPE NO GREATER THAN 1:2.
  
 4)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 PROVIDE LOCAL PRODUCT APPROVAL FOR
 THE RAISED WOOD DOOR FROM FLORIDA LUMBER
 COMPANY. NOT LISTED ON THE STATE PRODUCT
 APPROVAL SYSTEM OR SUBMIT A DIFFERENT
 APPROVED PRODUCT.
  
 7) THE SINGLE HUNG WINDOW SUBMITTED FROM
 PGT, INDICATE WHICH GLASS STRENGTH THAT
 WILL BE USED, 3/16" DSB OR SSB, THE
 ALLOWABLE PRESSURES VERY UPON THE
 STRENGTH OF GLAZING USED.
  
 8) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-12-03 Cont ID  
Sent By dpalmer Date 2004-12-03 Time 06:53 Rev Time 0.33
Received By dpalmer Date 2004-12-03 Time 06:53 Sent To  
Notes
2004-12-03 00:00:00NOC EXPIRED, SEE BLDG .

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-08-18 Cont ID  
Sent By dpalmer Date 2004-08-18 Time 16:21 Rev Time 0.50
Received By dpalmer Date 2004-08-18 Time 16:19 Sent To  
Notes
2004-08-18 00:00:00********** UNSAT 3RD REVIEW *********
  
 PLEASE SEE THE FOLLOWING NOTES FROM
 FIRST TWO REVIEWS STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 NO.
 PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE SEE THIS IS STILL SHOWN ON W/
 GEN LTS AND RECEPTS,SD'S .
  
 5)NOTE: NOTE #5 OK
  
 6)NOTE: NOTE #6 NO.
 PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 SD'S STILL NOT SHOWN ON ARC FAULT PRO-
 -TECTED CIRCUITS.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 NO.
 PLEASE SEE A/C KW STILL SHOWN AS 4KW.
 PLEASE CORRELATE. ELECTRICAL PLANS WERE
 CORRECTED, HOWEVER A/C PLANS STILL SHOW
 4KW.
  
 9)NOTE: NOTE #9 OK
  
 10)NOTE: PLEASE SEE 250.58, REDLINE
 ITEM.
  
 11)NOTE: PLEASE SEE A NOTICE WAS GIVEN
 ON PREVIOUS REVIEW WITH RESPECT TO
 DESIGN PROFESSIONAL PER FS 553.80(2)(B)
 WHICH REQUIRES A 4X FEE FOR PLAN REVIEW
 PORTION OF PERMIT FEE FOR ANY OF THE
 SAME CODE COMPLIANCE NOT ADDRESSED THREE
 OR MORE TIMES.
 PLEASE SEE A 4X FEE FOR PLAN REVIEW HAS
 NOW BEEN ACCESSED.
 PLEASE SEE BZ#245127 $960.00 ATTACHED TO
 PLANS. THIS IS REQUIRED UNDER STATE LAW
 AND MUST BE PAID ALONG WITH RESUB FEE
 BEFORE SUBMITTING PLANS FOR REVIEW.
 PLEASE SEE ONE SET OF ELECTRICAL SHEETS
 FROM EACH SUBMITTAL HAS NOW BEEN RETAIN-
 -ED FOR FILE. PLANS AT THIS TIME MAY BE
 FILED FOR REVIEW BY STATE BOARD OF ARCH.
 **PLEASE SEE AS OF TODAY'S DATE, NO
 ONE HAS CONTACTED MYSELF TO GO OVER
 COMMENTS. NAME, PHONE # AND E-MAIL
 ADDRESS HAS BEEN AT THE BOTTOM OF EACH
 REVIEW NOTES.** PLEASE DO NOT HESITATE
 IN CONTACTING ME IF THERE ARE ANY
 QUESTIONS.
  
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-04 Cont ID  
Sent By csiegber Date 2004-08-12 Time 15:12 Rev Time 1.00
Received By dpalmer Date 2004-06-04 Time 14:20 Sent To  
Notes
2004-06-04 00:00:00********* UNSAT ***********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 WERE NOT ADDRESSED.
  
 NOTE #1 NO. GROUPING OF MAINS NOT SHOWN
 PLEASE SEE CONDUCTORS ARE STILL SHOWN
 OVERSIZED BUT PERMITTED.
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN DISC TO PANEL.
 250.110,250.24, SIZE PER 250.122
  
 NOTE #2 OK
  
 NOTE #3 SM APPL CIRCUITS ADDED, HOWEVER
 WRONG LOAD IS SHOWN PER 220.16.
  
 NOTE #4 NO
  
 NOTE #5 OK
  
 NOTE #6 NO
  
 NOTE #7 OK
  
 NOTE #8 ?? 4KW STILL SHOWN FOR HEAT LOAD
 ?
 NOTE #9 OK
  
 NEW NOTE:
 1)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) THIS IS GIVEN AS A
 NOTICE AFTER SECOND REVIEW W/ ANY OF THE
 SAME COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-16 Cont ID  
Sent By dpalmer Date 2004-04-16 Time 20:27 Rev Time 0.50
Received By dpalmer Date 2004-04-16 Time 20:20 Sent To  
Notes
2004-04-16 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY SERVICE SHOWN??
 SHOWS NEW 100A METERCAN WITH 500MCM
 FEEDING CAN? ALSO SHOWS NEW 3/0'S FEED-
 -ING 100A DISC. PLEASE VERIFY SIZE OF
 LUGS. LARGER CONDUCTORS MAY BE USED
 BUT SEEMED TO BE OVERSIZED FOR 100A SERV
 ICE?
 PLEASE VERIFY GROUPING OF MAINS FOR
 BLDG. 230.72. ETC.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE 210.11C1 FOR A MIN
 OF TWO SM APPL CIRCUITS REQ'D. 220.16
 ONE SHOWN.
  
 4)NOTE: PLEASE SEE210.11C3 FOR MIN
 REQ'D FOR BATH. THIS IS NOT ON W/ GEN
 LT ANS RECEPTS AS INDICATED.
  
 5)NOTE: PLEASE SEE PLANS REFERENCE THE
 1999 NEC. THE STATE ADOPTED THE 2002 NEC
 JULY 1ST, 2003
  
 6)NOTE: PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION REQ'D. SD'S ARE SHOWN ON
 BATH/LTS W/OUT AFCI.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 2' OF WALL PER 210.52 BDRM#2
  
 8)NOTE: PLEASE CHECK KW RATING SHOWN
 FOR AHU HEAT. 4KW IS NOT A COMMON SIZE.
  
 9)NOTE: PLEASE SHOW DISC MEANS FOR A/C
 COND UNIT. 440.11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-16 Cont ID  
Sent By nmccray Date 2004-12-16 Time 12:29 Rev Time 0.00
Received By nmccray Date 2004-12-16 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-04-06 Cont ID  
Sent By nmccray Date 2004-04-06 Time 13:26 Rev Time 0.00
Received By nmccray Date 2004-04-06 Time 13:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-01 Cont ID  
Sent By mjacobs Date 2004-12-01 Time 07:16 Rev Time 0.00
Received By mjacobs Date 2004-12-01 Time 16:35 Sent To  
Notes
2004-12-01 00:00:00SENT TO "COMM BD#4

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-12 Time 15:11 Rev Time 0.00
Received By csiegber Date 2004-08-12 Time 15:11 Sent To E
Notes
2004-08-12 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-19 Cont ID  
Sent By csiegber Date 2004-06-02 Time 14:46 Rev Time 0.00
Received By jwitmer Date 2004-06-02 Time 14:46 Sent To PC
Notes
2004-06-02 00:00:00TO COMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-28 Cont ID  
Sent By jwitmer Date 2004-04-28 Time 09:23 Rev Time 0.00
Received By jwitmer Date 2004-04-02 Time 10:25 Sent To PC
Notes
2004-04-02 00:00:00TO COMM BD#17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-23 Cont ID  
Sent By pkrauss Date 2004-12-23 Time 08:56 Rev Time 0.40
Received By pkrauss Date 2004-12-23 Time 07:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-21 Cont ID  
Sent By pkrauss Date 2004-04-21 Time 11:03 Rev Time 0.40
Received By pkrauss Date 2004-04-21 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-04-17 Cont ID  
Sent By kstevens Date 2004-04-17 Time 14:32 Rev Time 0.33
Received By kstevens Date 2004-04-17 Time 14:32 Sent To  
Notes
2004-04-17 00:00:00NO PLUMBING PLANS SUBMITTED - CONDENSATE
 SHALL DISCHARGE AT LEAST 1 FOOT FROM
 STRUCTURE WALL - SECTION 1503.4.4