Plan Review Details - Permit 04031653
Plan Review Stops For Permit 04031653
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 12:00 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 12:00 Sent To P
Notes
2004-05-06 00:00:00TO GAS/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-06 Time 08:49 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 08:49 Sent To P
Notes
2004-04-06 00:00:00TO GAS/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-31 Cont ID  
Sent By alange Date 2004-03-31 Time 10:46 Rev Time 0.00
Received By alange Date 2004-03-31 Time 10:46 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-10 Cont ID  
Sent By csiegber Date 2004-05-06 Time 12:00 Rev Time 1.00
Received By kstevens Date 2004-04-10 Time 12:43 Sent To  
Notes
2004-04-10 00:00:00 
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
  
 Z

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-04-06 Time 08:49 Rev Time 0.50
Received By kstevens Date 2004-04-03 Time 15:06 Sent To  
Notes
2004-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A) THE FOLLOWING INFORMATION IS REQUIRED
 AT TIME OF APPLICATION FOR GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 4) SEE ATTACHED SHEET FOR GAS PERMIT RE-
 QUIREMENTS FOR FUTURE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]