Plan Review Details - Permit 04031591
Plan Review Stops For Permit 04031591
Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2007-12-24 Cont ID  
Sent By rbrown Date 2007-12-24 Time 17:11 Rev Time 0.00
Received By rbrown Date 2007-12-24 Time 17:11 Sent To  
Notes
2007-12-24 17:12:54REVISION FOR SHEETS A0-2, A0-3, A1-0, A1-1, A2-0, A2-1,
 A2-2, AND A2-3

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status F Date 2007-09-30 Cont ID  
Sent By rbrown Date 2007-09-30 Time 15:08 Rev Time 0.00
Received By rbrown Date 2007-09-30 Time 15:08 Sent To  
Notes
2007-09-30 15:09:22BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 7/27/07 FOR PARKING SPACE LAYOUT
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FAIR HOUSING ACT REQUIREMENT 2 AND FBC
 11-4.1.2(5)(A)-NUMBER OF ACCESSIBLE PARKING SPACES.
 THE SUBMITTED REVISED PLANS SHOW A PROPOSAL TO REDUCE
 THE NUMBER OF ACCESSIBLE PARKING SPACES BUT A REVISED
 SHEET A0-2 (REVISION # 38 IS THE LATEST ON FILE) HAS
 NOT BEEN SUBMITTED WITH A REVISED PARKING SPACE TABLE.
 TO PROCEED WITH THIS REVISION THE PARKING TABLE MUST BE
 REVISED TO DEMONSTRATE COMPLIANCE WITH THE FAIR HOUSING
 ACT REQUIREMENT FOR 2% OF THE PARKING SPACES TO BE
 ACCESSIBLE, AND FBC 11-4.1.2(5)(A) REQUIREMENT FOR
 COMMERCIAL SPACE (INCLUDING LIVE/WORK LOFTS) TO HAVE 1
 ACCESSIBLE SPACE FOR EVERY 25 PARKING SPACES.
  
 2)FBC 3203-THE SUBMITTED REVISED PLANS SHOW LOFT
 DOORS SWINGING ACROSS THE NORTH PROPERTY LINE INTO THE
 PUBLIC RIGHT OF WAY.THE LATEST REVISION OF THE GROUND
 LEVEL PLANS ON FILE SHOW INSWING DOORS.DOORS SHALL
 NOT SWING OVER PUBLIC PROPERTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status F Date 2007-09-30 Cont ID  
Sent By rbrown Date 2007-09-30 Time 14:34 Rev Time 0.00
Received By rbrown Date 2007-09-30 Time 14:34 Sent To  
Notes
2007-09-30 14:57:53BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 7/27/07 FOR PARKING SPACE LAYOUT
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FAIR HOUSING ACT REQUIREMENT 2 AND FBC
 11-4.1.2(5)(A)-NUMBER OF ACCESSIBLE PARKING SPACES.
 THE SUBMITTED REVISED PLANS SHOW A PROPOSAL TO REDUCE
 THE NUMBER OF ACCESSIBLE PARKING SPACES BUT A REVISED
 SHEET A0-2 (REVISION # 38 IS THE LATEST ON FILE) HAS
 NOT BEEN SUBMITTED WITH A REVISED PARKING SPACE TABLE.
 TO PROCEED WITH THIS REVISION THE PARKING TABLE MUST BE
 REVISED TO DEMONSTRATE COMPLIANCE WITH THE FAIR HOUSING
 ACT REQUIREMENT FOR 2% OF THE PARKING SPACES TO BE
 ACCESSIBLE, AND FBC 11-4.1.2(5)(A) REQUIREMENT FOR
 COMMERCIAL SPACE (INCLUDING LIVE/WORK LOFTS) TO HAVE 1
 ACCESSIBLE SPACE FOR EVERY 25 PARKING SPACES.
  
 2)FBC 3203-THE SUBMITTED REVISED PLANS SHOW A
 NUMBER OF REVISIONS THAT HAVE NOT BEEN SUBMITTED
 PREVIOUSLY, INCLUDING LOFT DOORS SWINGING ACROSS THE
 NORTH PROPERTY LINE INTO THEPUBLIC RIGHT OF WAY.THE
 LATEST REVISION OF THE GROUND LEVEL PLANS ON FILE SHOW
 INSWING DOORS.DOORS SHALL NOT SWING OVER PUBLIC
 PROPERTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2007-09-30 Cont ID  
Sent By rbrown Date 2007-09-30 Time 14:31 Rev Time 0.00
Received By rbrown Date 2007-09-30 Time 14:30 Sent To  
Notes
2007-09-30 14:33:42REVISION SUBMITTED ON 7/19/07.OK EXCEPT SHEET A0-3
 DENIED BY PLANNING DEPT, AND SHEET A8-1 DENIED BY
 ELECTRICAL FOR BUS DUCT DETAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2007-08-05 Cont ID  
Sent By rbrown Date 2007-08-05 Time 19:01 Rev Time 0.00
Received By rbrown Date 2007-08-05 Time 19:01 Sent To  
Notes
2007-08-05 19:02:04SUBMITTAL ON 7/19/07 FOR SHOP DRAWING FOR LIGHT GAGE
 STEELFRAMINGTO SOFFIT AT ALLEY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status F Date 2007-07-14 Cont ID  
Sent By rbrown Date 2007-07-14 Time 14:42 Rev Time 0.00
Received By rbrown Date 2007-07-14 Time 14:42 Sent To  
Notes
2007-07-14 14:53:09BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 7/9/07 FOR SHOP DRAWING AND CALCULATIONS
 FOR LIGHT GAGE STEELFRAMINGTO SOFFIT AT ALLEY.
  
 1)ONLY ONE SIGNED AND SEALED COPY SUBMITTED.THREE
 SIGNED AND SEALED COPIES ARE REQUIRED, AND ALL THREE
 SHALL HAVE ORIGINAL SHOP REVIEW STAMP FROM THE ENGINEER
 OF RECORD.
  
 2) EVERY SHEET OF THE REQUIRED COPIES OF THE
 CALCULATIONS AND SHOP DRAWING (SEE COMMENT ABOVE) SHALL
 INCLUDE THE PRINTED NAME AND LICENSE NUMBER (P.E.
 41830) FOR RABIH J. BOUERI, P.E., AND THE CERTIFICATE
 OF AUTHORIZATION NUMBER (COA# 5336) FOR THE COMPANY,
 BOUERI ENGINEERS, INC.THIS MAY BE ADDED BY HAND TO
 EACH COPY.THE REQUIRED INFORMATION HAS BEEN ADDED (BY
 PLAN REVIEWER) TO THE COPY SUBMITTED HERE BUT FURTHER
 COPIES WILL BE DENIED IF SUBMITTED WITHOUT THIS
 INFORMATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status P Date 2007-06-16 Cont ID  
Sent By rbrown Date 2007-06-16 Time 16:41 Rev Time 0.00
Received By rbrown Date 2007-06-16 Time 16:41 Sent To  
Notes
2007-06-16 16:42:26REVISION SUBMITTED ON 4/11/07 FOR SHEETS A1-14, A1-15
 AND A8-2.ALSO REVIEWED BY PLUMBING FOR OVERFLOW
 SCUPPERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2007-06-16 Cont ID  
Sent By rbrown Date 2007-06-16 Time 15:39 Rev Time 0.00
Received By rbrown Date 2007-06-16 Time 15:39 Sent To  
Notes
2007-06-16 15:40:57REVSION SUBMITTED ON 3/19/07 FOR SHEET A0-2 CHANGE
 OCCUPANCY TYPE FROM "R" TO "R2" ON THE BUILDING DATA
 TABLE

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2007-06-16 Cont ID  
Sent By rbrown Date 2007-06-16 Time 10:52 Rev Time 0.00
Received By rbrown Date 2007-06-16 Time 10:51 Sent To  
Notes
2007-06-16 10:54:12SUBMITTAL ON 3/21/07 FOR H.M. A/C CLOSET DOOR SPEC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2007-05-10 Cont ID  
Sent By rbrown Date 2007-05-10 Time 10:26 Rev Time 0.00
Received By rbrown Date 2007-05-10 Time 10:26 Sent To  
Notes
2007-05-10 10:27:09REVISION SUBMITTED ON 4/19/07 FOR DELTA DOORS
 MANUFACTURING'S SERIES DH-350 ALUMINUM IN-SWING DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 15:17 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 15:17 Sent To  
Notes
2007-02-11 15:20:00REVISION SUBMITTED 12/18/06 TO INCLUDE STRUCTURAL
 DETAILS FOR PLANTER WALL AND SCULPTURE BASE LOCATED IN
 THE OPEN SPACE SOUTH OF THE WHITNEY.
  
 OK SUBJECT TO REVIEW BY PLANNING AND ZONING DEPT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status F Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 13:48 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 13:48 Sent To  
Notes
2007-02-11 14:11:44BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 2/2/07 FOR DELTA DOOR
 MANUFACTURING'S SERIES DH-350 ALUMINUM IN-SWING DOOR.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 106.1.1THE TEST REPORT IS FOR AN IN-SWING
 DOOR, YET NOTES HAVE BEEN ADDED TO THE LOCATION PLANS
 STATING THAT THE PROPOSED REVISION IS TO CHANGE TO AN
 OUTSWING DOOR, PLEASE CLARIFY.NOTE: THE DOOR MUST BE
 IN-SWING.AN IN-SWING DOOR IS REQUIRED AT THIS
 LOCATION IN ORDER TO PROVIDE THE NECESSARY SAFE EGRESS
 FROM THE "LANDSCAPED COURT".
  
 2) FBC* 106.1ONLY TWO COPIES WERE SUBMITTED.THIS IS
 A THRESHOLD INSPECTOR PROJECT SO THREE COPIES OF ALL
 DOCUMENTS ARE REQUIRED.
  
 3) FLORIDA ADMINISTRATIVE CODE RULE 9B-72.THE
 PROPOSED DOOR DOES NOT APPEAR TO HAVE A STATEWIDE OR
 MIAMI-DADE PRODUCT APPROVAL SO LOCAL (WEST PALM BEACH)
 PRODUCT APPROVAL IS REQUIRED.PLEASE PROVIDE
 DOCUMENTATION TO SHOW THAT THIS PRODUCT IS COVERED BY A
 QUALITY ASSURANCE PROGRAM PROVIDED BY A FLORIDA STATE
 APPROVED QUALITY ASSURANCE ENTITY.FOR A LIST OF
 FLORIDA STATE APPROVED QUALITY ASSURANCE ENTITIES GO TO
 WWW.FLORIDABUILDING.ORG/PR/PR_ORG_SRCH.ASPX
  
 4) THIS WAS BROUGHT IN AS A SUBMITTAL (NO FEE) WHEN IT
 IS IN FACT A REVISION.A $60 REVISION FEE IS NOW DUE,
 AND AN ADDITIONAL $60 REVISION FEE WILL BE DUE WHEN THE
 REVISION IS BROUGHT BACK IN TO ADDRESS THE ABOVE
 COMMENTS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2006-10-24 Cont ID  
Sent By rbrown Date 2006-10-24 Time 08:22 Rev Time 0.00
Received By rbrown Date 2006-10-24 Time 08:22 Sent To  
Notes
2006-10-24 08:25:30SUBMITTAL ON 10/5/06 FOR 'SUPER THERM' SPRAY APPLIED
 INSULATIONPRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2006-10-01 Cont ID  
Sent By rbrown Date 2006-10-01 Time 18:25 Rev Time 0.00
Received By rbrown Date 2006-10-01 Time 18:25 Sent To  
Notes
2006-10-01 00:00:00SUBMITTAL ON 8/23/06 FOR WILKINSON
 HI-RISE TRASH CHUTE SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2006-08-06 Cont ID  
Sent By rbrown Date 2006-08-06 Time 16:34 Rev Time 0.00
Received By rbrown Date 2006-08-06 Time 16:34 Sent To  
Notes
2006-08-06 00:00:00REVISION RE-SUBMITTED ON 7/25/06 FOR
 ROLLING TECHNOLOGIES DOOR AND WINDOW
 DETAILS AND PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 21:25 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 21:25 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR ROOF SLAB, POUR 4 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 21:22 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 21:22 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR ROOF SLAB, POUR 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 21:19 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 21:19 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR ROOF SLAB, POURS 2 & 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 21:15 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 21:15 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 8TH FLOOR, POUR 4 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 21:11 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 21:11 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 8TH FLOOR, POURS 2 & 3
 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 21:08 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 21:08 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 8TH FLOOR, POUR 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 21:04 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 21:04 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 7TH FLOOR, POUR 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 20:59 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 20:59 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 7TH FLOOR, POUR 4 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 20:57 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 20:57 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 7TH FLOOR, POURS 2 & 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 20:54 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 20:54 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 6TH FLOOR, POURS 3 & 4
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 20:50 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 20:50 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 6TH FLOOR, POURS 1 & 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 20:30 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 20:30 Sent To  
Notes
2006-06-25 00:00:00ARCHITECTURAL REVISION FOR SHEETS A0-3,
 A0-4, A1-0, A1-2, A2-0, A2-1, A2-4, A2-5
 REDLINED 'SEPARATE PERMIT REQ'D FOR
 FUTURE TENANT OCCUPATION OF THE
 NORTH-WEST LOFT'.

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:36 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:36 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 5TH FLOOR, POURS 3 & 4
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:32 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:32 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 5TH FLOOR, POURS 1 & 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:28 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:28 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 4TH FLOOR, POUR 4 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:24 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:24 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 3RD FLOOR, POUR 5 AND 4TH
 FLOOR, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:20 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:20 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 4TH FLOOR, POUR 2 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:16 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:15 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 2ND FLOOR, POUR 5 AND 3RD
 FLOOR, POUR 4 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:12 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:12 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 3RD FLOOR, POUR 3 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:09 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:09 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 3RD FLOOR, POUR 2 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 19:05 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 19:05 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 3RD FLOOR, POUR 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 18:59 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 18:59 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 2ND FLOOR, POUR 4 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 18:58 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 18:58 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 2ND FLOOR, POUR 3 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 18:52 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 18:52 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 2ND FLOOR, POUR 2 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 18:48 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 18:48 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR MEZZANINE SLAB, POUR 4
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2006-06-25 Cont ID  
Sent By rbrown Date 2006-06-25 Time 18:46 Rev Time 0.00
Received By rbrown Date 2006-06-25 Time 18:46 Sent To  
Notes
2006-06-25 00:00:00SUBMITTAL FOR 2ND FLOOR, POUR 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2006-06-14 Cont ID  
Sent By rbrown Date 2006-06-14 Time 09:04 Rev Time 0.00
Received By rbrown Date 2006-06-14 Time 16:34 Sent To  
Notes
2006-06-14 00:00:00ARCHITECTURAL SUBMITTAL ON 4/17/06 FOR
 TRELLIS DOCUMENTATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2006-04-09 Cont ID  
Sent By rbrown Date 2006-04-09 Time 19:26 Rev Time 0.00
Received By rbrown Date 2006-04-09 Time 19:26 Sent To  
Notes
2006-04-09 00:00:00BUILDING PLAN REVIEW
 ******DENIED********
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 2/13/05 FOR ROLLING
 TECHNOLOGIES DOOR AND WINDOW DETAILS AND
 PRODUCT APPROVALS.
  
 1) ONLY TWO COPIES OF THE DOCUMENTS WERE
 SUBMITTED.THIS IS A THRESHOLD
 INSPECTOR PROJECT SO A THIRD COPY OF ALL
 DOCUMENTS IS REQUIRED.
  
 2) SINGLE HUNG WINDOW, LARGE MISSILE
 IMPACT RATED.THE SUBMITTED MIAMI WALL
 SYSTEMS, INC SERIES 122 ALUMINUM SINGLE
 HUNG WINDOW LMI PRODUCT APPROVAL NOA#
 04-1122.06 STATES A MAXIMUM UNIT FRAME
 HEIGHT OF 72".THIS MAXIMUM HEIGHT IS
 EXCEEDED IN THE COMPONENTS THAT MAKE UP
 WINDOWS REF. F1A LM, F1B LM, F1D LM,
 W1 LM, W3 LM AND SFC LM, ALL OF WHICH
 ARE SHOWN ON PLAN SHEET 32B OF 49 AS
 BEING BASED ON THIS PRODUCT APPROVAL.
 PROVIDE AN ALTERNATIVE PRODUCT APPROVAL
 AND AMEND THE WINDOW/DOOR SCHEDULE ON
 PLAN SHEET 32B.
  
 3) SINGLE HUNG WINDOW, SMALL MISSILE
 IMPACT RATED.THE SUBMITTED MIAMI WALL
 SYSTEMS, INC SERIES 122 ALUMINUM SINGLE
 HUNG WINDOW SMI PRODUCT APPROVAL NOA#
 04-1122.07 STATES A MAXIMUM UNIT FRAME
 HEIGHT OF 72".THIS MAXIMUM HEIGHT IS
 EXCEEDED IN THE COMPONENTS THAT MAKE UP
 WINDOWS REF. W1 SM, W3 SM, W8A SM AND
 SFD SM, ALL OF WHICH ARE SHOWN ON PLAN
 SHEET 32B OF 49 AS BEING BASED ON THIS
 PRODUCT APPROVAL.PROVIDE AN
 ALTERNATIVE PRODUCT APPROVAL AND AMEND
 THE WINDOW/DOOR SCHEDULE ON PLAN SHEET
 32B.
  
 4) SLIDING GLASS DOOR, LARGE MISSILE
 IMPACT RATED.THE SUBMITTED MIAMI WALL
 SYSTEMS, INC. SERIES 100 ALUMINUM
 SLIDING GLASS DOOR TEST REPORT FROM
 FENESTRATION TESTING LABORATORY,
 COVERING THE PROPOSED DOOR HEIGHTS, IS
 NOTED.SIGNED AND SEALED COPIES OF THIS
 REPORT ARE REQUIRED BECAUSE THE DOOR
 HEIGHTS PROPOSED FOR THIS PROJECT ARE
 OUTSIDE THE SCOPE OF PRODUCT APPROVAL
 NOA# 01-0123.02
  
 5) SLIDING GLASS DOOR, SMALL MISSILE
 IMPACT RATED.THE SUBMITTAL OF
 COMPARATIVE ANALYSIS IN SUPPORT OF THE
 SUBMITTED MIAMI WALL SYSTEMS, INC.
 SERIES 100 ALUMINUM SLIDING GLASS DOOR
 PRODUCT APPROVAL NOA# 01-1108.03, IS
 NOTED.THE HEIGHTS OF THE PROPOSED
 SLIDING GLASS DOORS EXCEED THE 104-3/4"
 MAXIMUM STATED IN THE PRODUCT APPROVAL.
 WHILE COMPARATIVE/RATIONAL ANALYSIS CAN
 BE USED TO JUSTIFY RESISTANCE TO WIND
 PRESSURES, THE MISSILE IMPACT RATING OF
 THE DOORS CAN ONLY BE SHOWN BY TESTING.
 RATIONAL ANALYSIS CANNOT BE USED TO
 JUSTIFY THE USE OF THE DOORS OUTSIDE THE
 SCOPE OF THE PRODUCT APPROVAL WHEN
 MISSILE IMPACT RATING IS REQUIRED.
 SUBMIT A MISSILE IMPACT TEST REPORT OR
 SUBMIT AN ALTERNATIVE PRODUCT APPROVAL
  
 6) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2005-10-20 Cont ID  
Sent By rbrown Date 2005-10-20 Time 22:21 Rev Time 0.00
Received By rbrown Date 2005-10-20 Time 17:43 Sent To  
Notes
2005-10-20 00:00:00ARCHITECTURAL SUBMITTAL ON 10/11/05 FOR
 GARAGE DOOR PRODUCT APPROVAL AND MANUF
 DATA SHEETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-10-20 Cont ID  
Sent By rbrown Date 2005-10-20 Time 21:49 Rev Time 0.00
Received By rbrown Date 2005-10-20 Time 21:49 Sent To  
Notes
2005-10-20 00:00:00ARCHITECTURAL/STRUCTURAL REVISION
 SUBMITTED 9/8/05 FOR SHEETS A0-3, A1-1,
 A2-3, A8-1, S-4, S-5, S-6, S-7, S-8 AND
 S-42

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-08-25 Cont ID  
Sent By rbrown Date 2005-08-25 Time 09:37 Rev Time 0.00
Received By rbrown Date 2005-08-25 Time 09:37 Sent To  
Notes
2005-08-25 00:00:00STRUCTURAL SUBMITTAL ON 8/23/05 FOR POUR
 3, MEZZANINE LEVEL (GRIDS 7-11/ A-H)
 SHORING INSPECTION LETTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-08-22 Cont ID  
Sent By rbrown Date 2005-08-22 Time 15:17 Rev Time 0.00
Received By rbrown Date 2005-08-22 Time 15:17 Sent To  
Notes
2005-08-22 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 RFI #136 AND #137-REPAIR PROCEDURE
 FOR FOOTING CBF-14
  
 --PROVISO--
 IF THE RESPONSE TO EITHER RFI RESULTS IN
 A CHANGE TO THE PERMIT APPROVED PLAN FOR
 FOOTING CBF-14, THE RELEVANT PLANS
 SHOULD BE REVISED AND SUBMITTED FOR
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-08-22 Cont ID  
Sent By rbrown Date 2005-08-22 Time 15:13 Rev Time 0.00
Received By rbrown Date 2005-08-22 Time 15:13 Sent To  
Notes
2005-08-22 00:00:00STRUCTURAL SUBMITTAL ON 8/22/05 FOR POUR
 2, MEZZANINE LEVEL (GRIDS 15-11/ A-H)
 SHORING INSPECTION LETTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-08-09 Cont ID  
Sent By rbrown Date 2005-08-09 Time 11:36 Rev Time 0.00
Received By rbrown Date 2005-08-09 Time 11:36 Sent To  
Notes
2005-08-09 00:00:00STRUCTURAL SUBMITTAL ON 7/15/05 FOR
 MEZZANINE TO ROOF LEVEL SHORING AND
 RE-SHORING SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-07-15 Cont ID  
Sent By rbrown Date 2005-07-15 Time 21:16 Rev Time 0.00
Received By rbrown Date 2005-07-15 Time 16:36 Sent To  
Notes
2005-07-15 00:00:00ARCHITECTURAL AND STRUCTURAL REVISION
 SUBMITTED 5/4/05 FOR GENERAL UPDATE OF
 PLANS.
  
 ONLY THE FOLLOWING SHEETS NEED TO BE
 REVISED AND RE-SUBMITTED.ALL OTHER
 SHEETS HAVE BEEN STAMPED AND ONE COPY
 RETAINED FOR RECORDS:
  
 1) FBC 704.1SHEET A0-3, GROUND LEVEL
 LIFE SAFETY PLAN.OCCUPANCY OF THE
 RELOCATED VALET STATION IS NOT LABELLED.
 THE LABEL 'VALET' SHOULD BE MOVED FROM
 THE OLD LOCATION TO THE NEW SO THAT
 OCCUPANCY SEPARATION CAN BE CONFIRMED
 UNNECESSARY.
  
 2) SHEET A0-3 AND A1-1THE NEW EGRESS
 DOOR ADJACENT THE RELOCATED VALET
 STATION SWINGS ACROSS THE CURB INTO THE
 PARKING GARAGE VEHICLE ACCESSWAY.THE
 DOOR COULD BE STRUCK BY AN EXITTING
 VEHICLE AND CAUSE PERSONAL INJURY TO
 PERSONS USING THE DOOR.AMEND THE PLAN.
  
 3) SHEET A8-1TO EXPEDITE PERMIT ISSUE,
 EACH COPY OF THIS SHEET IN THE PERMITTED
 SET OF PLANS INCLUDED A HANDRITTEN NOTE:
 "PRE-CAST MOULDINGS SHALL BE
 MECHANICALLY FASTENED TO STRUCTURE,
 MANUFACTURER TO SUBMIT SHOP DRAWINGS FOR
 APPROVAL"-SIGNED AND DATED BY STUART
 COHEN.THIS NOTE MUST BE ADDED TO THE
 REVISED SHEET A8-1 BEFORE IT IS PRINTED,
 SIGNED AND SEALED.
  
 4) SHEET A9-1TO EXPEDITE PERMIT ISSUE,
 INTERIOR ELEVATIONS 1 TO 6 ON EACH COPY
 OF THIS SHEET, IN THE PERMITTED SET OF
 PLANS, WERE REDLINED TO SHOW THE
 REQUIRED HEIGHTS FOR THE VANITY (2'-10"
 AFFL) AND THE W.C. (BETWEEN 17" AND 19"
 AFFL). THESE DIMENSIONS MUST BE ADDED TO
 THE REVISED SHEET A9-1 BEFORE IT IS
 PRINTED, SIGNED AND SEALED.
  
 5) SHEETS A4-0, A4-1 AND A4-2NORTH,
 EAST AND SOUTH ELEVATIONS.SUBMIT
 DETAILS TO SHOW THE LEVEL TRANSITION
 (STEPS/RAMPS), AT EACH ENTRY WAY, FROM
 THE SIDEWALK TO THE (NOW RAISED) GROUND
 FLOOR SLAB.IF NO TRANSITION IS
 REQUIRED, THEN THIS SHOULD BE JUSTIFIED
 BY AMENDING THE ELEVATIONS TO CLARIFY
 THE RELATIONSHIP BETWEEN SIDEWALK LEVEL
 PROFILE AND GROUND FLOOR SLAB LEVELS.
  
 6) THE PROVISOS ATTACHED TO THE
 PERMITTED SET OF PLANS HAVE NOT YET BEEN
 ADDRESSED.A COPY IS ATTACHED TO THESE
 NOTES.PLEASE ADDRESS THE PROVISOS OR
 PROVIDE A LETTER GIVING THE TIME-FRAME
 IN WHICH THEY WILL BE ADDRESSED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-19 Cont ID  
Sent By rbrown Date 2005-06-09 Time 15:27 Rev Time 0.00
Received By rbrown Date 2005-06-09 Time 15:25 Sent To  
Notes
2005-05-03 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 - PROVISO -
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
  
 - PROVISO -
 SINGLE HUNG WINDOWS OVER 110-3/16" TALL.
 WE ACKNOWLEDGE RECEIPT OF R.C.
 ALUMINUM'S APPLICATION FOR SITE SPECIFIC
 PRODUCT APPROVAL FOR 'ALUMINUM SINGLE
 HUNG WINDOW MULLED TOGETHER OVER FIXED
 WINDOW' FOR WINDOWS BETWEEN 110-3/16"
 AND 140" TALL.THE APPLCATION INCLUDES
 ONLY A COPY OF FENESTRATION TESTING
 LABORATORY, INC REPORT# 4020.IT CANNOT
 BE APPROVED WITHOUT ORIGINAL
 SIGNED/SEALED AND DATED REPORT PAGES.
 R.C. ALUMINUM ADVISED THAT THEY WILL NOT
 SUPPLY THIS UNTIL THEY HAVE A SIGNED
 CONTRACT TO SUPPLY.THIS MUST BE
 ADDRESSED BEFORE WINDOW BUCK INSPECTION.
 ALTERNATIVELY,SUBMIT STATEWIDE PRODUCT
 APPROVAL PAPERWORK IF OBTAINED BEFORE
 BUCK INSPECTION.THIS PROVISO APPLIES
 ONLY TO WINDOWS BETWEEN 110-3/16" AND
 140" TALL BECAUSE THE SUBMITTED
 STATEWIDE PRODUCT APPROVAL FL3398 (BASED
 ON MIAMI-DADE NOA# 03-1216.04) COVERS
 THIS WINDOW CONGURATION FOR WINDOWS UPTO
 110-3/16" TALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-11-09 Cont ID  
Sent By rbrown Date 2004-11-17 Time 16:37 Rev Time 0.00
Received By rbrown Date 2004-11-08 Time 16:37 Sent To Z
Notes
2004-11-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 SHEET S.0, FOUNDATION NOTE STILL REFERS
 TO GROUND IMPROVEMENT BY VIBROFLOTATION.
 AS 'SOIL MIXING' IS BEING USED INSTEAD,
 THE FOUNDATION NOTE ON THE PLAN SHALL BE
 REVISED TO REFLECT THAT.
  
 CONSTRUCTION OVER THE 'RIGHT OF WAY'.
 SUBMIT A RECORDED COPY OF THE AGREEMENT
 BETWEEN THE DEVELOPER AND THE CITY (CITY
 ATTORNEY'S OFFICE) ESTABLISHING
 TEMPORARY SHARED OWNERSHIP OF 'THE
 ALLEY' FOR THE LIFE OF THE BUILDING. IT
 IS UNDERSTOOD THAT THE AGREEMENT IS
 VALID ONLY FOR THE LIFE OF THIS
 BUILDING.
  
 INFORMATIVE
 -713.13 F.S.A NOTICE OF
 COMMENCEMENT SHALL BE RECORDED AT PALM
 BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A
 PERMIT CAN BE ISSUED. BLANK FORMS ARE
 AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BE RE-RECORDED IF THE DESCRIBED
 IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 INFORMATIVE
 -IMPACT FEES. THE PLANS SHALL BE
 TAKEN TO PALM BEACH COUNTY BUILDING
 DEPARTMENT FOR IMPACT FEE ASSESSMENT.
 THEY SHALL BE STAMPED AT THAT OFFICE
 AND A COPY OF THE PAID RECEIPT SUBMITTED
 TO THE CITY OF WEST PALM BEACH DEPT OF
 CONSTRUCTION SERVICES BEFORE A PERMIT
 CAN BE ISSUED.
  
 INFORMATIVE
 -CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL,
 AND THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION
 OF PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE.
  
 PROVISO
 -SHEET A3-1 SHALL BE AMENDED TO OMIT
 THE VISION PANELS FROM DOORS 100 & 102
 (AS PER DOORS 3 & 4), OR SUBMIT A
 PRODUCT APPROVAL FOR COMMERCIAL DOOR
 WITH VISION PANEL.
  
 PROVISO
 -THE SUBMITTED GAF MATERIALS CORP
 ROOF PRODUCT APPROVAL NOA# 03-0501.03
 IS FOR 'MODIFIED BITUMEN' BUT PLAN SHEET
 A1-15 SPECIFIES '4-PLY BUILT UP' ROOF.
 AMEND THE PLAN OR SUBMIT A PRODUCT
 APPROVAL FOR BUILT-UP ROOFING.
  
 PROVISO
 -THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
  
 FEE NOTE:
 -FEE FOR SECOND RESUBMITTAL ($34750)
 IS WAIVED PER NEIL MELICK'S MEETING
 WITH OSCAR BEHNCKE AND VERBAL
 INSTRUCTION TO ROBERT BROWN AND LUIS
 MARTINEZ.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-06-09 Cont ID  
Sent By rbrown Date 2004-08-27 Time 18:08 Rev Time 0.00
Received By rbrown Date 2004-08-23 Time 08:08 Sent To  
Notes
2004-08-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 8/3/04:
  
 2) COMMENT RESPONSE NOTED.
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3) COMMENT RESPONSE NOTED.
 IMPACT FEES. THE PLANS SHALL BE TAKEN TO
 PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 7) IN ORDER TO CONSTRUCT OVER THE 'RIGHT
 OF WAY' IT WILL BE NECESSARY TO HAVE THE
 CITY OF WEST PALM BEACH COMMISSION 'DEED
 OVER', TO THE DEVELOPER, THAT PART OF
 THE ALLEY THAT IS UNDER THE BUILDING
 WHILE MAINTAINING ACCESS AND UTILITIES
 EASEMENTS.NEIL MELICK (BUILDING
 OFFICIAL) HAS BEEN CONSULTED AND HAS
 RULED THAT, UNLESS THE ABOVE PROCEDURE
 IS FOLLOWED, THE CONSTRUCTION OF
 HABITABLE SPACE OVER THE ALLEY WOULD
 CONSTITUTE CONSTRUCTION OUTSIDE OF THE
 PROPERTY LINE. THIS WOULD BE A VIOLATION
 OF FBC TABLE 600 WHICH STATES THAT, FOR
 ALL TYPES OF CONSTRUCTION, NO OPENINGS
 ARE PERMITTED AT THE PROPERTY LINE.
  
 8) FBC* 105.13.1SPECIAL INSPECTOR. THE
 THRESHOLD INSPECTOR AGREEMENT APPEARS
 TO HAVE BEEN PULLED APART, BEFORE
 SUBMITTAL, AND IS NOW MISSING THE SHEETS
 FOR THE OWNER'S, ENGINEER'S AND
 CONTRACTOR'S SIGNATURES.PLEASE
 ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL: 561 805 6711),
 A MEETING INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR
 AND ENGINEER.
  
 43) THE FOLLOWING COMMENTS PERTAIN TO
 THE SUBMITED PRODUCT APPROVALS:
 (A) THE SUBMITTED R.C. ALUMINUM
 SINGLE HUNG WINDOW PRODUCT APPROVAL NOA#
 03-1216.04 SHOWS, ON DRG SHEET 2, A 72"
 (6'-0") MAXIMUM HEIGHT FOR SINGLE HUNG
 WINDOWS.THIS IS LESS THAN THE 7'-0"
 REQUIRED ON SHEET A3-2 (AT 2ND AND 3RD
 FLOORS) FOR THIS PROJECT.ALSO, DRAWING
 SHEET 3 OF THE PRODUCT APPROVAL SHOWS A
 MAXIMUM HEIGHT OF 9'-2" FOR 'SINGLE
 HUNG-ABOVE-FIXED' WINDOWS.THIS IS LESS
 THAN THE 10'-0" REQUIRED ON SHEET A3-3
 (AT 3RD FLOOR) FOR THIS PROJECT.AMEND
 THE PLANS OR SUBMIT AN ALTERNATIVE
 PRODUCT APPROVAL.
 (C) ON SHEET A1-0, DOORS 3 & 4 AND,
 SHEETS A-14 AND A1-15, DOORS 100 & 102
 ARE COMMERCIAL INSWING DOORS WITH
 10"X 10" VISION PANELS (TYPE E ON SHEET
 A3-1).THE SUBMITTED FLEMING COMMERCIAL
 STEEL DOOR PRODUCT APPROVAL NOA#
 02-0523.07 IS FOR A DOOR WITH NO VISION
 PANEL.AMEND THE PLAN OR SUBMIT AN
 ALTERNATIVE PRODUCT APPROVAL.
 (D) SHEET A1-0, TRANSFORMER VAULT
 DOOR 11.THE REQUIRED DESIGN WIND
 PRESSURE FOR THIS DOOR IS +/- 60 PSF
 (FROM SHEET A-10.5) WHICH EXCEEDS THE
 +/-50 PSF MAXIMUM ALLOWABLE DESIGN
 PRESSURE GIVEN ON THE SUBMITTED CURRIES
 LOUVERED OUTSWING DOOR PRODUCT APPROVAL
 NOA# 03-0319.04.SUBMIT AN ALTERNATIVE
 PRODUCT APPROVAL.
 (F) THE SUBMITTED R.C. ALUMINUM
 WINDOW WALL SYSTEM PRODUCT APPROVAL NOA#
 03-1224.03 SHOWS, ON DRAWING SHEET 2, A
 10'-0" MAXIMUM D.L. OPENING HEIGHT.
 THIS IS LESS THAN THE 12' HEIGHT (STF-A)
 REQUIRED ON SHEET A3-3 FOR THIS PROJECT.
 AMEND THE PLANS OR SUBMIT AN ALTERNATIVE
 PRODUCT APPROVAL.
 (G) SUBMIT PRODUCT APPROVALS FOR THE
 STOREFRONT DOORS.
 (H) FOR EACH SUBMITTED PRODUCT
 APPROVAL THAT DOES NOT HAVE A STATEWIDE
 PRODUCT APPROVAL LISTING, THE
 MANUFACTURER SHALL COMPLETE AN
 APPLICATION FORM FOR LOCAL PRODUCT
 APPROVAL (AVAILABLE FROM THIS OFFICE OR
 FROM WWW.FLORIDABUILDING.ORG/PR/PR_
 OVERVIEW.ASP).THIS APPLIES TO NOA#'S
 01-0829.05, 02-1216.02, 02-1216.03,
 02-0222.03, 02-0222.04, 03-1023.02,
 04-0512.02.
 (I) THE PRODUCT APPROVAL SHEETS SHALL
 BE MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.THIS APPLIES TO ALL
 SUBMITTED PRODUCT APPROVALS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-03 Cont ID  
Sent By rbrown Date 2004-08-03 Time 20:18 Rev Time 0.00
Received By rbrown Date 2004-07-30 Time 16:28 Sent To  
Notes
2004-07-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/6/04:
  
 2) COMMENT RESPONSE OF 6/15/04 IS NOTED.
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3) COMMENT RESPONSE OF 6/15/04 IS NOTED.
 IMPACT FEES. THE PLANS SHALL BE TAKEN TO
 PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 4) COMMENT RESPONSE OF 6/15/04 IS NOTED.
 CONDOMINIUM V APARTMENTS.THE PLANS
 MAKE REFERENCE TO CONDOMINIUM.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 7) COMMENT RESPONSE OF 6/15/04 IS NOTED.
 SUBMIT A RECORDED COPY OF THE AERIAL
 RIGHTS FOR CONSTRUCTION OVER THE RIGHT
 OF WAY.THE AERIAL RIGHTS SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE.
  
 8) FBC* 105.13.1SPECIAL INSPECTOR. THE
 SUBMITTED THRESHOLD INSPECTOR AGREEMENT
 IS MISSING THE ENGINEER'S SIGNATURE/SEAL
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, THRESHOLD INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
 MR PISKURA HAS BEEN GIVEN A COPY OF THE
 SUBMITTED THRESHOLD INSPECTION
 AGREEMENT FOR HIS RECORDS.
  
 10) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.THE 8,000 PSF ALLOWABLE BEARING
 PRESSURE STATED IN THE SUBMITTED
 ARDAMAN & ASSOCIATES REPORT (DATED
 9/18/03) IS EXCEEDED BY THE PROPOSED
 10,000 PSF ALLOWABLE BEARING PRESSURE
 STATED ON SHEET S-0, UNDER'FOUNDATIONS',
 WHICH REFERS TO AN ARDAMAN & ASSOCIATES
 REPORT DATED 10/13/03.EITHER PROVIDE
 THREE COPIES OF THAT REPORT OR AMEND THE
 BEARING CAPACITY ON SHEET S-0 AND AMEND
 THE FOUNDATION DESIGN ACCORDINGLY.
  
 15) 705.1.1.2SOUTH WALL FACING ALLEY.
 EVERY OPENING WITHIN 15 FT OF THE
 PROPERTY LINE SHALL BE EQUIPPED WITH
 OPENING PROTECTIVES.OPENINGS IN
 RECESSED WALLS THAT HAVE A SLAB ABOVE
 (I.E. NOT OPEN TO THE SKY) ARE TREATED
 AS THOUGH THE OPENING OCCURRED AT THE
 EDGE OF THAT SLAB.THEREFORE THE
 FOLLOWING OPENINGS REQUIRE OPENING
 PROTECTIVES:
 (A) SHEET A1-1, PARKING GARAGE VEHICLE
 EXIT OPENING.
 (B) SHEET M2.01, FIRE PUMP AND DOMESTIC
 PUMP ROOMS.
 (C) SHEET M2.03, 'GARAGE OPENINGS'.
 (D) SHEET A1-1, TEL/TV ROOM LOUVERS.
 (E) SHEET M2.05, 'GARAGE OPENINGS'.
  
 18) FBC 1606.2.5SHEET A1-6, 3RD FLOOR
 PLAN.THE DOOR FROM THE LANDSCAPE
 COURT TO THE SITTING AREA IS STILL
 MARKED #57 WHICH IS CALLED UP AS
 ELECTRICAL ROOM DOOR ON THE DOOR
 SCHEDULE (SHEET A3-1).AGAIN, SHOULD
 THIS DOOR BE MARKED #51?
  
 26) FBC 704.1.1 AND FBC 705.1.2.1
 SHEET A1-2 AND A1-3, MEZZANINE PLAN.
 DOORS #32 TO THE A/C ROOMS SHOULD BE
 MIN. 3/4 HOUR FIRE-RATED TO PROVIDE
 SEPARATION FROM THE PARKING GARAGE.
 AMEND THE DOOR SCHEDULE, SHEET A3-1.
  
 31) FBC 1004.1.3SHEET A1-6, 3RD FLOOR
 EGRESS FROM THE LANDSCAPED COURT THROUGH
 THE SITTING AREA.THE COMMON PATH OF
 TRAVEL EXTENDS TO THE EXIT ACCESS
 CORRIDOR AND EXCEEDS 75 FT.PROVIDE TWO
 EXIT ACCESS DOORS, MIN. 20 FT O.C., FROM
 THE SITTING AREA THROUGH THE CORRIDOR
 WALL SUCH THAT TWO SEPARATE AND DISTINCT
 PATHS OF TRAVEL ARE AVAILABLE.
  
 34) FBC 411.2.6 SHEET A1-7.PARKING
 GARAGE DOORS #58 SHALL BE MIN. 3/4 HOUR
 FIRE-RATED.AMEND THE DOOR SCHEDULE,
 SHEET A3-1.
  
 43) THE FOLLOWING COMMENTS PERTAIN TO
 THE SUBMITTED PRODUCT APPROVALS:
 (A) THE SUBMITTED PRODUCT APPROVALS
 FOR THE SINGLE HUNG WINDOWS AND SLIDING
 GLASS DOORS ARE MIAMI-DADE NOTICES OF
 ACCEPTANCES FOR MIAMI WALL SYSTEMS, INC
 A SEARCH AT THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 SHOWS NO MATCHING STATEWIDE PRODUCT
 APPROVAL.SPECIFY ALTERNATIVES THAT
 HAVE STATEWIDE OR LOCAL PRODUCT
 APPROVAL.
 (B) THE SUBMITTED FLEMING DOOR OUTSWING
 COMMERCIAL STEEL DOOR PRODUCT APPROVAL
 NOA INCLUDES DRAWING SHEETS 1 THRU 10
 WHICH DO NOT CARRY THE MIAMI-DADE CODE
 COMPLIANCE STAMP.SUBMIT THREE COPIES
 IF DRAWING SHEETS 1 THROUGH 10 THAT
 INCLUDE THE COMPLIANCE STAMPS.
 (C) SHEETS A1-14 AND A1-15 SHOW DOORS
 ON STAIRS 1, 2 AND 3 AND ON THE TWO
 ELEVATOR LOBBIES WHICH ARE INSWING.
 THE SUBMITTED PRODUCT APPROVAL IS FOR
 OUTSWING DOORS.SUBMIT A PRODUCT
 APPROVAL FOR INSWING HOLLOW METAL DOORS
 (D) SHEET A3-1, DOOR SCHEDULE.SUBMIT
 PRODUCT APPROVALS FOR DOOR TYPES A, B,
 C AND F WHICH ARE ALL USED AS EXTERIOR
 DOORS.
 (E) SUBMIT PRODUCT APPROVALS FOR THE
 STOREFRONT WINDOWS AND DOORS.
 NOTE: THE PRODUCT APPROVAL SHEETS SHALL
 BE MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 44) PRODUCT APPROVAL.RULE 9B-72 FAC.
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHOUT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 47) 481.221(1)(A) F.S.ARCHITECT'S
 SIGNATURE ON PLANS.A RUBBER STAMP OF
 STUART COHEN'S SIGNATURE HAS BEEN USED
 ON A NUMBER OF THE SUBMITTED PLANS
 (INCLUDING, BUT NOT LIMITED TO, SHEETS
 A0-1, A0-2, A0-4, A0-11, A1-14, A1-15).
 AN ORIGINAL SIGNATURE IS REQUIRED ON
 EACH PLAN SHEET.
  
 48) FBC 104.2.1.2SHEET A8-1, PRE-CAST
 CONCRETE MOLDINGS.PROVIDE FASTENING
 DETAILS FOR ATTACHMENT OF THE
 ARCHITECTURAL MOLDINGS.
  
 49) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-06 Cont ID  
Sent By rbrown Date 2004-05-06 Time 17:52 Rev Time 0.00
Received By rbrown Date 2004-03-30 Time 10:57 Sent To  
Notes
2004-03-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 4) CONDOMINIUM V APARTMENTS.THE PLANS
 MAKE REFERENCE TO CONDOMINIUM.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 5) FBC* 104.2.4SITE SURVEY.THE
 SUBMITTED SURVEY DRAWING HAS NOT BEEN
 SIGNED AND SEALED BY A LICENSED SURVEYOR
 AND MAPPER.THE SURVEY DRAWING DOES
 INCLUDE THE 'SURVEYORS CERTIFICATE',
 PRINTED NAME AND PRINTED LICENSE
 NUMBER OF BOTH PAUL J. STOWELL AND
 CLYDE MCNEAL.THE DRAWING SHALL BEEN
 SIGNED AND SEALED BY ONE OF THESE
 SURVEYORS.
 (REF: 472.025(1) FL. STATUTES)
  
 6) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 NOTE: THE UNITY OF TITLE SHALL INCLUDE
 LOT 7, BLOCK 19, SOUTH OF THE ALLEY,
 WHICH IS SHOWN ON THE PLANS AS PART-
 APARTMENT UNIT AND PART-PARK AREA.
  
 7) SUBMIT A RECORDED COPY OF THE AERIAL
 RIGHTS FOR CONSTRUCTION OVER THE RIGHT
 OF WAY.THE AERIAL RIGHTS SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE.
  
 8) FBC* 105.13.1SPECIAL INSPECTOR.IT
 IS NOTED THAT THE STRUCTURAL INSPECTION
 PLAN IS PROVIDED ON SHEET S-0.SUBMIT
 A SIGNED THRESHOLD INSPECTOR AGREEMENT.
 FOR FURTHER DETAILS, CONTACT HAROLD
 PISKURA (THRESHOLD INSPECTION PROGRAM
 CO-ORDINATOR) ON 561-805 6711.
  
 9) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.IT IS NOTED THAT SHEET S-0 REFERS
 TO ARDAMAN & ASSOCIATES REPORT 03-2186
 (9/18/2003).SUBMIT THE GEOTECHNICAL
 REPORT.
  
 10) FBC* 104.4.5 SPECIAL FOUNDATION
 PERMIT. THE BUILDING OFFICIAL MAY, AT
 HIS DISCRETION, ISSUE A SPECIAL PERMIT
 FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST BY THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH SPECIAL PERMIT IS PROCEED
 ING AT HIS/HER OWN RISK AND WITHOUT
 ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE
 REQUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODES.
  
 11) A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE SWIMMING POOL.
  
 12) FBC 104.2.1.2SHEET A0-2, BUILDING
 DATA.THE BUILDING AREAS, ARRANGED BY
 STORY AND OCCUPANCY, SHALL BE STATED ON
 THE PLANS.
  
 13) FBC TABLE 600SHEET A0-2, FIRE
 RESISTANCE RATINGS.THE PLANS SHALL
 STATE THE REQUIRED FIRE RESISTANCE
 RATINGS FOR THE WALLS, COLUMNS, BEAMS,
 FLOOR/CEILING ASSEMBLIES AND ROOF FOR A
 TYPE I BUILDING.
  
 14) INFORMATIVE:
 FBC 104.2.1.2THE ARCHITECTURAL PLANS
 DO NOT INCLUDE A GENERAL NOTES/
 SPECIFICATION SHEET.
  
 15) FBC 705.1.1.2SHEET A-10.3, SOUTH
 ELEVATION OPENINGS.ALL OPENINGS IN
 WALLS LOCATED WITHIN 15 FEET OF THE
 PROPERTY LINE SHALL BE EQUIPPED WITH
 OPENING PROTECTIVES CONFORMING TO
 FBC 705.1.EXCEPTION (3) WILL NOT APPLY
 TO THE PARKING GARAGE LOUVERS BECAUSE IT
 IS NOT AN 'OPEN' PARKING STRUCTURE.
  
 16) FBC 1001.1.3SHEET A0-4MEZZANINE
 PARKING LIFE SAFETY PLAN.ACCESS FROM
 THE PARKING GARAGE TO STAIR #3 AND
 ELEVATORS #3 AND #4 IS SHOWN THROUGH A
 PARKING SPACE WHICH HAS NOT BEEN
 'PAINTED OUT'.AMEND THE PLAN TO SHOW
 AN UNOBSTRUCTED PATH BY 'PAINTING OUT'
 THE RELEVANT PARKING SPACE ON SHEETS
 A0-4 AND A1-3.
  
 17) FBC 1004.1.4SHEET A0-5.THE TWO
 EXITS FROM THE PARKING GARAGE, AT THIS
 LEVEL, ARE SPACED APPROXIMATELY 80 FEET
 APART.THIS IS LESS THAN THE REQUIRED
 DISTANCE OF ONE-THIRD THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THAT AREA, FOR A SPRINKLERED BUILDING.
 AMEND THE PLAN.
  
 18) FBC 1012.1.2SHEET A0-6, THIRD
 FLOOR LIFE SAFETY PLAN.THE DOOR FROM
 THE LANDSCAPE COURT INTO THE SITTING
 AREA SHALL SWING IN THE DIRECTION OF
 EGRESS AS THE LANDSCAPE COURT AREA CAN
 ACCOMMODATE AN OCCUPANT LOAD IN EXCESS
 OF 50 PEOPLE.REVERSE THE SWING OF THE
 DOOR.SHOULD THIS DOOR BE MARKED #51 ON
 SHEET A1-6?
  
 19) FBC 1012.1.2SHEET A0-7, FOURTH
 FLOOR LIFE SAFETY PLAN.THE DOOR FROM
 PAVED DECK AND LAWN AREAS INTO THE
 CORRIDOR SHALL SWING IN THE DIRECTION OF
 EGRESS AS THE DECK AND LAWN AREA CAN
 ACCOMMODATE AN OCCUPANT LOAD IN EXCESS
 OF 50 PEOPLE.REVERSE THE SWING OF THE
 DOOR.SHOULD THIS DOOR BE MARKED #74 ON
 SHEET A1-9?
  
 20) FBC 1012.1.4SHEET A0-10, ROOF
 LEVEL LIFE SAFETY PLAN.THE RESTROOM
 DOOR SWING LEAVES LESS THAN HALF OF THE
 REQUIRED PASSAGEWAY WIDTH UNOBSTRUCTED.
 AMEND THE PLAN.
  
 21) FBC 412.6SHEETS A0-3 TO A0-10,
 LIFE SAFETY PLANS.'FIRE PROTECTION
 COMPONENTS NOTE #13' IS NOT RELEVANT TO
 THIS PROJECT AND MAY CAUSE SOME
 CONFUSION.
  
 22) FBC 11-4.8.5(2)SHEET A1-0, GROUND
 FLOOR PLAN.THE RAMP ADJACENT TO
 STAIR #1 SHALL BE AT LEAST 7'-11" LONG
 TO ACHIEVE THE REQUIRED LEVEL CHANGE
 WITH A SLOPE OF 1 IN 12. THE TOP LANDING
 IS SHOWN AT THE REQUIRED MINIMUM OF FIVE
 FEET FROM THE DOOR/WALL BUT THE RAMP IS
 DRAWN TOO SHORT.AMEND THE PLAN TO
 ENSURE THAT THERE WILL NOT BE A CONFLICT
 BETWEEN THE REQUIRED 18" MIN. RAMP
 HANDRAIL EXTENSION AND THE EXIT
 DISCHARGE FROM STAIR #1.
  
 23) FBC 11-4.8.5(2)SHEET A1-0, GROUND
 FLOOR PLAN.EACH OF THE DWELLING UNITS
 (NOT THE MEZZANINE LEVEL OF THE TWO-
 STORY UNITS) IS REQUIRED TO COMPLY WITH
 FAIR HOUSING.DUE TO THE STAIRWAY SHOWN
 IN THE CORRIDOR BETWEEN LOFT 5 AND
 ELEVATOR #1, LOFTS 3, 5 AND 7 DO NOT
 HAVE ACCESS TO THE ELEVATORS, AND THE
 FACILITIES ON THE UPPER FLOORS, WITHOUT
 FIRST LEAVING THE BUILDING.AMEND THE
 CORRIDOR AND ELEVATOR LOBBY LEVELS AS
 NECESSARY TO ALLOW A RAMP, WITH FOUR
 FOOT TOP LANDING AND 18" HANDRAIL
 EXTENSION (AS REQUIRED BY FBC 11-4.8.5),
 INSTEAD OF STAIRS.
  
 24) FBC 11-4.8.5SHEET A1-1, GROUND
 FLOOR PLAN.THE CORRIDOR RAMP BETWEEN
 GRIDS 15 AND 16 HAS A RISE OF MORE THAN
 6", SO HANDRAILS ARE REQUIRED IN EACH
 SIDE.HANDRAILS ARE ALSO REQUIRED BOTH
 SIDES OF EACH OF THE GROUND FLOOR RAMPS
 THAT ARE LONGER THAN 72".AMEND THE
 PLANS.
  
 25) FBC 11-4.8.5SHEET A1-1, GROUND
 FLOOR PLAN.THE RAMP BETWEEN LOFT-5 AND
 ELEVATOR #4 REQUIRES A FOUR FOOT LONG
 LANDING BETWEEN THE RAMP AND THE 'PUSH
 SIDE' OF THE ELEVATOR LOBBY DOOR.
  
 26) FBC 412.6.2SHEETS A1-2 AND A1-3,
 MEZZANINE PLAN.THE A/C ROOMS SHALL NOT
 OPEN INTO THE ELEVATOR LOBBIES.AMEND
 THE PLANS.
  
 27) FBC 1012.1.4SHEET A1-7, 3RD FLOOR
 PLAN.THE SWING OF DOOR #40 FROM THE
 PARKING GARAGE TO THE CORRIDOR, ADJACENT
 TO ELEVATOR #3, LEAVES LESS THAN HALF OF
 THE REQUIRED CORRIDOR WIDTH UNOBSTRUCTED
 AMEND THE PLANS TO RECESS THE DOORWAY.
  
 28) FBC 1508ROOF COVERINGS.
 SHEETS A1-14 AND A1-15 DO NOT GIVE ANY
 DESCRIPTION OR SPECIFICATION FOR THE
 ROOF COVERINGS AT THIS LEVEL.
  
 29) FBC 3003.4.1STRETCHER ACCESSIBLE
 ELEVATOR.IT IS NOTED THAT SHEET A7-2
 SHOWS THE ELEVATOR SIZES AND SHEET A9-0
 STATES THAT ELEVATOR #1 ACCOMMODATES AN
 AMBULANCE STRETCHER 76" LONG X 24" WIDE
 IN THE HORIZONTAL POSITION.THIS
 ELEVATOR SHALL BE IDENTIFIED BY SIGNAGE.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 30) FBC 411.2.6SHEET A3-1, DOOR SCHED.
 2ND FLOOR DOOR #40 SHALL BE 3/4-HOUR
 FIRE-RATED.AMEND THE PLAN.
  
 31) FBC 704.2.4SHEET A1-6, 3RD FLOOR
 SITTING AREA.THIS ROOM SHALL BE
 SEPARATED FROM THE EXIT ACCESS CORRIDOR
 BY 1/2-HOUR FIRE-RATED WALLS AND A
 20 MINUTE FIRE-RATED DOOR.THE DOOR
 SHALL SWING IN THE DIRECTION OF EGRESS
 BUT ITS SWING SHALL NOT OBSTRUCT MORE
 THAN HALF OF THE REQUIRED CORRIDOR
 WIDTH.
  
 32) FBC 704.2.4SHEETS A1-6 TO A1-13,
 3RD FLOOR TO 8TH FLOOR PLANS.WHAT
 APPEARS TO BE A MECHANICAL ROOM (NOT
 LABELLED) AT THE CORRIDOR INTERSECTION
 OPPOSITE THE ELECTRICAL AND TENANT
 STORAGE ROOMS DOES NOT HAVE A DOOR
 REFERENCE.NO APPROPRIATE REFERENCE CAN
 BE FOUND ON THE DOOR SCHEDULE
 (SHEET A3-1).A MINIMUM OF 20 MINUTE
 FIRE-RATED DOOR IS REQUIRED AT THESE
 LOCATIONS.AMEND THE PLANS/SCHEDULE.
  
 33) FBC 705.1.2SHEETS A0-3 TO A0-9 DO
 NOT SPECIFY THE REQUIRED TWO-HOUR FIRE-
 RATING FOR THE SHAFTS, INCLUDING THOSE
 ADJACENT TO ELEVATOR #1 AND ELEVATOR #4
 AND THOSE WITHIN THE MECHANICAL ROOM
 REFERENCED IN COMMENT #32 ABOVE.AMEND
 THE PLANS.
  
 34) FBC 411.2.6, 705.2.4 AND 1005.6.2
 SHEET A3-1, DOOR SCHEDULE, SHOWS DOOR
 #36 TO #74 AS REFERENCES FOR DOORS ON
 2ND TO 4TH FLOORS, BUT SHEETS A1-4 TO
 A1-9 (2ND TO 4TH FLOOR PLANS) SHOW DOORS
 AS #80 TO #86.AMEND THE PLANS SO THAT
 THE REQUIRED FIRE-RATING OF THE DOORS
 CAN BE DETERMINED/VERIFIED.
  
 35) FBC* F102.2.7SHEETS A4-2 AND A1-6,
 TRELLIS STRUCTURE.ARCHITECTURAL TRIM,
 ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 36) FBC* F102.2.8SHEETS A4-0 TO A4-3 &
 SHEETS A5-0 TO A5-2. PERMANENT CANOPIES/
 AWNINGS AND THEIR SUPPORTS, ON BUILDINGS
 LOCATED IN THE FIRE DISTRICT, SHALL BE
 OF NON-COMBUSTIBLE MATERIAL, FIRE
 RETARDANT TREATED WOOD, WOOD OF TYPE III
 SIZES OR OF 1-HOUR RESISTANT
 CONSTRUCTION.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 37) FBC 1608.2.2GUARDRAIL STRENGTH. IT
 IS NOTED THAT SHTS A7-0,A7-1,A7-6 & A8-3
 STATE THE HANDRAIL STRENGTH REQIREMENTS.
 ALSO, THE GUARDRAILS SHALL BE DESIGNED
 AND CONSTRUCTED FOR A CONCENTRATED LOAD
 OF 200 LB APPLIED IN ANY DIRECTION AT
 THE TOP OF THE GUARDRAIL, A CONCENTRATED
 HORIZONTAL LOAD OF 200 LB APPLIED ON A
 1 SQ FT AREA AT ANY POINT, AND A LINE
 LOAD OF 50 PLF APPLIED HORIZONTALLY AT
 THE REQUIRED GUARDRAIL HEIGHT WITH A
 SIMULTANEOUS LINE LOAD OF 100 PLF
 APPLIED VERTICALLY DOWNWARD ON THE TOP
 OF THE GUARDRAIL.THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY (UNLESS NOTED
 ABOVE) BUT SHALL BE APPLIED INDIVIDUALLY
 TO PRODUCE MAXIMUM STRESS IN EACH OF THE
 COMPONENTS OR SUPPORTS.AMEND/ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 38) FBC 1606.1.7WIND LOAD. IT IS NOTED
 THAT SHEET S-0 STATES BASIC WIND SPEED,
 WIND IMPORTANCE FACTOR AND WIND EXPOSURE
 CATEGORY.THE PLAN SHALL ALSO STATE THE
 INTERNAL PRESSURE COEFFICIENT (0.18) AND
 THE COMPONENT AND CLADDING DESIGN WIND
 PRESSURES INCL ROOF.AMEND THE PLANS.
 ALSO, SUBMIT THE REFERENCE RWDI WIND
 TUNNEL TEST REPORT.
  
 39) SHEETS S-33 AND S-34POOL DECK AND
 ROOF REINFORCING PLANS.THESE PLANS ARE
 NOT COMPLETE.
  
 40) FBC 903.7.6SHEETS FP2.03 & FP2.04,
 MEZZANINE SPRINKLER PLANS DO NOT SHOW
 SPRINKLER COVERAGE IN EITHER OF THE
 ELEVATOR LOBBIES.
  
 41) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 42) FBC 1005.6.9.9SHEET M6.01, STAIR
 PRESSURIZATION RISER.THE NOTE BELOW
 EACH (#1, #2 AND #3) STAIR RISER DIAGRAM
 SPECIFIES A MINIMUM PRESSURE
 DIFFERENTIAL OF 0.5" W.G.THIS SHOULD
 READ 0.05" W.G. AS IT EXCEEDS THE
 MAXIMUM ALLOWABLE POSITIVE PRESSURE.
 AMEND THE NOTE.
  
 43) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, STOREFRONT, EXTERIOR DOORS,
 SLIDING GLASS DOORS AND ROOF COVERINGS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 44) PRODUCT APPROVAL.RULE 9B-72 FAC.
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHOUT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 45) SHEET A3-2. IT IS NOTED THAT THE
 SLIDING GLASS DOOR AND SINGLE HUNG
 WINDOW DETAILS SPECIFY FRAME ATTACHMENT.
 NOTE THAT THE FRAME ATTACHMENT SHALL BE
 AS PER THE RELEVANT PRODUCT APPROVAL, OR
 BETTER.
  
 46) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2007-11-29 Cont ID  
Sent By dpalmer Date 2007-11-29 Time 15:15 Rev Time 0.00
Received By dpalmer Date 2007-11-29 Time 15:13 Sent To  
Notes
2007-11-29 15:16:00REV E3.06

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2007-11-07 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 08:58 Sent To  
Notes
2007-11-29 15:21:42NOTE ADDED 11/29/07
 LV SECURITY ALREADY SIGNED OFF AND PERMIT CLOSED.FOR
 FIRE REVIEW FOR DELETION OF MAGLOCKS.
2007-11-07 08:59:08** DENIEDREVISION **
  
 1) NOTE: PLEASE KNOW THE LOW VOLTAGE SECURITY PLANS AS
 SUBMITTED ARE REQUIRED TO BE UNDER SEPARATE PERMIT,
 PLANS AND FEES. THESE ARE NOT INCLUDED AS PART OF THE
 BASE BUILDING.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 16:08 Sent To PC
Notes
2007-08-23 16:09:15ELEC REV #12 ONLY FOR SHEET E2.01.

Review Stop E ELECTRICAL
Rev No 17 Status F Date 2007-08-01 Cont ID  
Sent By dpalmer Date 2007-08-01 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2007-08-01 Time 16:48 Sent To  
Notes
2007-08-01 17:13:55** UNSAT **
  
  
 1) NOTE: PLEASE SEE THE REVISED LANDSCAPE PLANS WHICH
 CONTAIN A SEAL WHICH IS NO LONGER VALID PER
 FAC61G1-16.002.
 PLEASE SEE THE ABOVE SECTION FOR THE MINIMUM REQUIRED
 SEAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE.
  
 2) NOTE: PLEASE SEE THE BUS-DUCT CURBING DETAIL DOES
 NOT MEET THE MINIMUM REQUIRED CONSTRUCTION REQUIREMENTS
 OF THE NEC.368.10C2B (2005), 368.6(2002), 364.6(1999)
 IF THIS CONSTRUCTION IS DONE IN BUILDING CORRECTIONS
 WILL BE REQUIRED.
 PLEASE ALSO SUPPLY DETAIL ON COMPLETE WATERPROOFING FOR
 COLD JOINTS MADE IN CONCRETE FOR THE FORTH SIDE WHICH
 WILL BE REQUIRED TO BE ADDED ALONG WITH SEAL BETWEEN
 CURBING AND FLOORING.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2007-07-17 Cont ID  
Sent By dpalmer Date 2007-07-17 Time 11:27 Rev Time 0.00
Received By dpalmer Date 2007-07-17 Time 11:27 Sent To PC
Notes
2007-07-17 11:27:25REV SHEETS 201 AND 306

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2007-07-07 Cont ID  
Sent By dpalmer Date 2007-07-07 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 15:08 Sent To I
Notes
2007-07-07 15:43:382007-07-07 15:43:38
 ** UNSAT **
  
 ** REVISIONS**
  
 1) NOTE: PLEASE SEE NEW SHEETS NOW SUBMITTED AS
 REVISIONS FOR LOW VOLTAGE CONTROLS FOR WHAT APPEARS TO
 BE PART OF A MANAGEMENT SYSTEM MUST BE SUBMITTED UNDER
 A SEPARATE PERMIT. THIS WAS NOT AND IS NOT PART OF THE
 ORIGINAL PLANS. ALL LV IS REQUIRED TO BE UNDER SEPARATE
 PERMITS.
  
 2) NOTE: PLEASE SEE REVISED SHEET E 201 INDICATES A
 REVISION, 9, 10, 11 HOWEVER ONLY THE TRIANGLES FOR 9
 AND 10 ARE LOCATED ON PLANS AND NO CHANGES COULD BE
 LOCATED FROM OUR PREVIOUS PLANS FOR SOME OF THESE AND
 ALSO NO REVISION #11 COULD BE LOCATED ON SHEET. PLEASE
 SEE THIS SHEET DOES NOT CONTAIN ANY REVISION #7. SKIPS
 FROM 6-8?
 PLEASE COORDINATE AND REVISE PLANS ACCORDINGLY. FBC
 106.1.2
  
 3) NOTE: PLEASE SEE SHEET E306 AS A OUR LAST REVISION
 ON FILE INDICATES REV #6 AND NOW THIS * REVISED SHEET*
 INDICATES A REV #7, YET THE LOCATION OF REV #7 ON
 SHEETS CONTAINS THE SAME ITEMS AS ON OUR FILE SET FOR
 REV #6??
 PLEASE COORDINATE PLANS AND REVISIONS.
  
  
 IF THERE ARE ANY QUESTIONS ON ANY OF THE ABOVE
 COMMENTS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-07 15:43:19 
 PLANS REMOVED FROM INCOMING. PLANS WILL RETURN TO
 INCOMING WAITING FOR COMM BOARD WHEN ELEC REVIEW IS
 COMPLETE.

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2007-04-16 Cont ID  
Sent By dpalmer Date 2007-04-16 Time 14:21 Rev Time 0.00
Received By dpalmer Date 2007-04-16 Time 14:20 Sent To PC
Notes
2007-04-16 14:21:34E101, 207

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2007-04-16 Cont ID  
Sent By dpalmer Date 2007-04-16 Time 14:20 Rev Time 0.00
Received By dpalmer Date 2007-04-16 Time 11:44 Sent To PC
Notes
2007-04-16 14:21:00E401 REVISION

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 11:59 Sent To  
Notes
2007-03-04 12:06:08*** UNSAT ***
  
 1) NOTE: PLEASE SEE ONCE AGAIN REVISONS FOR STREET
 LIGHTING IS BEING SUBMITTED UNDERTHE PLANSFOR THE
 BASE BUILDING WHICH IS NOT PERMITTED.PLEASE SUBMIT
 ANY REVISOS TO THE STREET LIGHTING PERMIT UNDER THE
 PERMIT FOR THAT USE/PROJECT. PLEASE SEE THAT PLANS
 WOULD BE REQUIRED TO SHOW THE MINIMUM WIND LOAD
 INFORMATION AS REQUIRED BY THE FBC 140MPH. PLEASE ALSO
 SEE THAT ALL RELEVANT CODES AND YEARS SHALL BE STATED
 ON PLANS IN WHICH THEY ARE PERMITTED.
 PLEASE DO NOT SUBMIT AS STATED ABOVE..
 THIS WORK IS BEING DONE IN THE CITY RIGHT OF WAY WHICH
 CAN NOT BE PART OF THE BASE BUILDING PERMIT.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2007-02-01 Cont ID  
Sent By dpalmer Date 2007-02-01 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2007-02-01 Time 18:58 Sent To  
Notes
2007-02-01 19:12:26** UNSAT **
  
  
  
 ** PLEASE BE AWARE OF COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 1) NOTE: PLEASE CLARIFY NEW *URBAN PARK* LANDSCAPE AND
 LIGHTING. IS THIS ON THE SAME LEGAL PROPERTY FOR
 BUILDING OR IS THIS ANOTHER LEGAL PROPERTY OR RIGHT OF
 WAY?
 IF THIS IS NOT THE SAME LEGAL PROPERTY THEN THIS MAY
 NOT BE INCLUDED FROM THIS MAIN BUILDING AND THE
 ELECTRICAL MAY NOT BE FED FROM THIS BUILDING.
 PLEASE PROVIDE REVISIONS, RESPONSE, MORE DETAILS.
 E1.01
 FBC 104.1
  
 2) NOTE: PLEASE SEE THE REVISIONS FOR SHEET E2.07
 SHOULD ALSO BE NOTED IN RESPONSE AS TO SCOPE OF
 REVISIONS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-11-20 Cont ID  
Sent By dpalmer Date 2006-11-20 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2006-11-20 Time 10:37 Sent To ENG
Notes
2006-11-21 11:25:03NOTES WHICH WERE ADDED ROUTING TO ENG WAS CHANGED.
 PLANS NOW BEING SENT OUTFRONT FOR PU AT THE REQUEST OF
 MANNY GONZALES AND RASIK FROM ENGINEERING DEPT.
2006-11-20 10:59:31*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED AS A REVISION
 UNDER THE BASE BUILDING PERMIT SHALL BE SUBMITTED UNDER
 A SEPARATE PERMIT.
 THIS WORK IS BEING DONE IN THE CITY RIGHT OF WAY WHICH
 CAN NOT BE PART OF THE BASE BUILDING PERMIT.
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS AND DETAILS FOR
 THE ELECTRICAL SCOPE OF WORK.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-09-18 Cont ID  
Sent By dpalmer Date 2006-09-18 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2006-09-18 Time 12:00 Sent To PC
Notes
2006-09-18 00:00:00REV OK, FOR UNITS AND SOME FAN/EXHAUST
 ITEMS IN GARAGE

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-02-27 Cont ID  
Sent By dpalmer Date 2006-02-27 Time 07:34 Rev Time 0.00
Received By dpalmer Date 2006-02-24 Time 20:19 Sent To  
Notes
2006-02-27 00:00:00********** UNSAT ************
  
 THE WHITNEY PROJECT
 410 EVERNIA ST.
 MR OSCAR BEHNCKE:
  
 1)NOTE: PLEASE SEE A "PROVISO" WAS GIVEN
 IN ORDER FOR BLDG PERMIT TO BE ISSUED.
 PLEASE SEE THIS "PROVISO" GIVEN REQUIRED
 THE GENERATOR, ATS, FIRE PUMP AND FIRE
 PUMP CONTROLLER TO BE UNDER SEPARATE
 PERMIT, HOWEVERPERMIT APPLICATION FOR
 THESE HAS NOT BEEN MADE. PLEASE SEE THE
 COMMENTS DATED 8/10/05 WHICH MENTIONED
 THE "PROVISO" HAD NOT BEEN ADDRESSED.
 THESE ITEMSON PLANS WERE NOT REVIEWED
 FORFULL CODE COMPLIANCE AS MUCH
 INFORMATION WAS NOT SUBMITTED ON
 ORIGINAL PLANS AND CHANGES TO BLDG MAIN
 ELECTRICAL SYSTEMS MAY BE NEEDED AS
 SHOWN.
 *** PLEASE KNOW, THIS WAS A "PROVISO"
 WAS GIVEN IN GOOD FAITH IN ORDER TO GIVE
 THE CONTRACTOR AND DELVELOPER THE
 ABILITY TO START PROJECT WITH THE
 UNDERSTANDING THE PERMIT APPLICATION,
 PLANS AND SPECS ETC WOULD BE SUBMITTED
 IN A TIMELY FASHION.
  
 ***PLEASE KNOW, IT HAS BEEN OVER 6
 MONTHS SINCE THIS NOTICE WS GIVEN IN
 NOTES DATED 8/10/05. PLEASE SEE A DATEE
 OF MAY 1ST, 2006 IS BEING GIVEN TO APPLY
 FOR ABOVE MENTIONED PERMITS. PLEASE
 KNOW, IF THESE ITEMS ARE NOT COMPLIED
 WITH, A REVOKING OF ISSUED ELECTRICAL
 PERMIT AND/OR PLACING A STOPWORK ORDER
 ON THE PROJECTS ELECTRICAL WORK WILL
 COMMENCE. PLEASE KNOW, THE DATE OF MAY
 1ST DEADLINE IS GIVEN.
  
 ** PLEASE ALSO KNOW, NO FUTHER
 ELECTRICAL REVSIONS WILL BE DONE OR
 REVIEWED FOR CODE COMPLIANCE.
 PLEASE BE AWARE REVISION AS SUBMITTED DO
 HAVE COMMENTS.
 ** PLEASE CORRELATE ALL LOADS ADJUSTED
 WITH PANEL SCHEDULES.
 ** PLEASE BE SURE TO CORRELATE ALL REV'S
 DATED ON TITLE BLOCK WITH THE REV'S
 INDICATED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE FOR PERMIT AND
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
  
2006-02-24 00:00:00REV'S IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 16:22 Rev Time 0.75
Received By dpalmer Date 2005-09-03 Time 15:44 Sent To  
Notes
2005-09-03 00:00:00REDLINED 620.23 FOR ELEVATOR MACHINE
 RMS.
  
  
 STAMPED ELECTRICAL REVISIONS.
 NO CORRECTIONS NEEDED.
  
 ONE SET ALSO STAMPED "OFFICE FILE SET"
 TO BE RETAINED WHEN REVIEWED BY FIRE.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-08-10 Time 07:28 Rev Time 0.00
Received By dpalmer Date 2005-08-10 Time 06.45 Sent To  
Notes
2005-08-10 00:00:00**********UNSAT *********
  
 REVS' #5 AND 6
  
 1)NOTE: PLEASE SEE RECEPTS MISSING FOR
 2' OF WALL SPACE IN KITCHENS IN SOME
 UNITS. 210.52
 THESE WERE REDLINED ON ONE SET OF PLANS.
 B-9,B-2, PH-8,,
  
 2)NOTE: PLEASE SEE PH-8 MENTIONS 2BDRM/
 2BATH, HOWEVER PLANS INDICATE 3 BEDRMS?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE SD OUTSIDE BEDRM IN
 PH-9.
 PLEASE ALSO SEE UNITS WITH SD'S SHOWN IN
 AREA WHICH APPEAR TO HAVE A "LOWERED
 CEILING". PLEASE BE SURE ALL SD'S ARE
 INSTALLED WITH IN 3' OF A PEAK AND W/IN
 18" OF CEILING.
 NFPA-72 CHAPTER 2
  
 4)NOTE: PLEASE SEE A "PROVISO" WAS GIVEN
 IN ORDER FOR BLDG PERMIT TO BE ISSUED.
 PLEASE SEE THIS "PROVISO" GIVEN REQUIRE
 DTHE GENERATOR, ATS, FIRE PUMP AND FIRE
 PUMP CONTROLLER TO BE UNDER SEPARATE
 PERMIT.
 AS OF TODAY'S DATE , NO PERMIT
 APPLICATION HAS BEEN SUBMITTED FOR THE
 ABOVE ITEMS.
 GEN AND ATS SAHLL BE SEAPARATE FROM FIRE
 PUMP AND FIRE PUMP CONTROLLER PERMIT.
 PLEASE UNDERSTAND NO OTHER ELECTRICAL
 REV'S WILL BE PASSED UNTIL "PROVISO" IS
 ADDRESSED.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-07-08 Cont ID  
Sent By dpalmer Date 2005-07-08 Time 09:30 Rev Time 0.50
Received By dpalmer Date 2005-07-08 Time 09:30 Sent To  
Notes
2005-07-08 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE ELECTRICAL REVSION
 SUBMITTED UNDER BASE BLDG PERMIT MUST BE
 UNDER A SEPARATE PERMIT.
 TEMP ELECTRICAL SERVICE PLANS MUST ALSO
 BE SIGNED, DATED AND SEALED BY A FLORIDA
 REGISTERED PE.
 471.003.
  
 2)NOTE: PLEASE ALSO SEE VLAUE FOR TEMP
 ELECTRICAL SERVICE MUST INCLUDE ALL
 LABOR AND MATERIALS. FBC 104.6.5
  
 PLEASE SUBMIT THE ABOVE UNDER NEW PERMIT
 APPLICATION.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-06-22 Cont ID  
Sent By dpalmer Date 2005-06-22 Time 10:22 Rev Time 8.00
Received By dpalmer Date 2005-06-21 Time 11:46 Sent To  
Notes
2005-06-22 00:00:00********** REVSIONS UNSAT **********
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW. INFORMATION FOR GENERATOR, ATS,
 FIRE PUMP, FUEL TANK ETC WAS NOT
 SUBMITTED UNDER MAIN PERMIT A "PROVISO"
 WAS GIVEN IN ORDER TO ISSUE BLDG PERMIT.
 PLEASE NOTE:GEN, FIRE PUMP ETC IS ALL
 REQUIRED TO BE SUBMITTED UNDER SEPARATE
 PERMIT(S) AND SEPARATE PERMIT FEES WILL
 APPLY.
 AS OF THIS REVIEW, NO PERMIT APPLICATION
 HAS BEEN SUBMITTED.
  
 2)NOTE: PLEASE SEE ALL FEEDERS ETC WHICH
 HAVE NOW BEEN CHANGED TO "ALUM".
 PLEASE SEE PER LOCAL AMENDMENTS, NO ALUM
 FOR GROUNDING OR BONDING IS PERMITTED.
 PLEASE REMOVE ALUM NOW SHOWN FOR THIS.
 PLEASE ALSO SEE NO ALUM IS PERMITTED
 SMALLER THAN #2.
 PLEASE NOW SPECIFY ON PLANS EACH FEEDER
 ETC WHICH WILL BE ALUM AND WHICH WILL BE
 COPPER AS SOME ARE NOT SPECIFIED.
 ORIG PLANS INDICATED ALL CONDUCTORS WERE
 TO REMAIN COPPER AND NO ALUM WAS TO BE
 INSTALLED PER ENGINEER.
 310.2,250.62
 PLEASE ALSO SEE NEXT NOTE FOR MIN
 SIZING.
  
 3)NOTE: PLEASE SEE 240.4C WHERE THE
 OVERCURRENT DEVICE IS RATED OVER 800
 AMPERES, THE AMPACITY OF THE CONDUCTORS
 IT PROTECTS SHALL BE EQUAL TO OR GREATER
 THAN THE RATING OF THE OVERCURRENT
 DEVICE DEFINED IN 240.6.
  
 NEW NOTES NOT ON ORIG REVIEW.
  
 1)NOTE; PLEASE SEE ALTERNATING OF EM
 CIRCUITS IN HALLWAY, AGRESS AREAS WILL
 BE REQUIRED. THESE AREAS ARE TO BE
 CIRCUITED AS STAIR-WELLS WHICH ARE SHOWN
 WITH ALTERNATING CIRCUITS. NFPA 101 7-9
  
 2)NOTE: PLEASE SEE MIN CIRCUITING
 REQUIRED FOR ELEVATOR MACHINE RMS PER
 620.23,620.24. MIN CIRCUITING REQUIRED
 NOT TO BE PART OR SHARE OTHER AREAS.
  
 3)NOTE: PLEASE SEE MANY UNITS WHICH
 INDICATE GEN LT /RECEPTS CIRCUITS SHOWN
 IN DINING/ KITCHEN AREAS. B1,B2,B3,B4
 ETC,PH3, PH9 ETC.
 PLEASE SEE GEN LT CIRCUIT IN KITCHEN.
 210.52B1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-27 Cont ID  
Sent By dpalmer Date 2004-08-27 Time 17:09 Rev Time 3.00
Received By dpalmer Date 2004-08-27 Time 16:09 Sent To  
Notes
2004-08-27 00:00:00*********** NOTE *******************
  
 PLEASE SEE GENERATOR/ ATS/ FUEL TANK/
 FIRE PUMP/ FIRE PUMP CONTROLLER ARE ALL
 REQUIRED TO BE UNDER A SEPARATE PERMIT.
  
 ALL OF THE ABOVE INFORMATION WAS REQUEST
 -ED ON TWO PREVIOUS REVIEWS AND NOT
 SUBMITTED.
 IF THE ABOVE INFORMATION WAS NOT
 SUBMITTED UNDER MAIN, THEN IT WILL BE
 REQUIRED TO BE PERMITTED SEPARATELY.
 THIS WILL INCLUDE VALUE/FEES.
  
 THIS INFORMATION MUST BE SUBMITTED
 BEFORE ANY ELECTRICAL INSPECTION IS
 CALLED IN. THIS WILL INCLUDE SLAB/
 UNDERGROUND INSPECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 *STAMPED PLANS**

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-26 Cont ID  
Sent By dpalmer Date 2004-07-26 Time 15:19 Rev Time 6.00
Received By dpalmer Date 2004-07-26 Time 10:07 Sent To  
Notes
2004-07-26 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE THERE IS SOME CIRCUIT
 -ING STILL MISSING IN APT UNITS.
 PLEASE SEE SOME GFI'S IN BATHS/CLOSET
 RECEPTS/ SD'S ETC MAY BE MISSING #'S.
 3.01,5.02,3.02 ETC
  
 2)NOTE: PLEASE SEE ELECTRICAL NOTES ON
 6.01 MENTIONS SD'S TO BE WIRED AHEAD
 OF BRANCH CIRCUIT FOR LIGHTING WITH ARC-
 FAULT PROTECTION; HOWEVER UNIT LAYOUTS
 INDICATE SD'S ON MANY OF THE RECEPT
 CIRCUITS.? PLEASE CORRELATE
  
 3)NOTE: PLEASE SEE 2002 NEC 210.12B FOR
 REQUIRED ARC FAULT PROETCTIONS.
 PANEL NOTES MENTIONS PROTECTION FOR
 BRANCH CIRCUITS AS NOTED TYP,NOTE#5, YET
 PLEASE SEE J-BOXES SHOWN IN MOST BEDRMS
 ARE NOT ON CIRCUITS AS NOTED. THEY ARE
 ON A SEPARATE LT BRANCH CIRCUIT W/OUT
 ARC FAULT PROTECTION.
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE SOME UNITS ARE MISSING SD'S
 ON FIRST FLR AREA LEADING TO FLR ABOVE,
 PLEASE ALSO SEE PH UNITS.
 8-1.4.1.6.2NFPA-72
  
 5)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. 3.03 A-4, 3.10 PH-9 AND OTHER
 UNITS CONTAINING 2'OF WALL SPACE INCLUD-
 -ING KITCHEN WALLS.
  
 6)NOTE: PLEASE SEE NOTES ON PH PLANS,
 (3.07,3.08) ETC REFERENCE TO SEE LIGHT-
 -ING LAYOUTS ON 2.15&2.16.
 PLEASE SEE 2.15,2.16 DO NOT SEEM TO
 CONTAIN ANY LAYOUT OF THESE LTS REFER-
 -ENCED.
  
 7)NOTE: PLEASE SEE ROOM DESIGNATIONS ARE
 PROVIDED ON SOME UNITS AND NOT OTHERS?
 PLEASE PROVIDE.
  
 8)NOTE: PLEASE SEE "ELECTRICAL NOTE"
 ON 6.01 STILL REFERENCE MIN AWG TO BE
 #12, YET PANELS SCHEDULES STILL INDICATE
 #14? PLEASE CORRELATE.
  
 9)NOTE: PLEASE ALSO SEE NOTE#1 ON
 ELECTRICAL NOTES, MENTIONS ALUM #3 AND
 LARGER PERMITTEED TO BE USED. PLEASE
 SEE LOCAL AMENDMENTS, 310.2-1 ALUM ONLY
 PERMITTED FOR #2 AND LARGER.
 PLEASE ALSO NOTE: ALUM CONDUCTORS ARE
 NOT PERMITTED FOR GROUNDING OR BONDING
 PER 310.2.2,250.62
  
 10)NOTE: PLEASE SEE RISER DIAGRAM ON
 SHEET 4.01, PLEASE SEE "DRAWING KEYNOTES
 ,BUSDUCT ON RISER NOTES #1 AND #3.
 PLEASE SEE NOTE # 3 MENTIONS BUS DUCT,
 YET NOTE#1 REFERENCES SUPPORT FOR CABLES
 ? PLEASE CORRELATE.
  
 11)NOTE: PLEASE SEE METER SUMMARY, MC-1
 SHOWS 3P-600A OCP, YET MC-1 ON LOAD
 SUMMARY MENTIONS A 1000A MCB IN A 1200A
 MAIN.
 PLEASE CORRELATE OVER CURRENT PROTECTION
  
  
 12)NOTE: PLEASE SEE RISER INDICATES
 ON FEEDER SCHEDULE (F-3) CONDUIT AND
 CONDUCTORS FROM FPL TO MC-1.
 PLEASE SEE ELECTRICAL ROOM LAYOUT ON
 3.12 APPEARS TO HAVE MORE THAN 8' OF
 UNPROTECTED CONDUCTORS INSIDE BLDG ELEC-
 -TRICAL RM. 230.70,230.6
 THESE MUST BE ENCASED ON A MIN OF 2"
 OF CONCRETE.
 PLEASE PROVIDE A NOTE ON RISER/PLANS
 WHICH REFERENCES TO THESE FEEDERS TO
 BE "ENCASED IN CONCRETE"
  
 13)NOTE:PLEASE SEE RISER DIAGRAM SHOWS
 POWER COMING IN FROM FPL INTO FIRE PUMP
 MAIN, YET RISER ALSO SHOWS POWER COMING
 FROM GENERATOR INTO SAME FIRE PUMP MAIN.
 PLEASE SEE THESE FEEDS WOULD NEED TO
 ENTER INTO ATS SWITCH AND THEN TO MAIN.
 IF GENERATOR IS RUNNING DUE TO A POWER
 FAILURE AND THE POWER RETURNS FROM FPL,
 THERE IS A POTENTIAL OF POWER COMING
 FROM TWO DIFFERENT SOURCES AS SHOWN.
 THIS WOULD CREATE AN FIRE/LIFE SAFETY
 HAZARD.
  
 14)NOTE: PLEASE SEE SOME CLOTHES CLOSETS
 ARE SHOWING RECEPTS. IF THESE ARE FOR
 ANY TYPE OF "PLUG-IN" LV TRANSFORMERS
 FOR ALARM PANELS ETC. THESE WILL NOT
 BE PERMITTED DUE TO THE CLOSE PROXIMITY
 OF EASILY IGNITIBLE MATERIALS. 240.24D
 PLEASE SEE SOME UNIT SHOW IN ALUNDRY RMS
 WHICH ARE OK.
 NOTE: IF RECEPTS ARE MOVED TO AN ARE OF
 CLOSET WHERE ITEMS ARE NOT ABLE TO BE
 STORED NEXT TO UNIT THEN PLEASE REVISE
 LOCATION. (ABOVE DRS)?
  
 15)NOTE: PLEASE SEE POSSIBLE FIRE REVIEW
 COMMENTS IN REFERENCE TO SPECS SHEETS
 NOT SUBMITTED FOR FIRE PUMP/GEN AND ASSC
 EQUIPMENT INCLUDING FUEL TANKS.
 PLEASE KNOW THAT SINCE NO SPECS SHEETS
 WERE SUBMITTED FOR FIRE PUMP, GENERATOR,
 ATS, FUEL TANKS ETC WILL ALL BE REQUIRED
 TO BE UNDER SEPARATE PERMITS. ELEC/FIRE/
 MECH ETC.
 THESE WILL ALSO BE REQUIRED TO PAY
 SEPARATE PERMIT FEES FOR EACH BASED ON
 THE VALUE OF EQUIPMENT AND LABOR.
 FBC 104.6.5
  
 16)NOTE: PLEASE SEE SOME ARCH SHEETS
 HAVE COME BACK IN WITHOUT AN ORIGINAL
 SIGNATURE. THERE ARE NUMEROUS SHEETS
 WITH A "RUBBER STAMP" SIGNATURE.
 FS 481.221 FAC 61G1-16 REQUIRES AN
 ORIGINAL SIGNATURE. THIS COMMENT IS FOR
 ARCH SHEETS AND NOT E-SHEETS BY
 STEVEN FELLER INC.
  
 PLEASE SEE THAT ONE SET REVIEWED HAS
 MANY OF THE ABOVE COMMENTS REDLINED AND/
 OR CIRCLED FOR LOCATIONS AND ITEMS
 MENTIONED IN COMMENTS.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO THREE
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 ABOUT ANY OF THE ABOVE COMMENTS, PLEASE
 DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-26 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 23:22 Rev Time 6.00
Received By dpalmer Date 2004-04-23 Time 22:35 Sent To  
Notes
2004-04-26 00:00:00**************** UNSAT *************
  
 1)NOTE: PELASE SEE FIRE REVIEW COMMENTS
 AS WILL HAVE AN AFFECT ON SOME ELECTRI-
 -CAL PLANS.
 PLEASE ALSO SEE NOTES FROM ANY OTHER
 REVIEWERS AS THEY MAY ALSO HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 2)NOTE: PLEASE SEE 61G15-23.002, PLEASE
 INCLUDE ALL REQ'D LICENSE #'S ON TITLE
 BLOCK AS REQ'D UNDER FS 471.023
 PLEASE ALSO HAVE ENGINEER SIGN PLANS
 WITH SIGNATURE AS SHOWN ON LICENSE/
 RAISED SEAL. INITIALS ARE NOT PERMITTED
 PER FS/ FBPE'S.
  
 3)NOTE: PLEASE SUBMIT MORE INFORMATION
 FOR LOCKED ROTOR OCP PER 695.4B1
 SIZED PERNEC LR.
  
 4)NOTE: PLEASE CLARIFY IF THERE IS ALSO
 GROUND LEVEL EGRESS TO OUTSIDE OF BLDG.
 IF SO, PLEASE PROIVDE LTNG PER 210.70
  
 5)NOTE: PLEASE PROVIDE NOTES FOR 700.8,
 700.9. PLEASE ALSO PROVIDE AIC RATING
 FOR GENERATOR MAX AVAILABLE FUALT
 CURRENT.
  
 6)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULES.
 PLEASE ARE NOT COMPLETE AT THIS TIME
 TO VERIFY THIS.
  
 7)NOTE: PLEASE NOTE GEN EXHAUST. THIS
 APPEARS TO HAVE A CONFLICT FOR EXHAUST
 10' OF OPENINGS/DOORS ETC.
  
 8)NOTE: LIGHTNING PROTECTION UNDER
 SEPARATE PERMIT.
 POOL ELECTRICAL WIRING ETC UNDER SEPARA-
 -TE PERMIT.
  
 9)NOTE:PLEASE SEE THAT THERE ARE AREAS
 IN GARAGE THAT SEEM TO HAVE LIGHTING
 MISSING.
  
 10)NOTE:PLEASE LABEL ALL PANELS ON PLANS
 SOME SHOWN WITH XX??
  
 11)NOTE: PLEASE SEE 210.52, RAILS AREAS
 ARE REQ'D TO HAVE OUTLETS.
  
 12)NOTE: PLEASE SEE SOME UNITS DO NOT
 SEEM TO BE COMPLETE WITH ELECTRICAL?
  
 13)NOTE: PLEASE PROVIDE NOTE FOR SHUTT-
 -ING DOWN OF GENERATOR/SIGNAGE REQ'D.
 230.2E
  
 14)NOTE:PLEASE SEE 250.6/ 250.24 THERE
 IS NO EQUIPMENT GROUNDING CONDUCTORS TO
 BE INSTALLED FROM FPL TO THE FIRST MEANS
 OF DISC.
  
 15)NOTE:: PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%
 PER 230.42,215.2,215.3,210.19 ETC.
 SOME PANELS SHOW.
  
 16)NOTE: PLEASE PROVIDE NOTE FOR ALL
 REQ'D DOOR HARDWARE UNDER 2002 NEC
 110.26.
  
 17)NOTE: PLEASE INDICATE GFI PROTECTION
 FOR WHIRLPOOL TUBS PER 680
  
 18)NOTE: PLEASE SEE NOTES PAGE:
 NOTE 1) MENTIONS ALL WIRING TO BE #12,
 YET PANEL SCHEDULES SHOW #14?
 PLEASE CORRELATE.
 NOTE 45)MENTIONS WINDS LOADS TO BE 110
 MPH. PLEASE SEE FBC FOR 140 MPH WIND
 LOAD.
 NOTE 56) SD'S TO BE A PART OF THE
 KIT/BATH LT CIRCUITS. PLEASE SEE 2002
 NEC 210.12. ARC FAULT PROTECTION FOR
 ALL OUTLETS.
  
 PLEASE NOTE: DUE TO PLANS NOT BEING
 COMEPLETE AT TIME OF PLAN REVIEW, THERE
 MAY BE OTHER COMMENTS ONCE PLANS HAVE
 BEEN COMPLETED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-04-23 00:00:001-ROLL OF PLANS IN ELECTRICAL FOR REVIEW
 PLAN REVIEW COMMENT S TO FOLLOW.
 ******* UNSAT ********
  
 PLANS SUBMITTED W/OUT BEING COMPLETE.
 PLAN REVIEW NOT COMPLETE AT THIS TIME.
 FURTHER REVIEW NOTES TO FOLLOW.
  
 DEWEY PALMER

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2006-11-21 Cont ID  
Sent By rchokshi Date 2006-11-21 Time 11:10 Rev Time 0.00
Received By rchokshi Date 2006-11-21 Time 11:10 Sent To  
Notes
2006-11-21 11:11:55NEEDS UTILITY REVIEW FROM MANNYG.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2006-10-19 Cont ID  
Sent By rchokshi Date 2006-10-19 Time 11:38 Rev Time 0.00
Received By rchokshi Date 2006-10-19 Time 11:36 Sent To E
Notes
2006-10-19 11:38:00ENG REVIEW NOT REQUIRED PER LUIS M. SEND TO ELEC,
 RASIK CHOKSHI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-08-24 Cont ID  
Sent By mamini Date 2004-08-24 Time 08:43 Rev Time 0.50
Received By mamini Date 2004-08-24 Time 08:42 Sent To  
Notes
2004-08-24 00:00:00PASSED:
 1. SEE PERMIT # 04080748 FOR UNDERGROUND
 UTILITIES AND SITE WORK. THIS PART OF
 UTILITY WORK IS UNDER DIFFERENT OWNER,
 HENCE, A SEPARATE PERMIT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-07-02 Cont ID  
Sent By mamini Date 2004-07-02 Time 16:17 Rev Time 0.50
Received By mamini Date 2004-07-02 Time 16:17 Sent To  
Notes
2004-07-02 00:00:00PASSED:
 1. SEE PERMIT # 04070054 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-04-30 Cont ID  
Sent By mamini Date 2004-04-30 Time 10:17 Rev Time 0.00
Received By MAMINI Date 2006-04-30 Time 20:49 Sent To  
Notes
2004-04-30 00:00:00FAILED:
 1. ALL OFFICIAL ELEVATION THROUGHOUT THE
 CITY OF WEST PALM BEACH MUST BE SHOWN IN
 VERTIAL DATUM OF 1929( NGVD-29 ).
 2. PLEASE SHOW CONNECTION FOR THE ROOF
 LEADER TO THE PROPOSED DRAINAGE SYS.
 3. ALL THE ISSUES AND SUBMITTALS TO
 STEVE SARLEY, REGARDING THE PROPOSED
 DRAINAGE SYSTEMS MUST BE RESOLVED AND
 APPROVED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2007-12-17 Cont ID  
Sent By mawillia Date 2007-12-17 Time 13:39 Rev Time 0.00
Received By mawillia Date 2007-12-17 Time 13:20 Sent To  
Notes
2007-12-17 13:32:33*****APPROVED, REVISION #9 DATED 10/12/07*****
  
  
 REVISED PLAN SHEET E3.06 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2007-11-21 Cont ID  
Sent By mwennerg Date 2007-11-21 Time 12:39 Rev Time 0.00
Received By mwennerg Date 2007-11-21 Time 12:39 Sent To  
Notes
2007-11-21 12:40:58SHEET A0.1 STAMPED, DATED AND SIGNED AFTER ZONING
 APPROVAL FROM LAST FIRE REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status F Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 16:16 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 15:49 Sent To  
Notes
2007-10-01 16:05:28*******APPROVED/PROVISO*****
  
  
 REVISED PLAN SHEETS A0.3 AND FP2.01 WERE REVIEWED.
 FP2.01 WAS STAMPED, INITIALED, AND DATED (WITH 1 OF THE
 3 BEING FILED).A0.3 WAS ACCEPTABLE;BUT BECAUSE
 THIS SHEET WAS DENIED BY PLANNING, IT STILL NEEDS TO BE
 FIRE-STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2007-02-06 Cont ID  
Sent By mwennerg Date 2007-02-06 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2007-02-06 Time 13:42 Sent To  
Notes
2007-02-06 13:49:39***APPROVED***
  
 1) FP 2.01 WAS SUBMITTED FOR REVISION UNDER THE
 BUILDING MASTER PERMIT NUMBER. THE REVISION IS OK,
 HOWEVER AS PREVIOUSLY STATED, ANY REVISION TO THE FIRE
 SPRINKLER SYSTEM SHALL BE SUBMITTED UNDER THE FIRE
 SPRINKLER PERMIT. THE SAME WOULD APPLY FOR ANY OTHER
 FIRE PROTECTION EQUIPMENT WHERE A SEPARATE PERMIT WAS
 REQUIRED. THE REVISED SHEET WILL BE FILED WITH THE FIRE
 SPRINKLER PERMIT. (05051264)
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2007-01-30 Cont ID  
Sent By mawillia Date 2007-01-30 Time 16:30 Rev Time 0.00
Received By mawillia Date 2007-01-30 Time 16:30 Sent To  
Notes
2007-01-30 16:32:03*****APPROVED*****
  
  
 SUBMITTAL FOR FIRE ALARM PANEL CHANGEOVER STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2006-03-16 Cont ID  
Sent By mwennerg Date 2006-03-16 Time 10:45 Rev Time 0.00
Received By mwennerg Date 2006-03-16 Time 10:45 Sent To  
Notes
2006-03-16 00:00:00******PROVISO******
  
 1) PLEASE SEE COMMENTS GENERATED BY
 ELECTRICAL PLAN REVIEW REGARDING
 GENERATOR, FIRE PUMP AND ASSOCIATED
 EQUIPMENT.
  
 2) REVISIONS MADE TO FIRE ALARM SYSTEM
 SHALL ALSO BE SUBMITTED UNDER FIRE ALARM
 PERMIT.
  
 3) REVISIONS MADE TO FIRE PROTECTION
 SHEETS SHALL ALSO BE SUBMITTED UNDER THE
 FIRE SPRINKLER PERMIT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2005-10-05 Cont ID  
Sent By mwennerg Date 2005-10-05 Time 11:03 Rev Time 0.00
Received By mwennerg Date 2005-10-05 Time 11:03 Sent To  
Notes
2005-10-05 00:00:00REVISIONS DATED 9/1/05-OK
  
 FIRE PROTECTION DRAWINGS HAVE BEEN
 SUBMITTED UNDER MASTER PERMIT. SEPARATE
 SHOP DRAWINGS NEED TO BE SUBMITTED UNDER
 FIRE SPRINKLER PERMIT APPLICATION. AT
 THAT TIME, THE SHEETS CAN BE STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2005-08-17 Cont ID  
Sent By mwennerg Date 2005-08-17 Time 09:21 Rev Time 0.00
Received By mwennerg Date 2005-08-17 Time 09:21 Sent To  
Notes
2005-08-17 00:00:00******DENIED******
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENT
 IN REGARDS TO SMOKE DETECTOR LOCATIONS
 IN UNITS.
  
 2) NO FIRE ALARM EQUIPMENT INSIDE UNITS
 CAN BE FOUND ON ELECTRICAL SHEETS.
 REFERENCE IS MADE TO FA DRAWINGS. PLEASE
 SHOW LOCATION OF ALL LOW VOLTAGE
 COMPONENTS FOR REVIEW.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2005-06-30 Cont ID  
Sent By mwennerg Date 2005-06-30 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2005-06-24 Time 10:49 Sent To  
Notes
2005-06-24 00:00:001. GENERAL REVISION # 9 ON PAGE
 AO-3 INDICATES EXIT TRAVEL POSSIBLY
 WHERE A DOOR IS PLANNED TO SEPARARE
 THE GARAGE FROM THE ALLEY. A SINGLE
 DOOR HAS BEEN RELOCATED IS THIS AREA
 AND IS THIS NOT THE PROPER EXIT. PLEASE
 RE-EXAMINE THIS AREA.
  
 2. BE ADVISED THAT ON PAGE A1-1
 A REVISION CLOUD INDICATES THE
 LOCATION OF THE PROPERTY LINE AND THE
 FIRE COMMAND DOOR IS OPENING OVER THE
 PROPERTY LINE.
  
 3. FIRE EXTINGUISHERS SHALL NOT EXCEED
 75 FEET OF TRAVEL DISTANCE.
  
 MIKE CARSILLO, FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 09:39 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 09:39 Sent To  
Notes
2004-09-16 00:00:001) EXIT SIGN NEEDED ON PAGE A0-6 NEAR
 GARAGE DOOR ADJHACEENT TO ELEVATOR # 3.
  
 2) SIGNAGE REQUIRED IN ALL STAIRWELLS
 INDICATING THE STAIR NUMBER, THE
 TERMINUS TOP AND BOTTOM AND THE FLOOR
 LEVEL.
  
 3) ALL CANVAS AWNINGS ARE TO BE FIRE
 RETARDANT.
  
 4) FIRE COMMAND ROOM REFERENCE STILL
 PRESENT ON A6-O.
  
 5) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR FIRE PUMP AND APPURTENANT
 EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-07-30 Cont ID  
Sent By mcarsill Date 2004-07-30 Time 12:16 Rev Time 0.00
Received By mcarsill Date 2004-07-30 Time 12:16 Sent To  
Notes
2004-07-30 00:00:001) MISSING EXIT SIGNS ON AO-5 FOR
 THE RESIDENTIAL ELEMENT.
  
 2) EXIT SIGNS SHALL NOT EXCEED 100
 FEET.
  
 3) SIGNS REQUIRED ON EXIT DOORS THAT
 FACE THE ALLEY. "EXIT DOOR, DO NOT
 BLOCK".
  
 4) THE WALLS SEPARATING THE GARAGE FROM
 OTHER PORTIONS OF THE BUILDING SHALL
 BE AT LEAST TWO HOUR RATED WITH HOUR AND
 A HALF OPENING PROTECTIVES.
  
 5) A FIRE COMMAND ROOM NOTE APPEARS ON
 PAGE A1-2. THIS APPEARS TO BE A
 DIFFERENT LOCATION THAN PREVIOUSLY
 PLAN SHEETS.
  
 6) EXTERIOR PLYWOOD DECKING DESCRIBED
 ON PAGE A1-16. THE BUILDING AGAIN
 IS LOCATED IN THE CITY FIRE LIMITS
 CERTAIN RESTRICTIONS WILL APPLY.
 ALSO SAME NOTES APPEAR ON PAGE A1-17.
  
 7) A FIRE COMMAND ROOM NOTE APPEARS
 ON PAGE A2-1. PLEASE CLARIFY.
  
 8) ELECTRONIC SWITCHES, CHAIN AND
 LOCK WILL BE REQUIRED ON FIRE LINE
 BACKFLOW DEVICE. NOTED ON PAGE FP2.01
  
 9) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON PAGE FP2.01 IS IN A DIFFERENT
 LOCATION AS ILLUSTRATED ON PREVIOUS
 PAGES.
  
 10) SAME CONDITION EXISTS ON PAGE
 FP2.02.
  
 11) MECHANICAL AREA ON PAGE FP2.02
 NOT FIRE SPRINKLER PROTECTED.
  
 12) PUMP ROOM 090 IS NOT FIRE
 SPRINKLER PROTECTED. WHY?
  
 13) WHY IS POOL EQUIPMENT ROOM 091
 NOT FIRE SPRINKLER PROTECTED. WHY?
  
 14) PLEASE EXPLAIN THE 1000 GPM FIRE
 PUMP. HOW MANY REQUIRED STANDPIPES
 ARE NEEDED TO MAKE THE BUILDING
 WORK.
  
 15) A NEW WATER FLOW TEST WILL
 BE REQUIRED FOR THE PROJECT. THE DATA
 SHOWN ON PAGE FP4.01 DISPLAY A DATE
 OF 8.8.03 WHICH MAKES THIS TEST
 MORE THAN ONE YEAR OLD. PLEASE
 SCHEDULE.
  
 16) PRESSURE REGULATING DEVICES SHOWN
 ON PAGE FP4.01. WILL THESE BE SET
 IN THE FIELD OR FACTORY SET.
  
 17) PLEASE DOCUMENT ON THE PLANS
 WHEN THE BATHROOMS WILL BE FIRE
 SPRINKLERED AND WHEN THEY ARE NOT.
  
 18) PLEASE EXPLAIN SMOKE DETECTORS
 LOCATED DIRECTLY OUTSIDE OF STAIRWAYS
 ON PAGE FA2.04.
  
 19) WHAT IS THE VOICE EVACUATION
 MESSAGE EXPECTED TO SAY AFTER THE
 FIRE ALARM SYSTEM IS INITIATED.
  
 20) THE FIRE ALARM SEQUENCE OF
 OPERATION FOR FIRE ALARM ITEM # 3
 IS INCORRECT. SMOKE DETECTORS WHEN
 ACTIVATED SHALL ALSO CAUSE THE
 BUILDING TO GO INTO FIRE ALARM
 MODE.
  
 21) HOW WILL THE CARBON MONOXIDE
 DETECTORS BE TESTED. PLEASE PROVIDE
 A TESTING CRITERIA. CALIBRATION GAS
 WILL BE REQUIRED TO SET THE POINTS
 ON THE DETECTOR.
  
 22) ALL EXTERIOR STAIRS ARE TO
 BE SLIP RESISTANT.
  
 23) NO FIRE HOSE VALVE CONNECTIONS
 SHOWN ON LIFE SAFETY ROOF PLAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-01 Cont ID  
Sent By mcarsill Date 2004-04-01 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2004-04-01 Time 12:46 Sent To  
Notes
2004-04-01 00:00:001) SITE PLAN DOES NOT DISPLAY ANY
 EXISTING OR NEW FIRE HYDRANTS.
  
 2) EXIT STAIRS ARE REQUIRED TO BE
 KEPT UP WITH CONSTRUCTION.
  
 3) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE
 STORIES OR 30 FEET IN HEIGHT.
  
 4) PLEASE EXPLAIN HOW ALL OF THE
 REQUIRED EQUIPMENT OF THE FBC, SECTION
 412 ARE EXPECTED TO FIT INTO THE
 SMALL COMMAND ROOM.
  
 5) HOW WILL EXIT DISCHARGE LOCATIONS
 BE MAINTAINED IN THE ALLEY. BY THE WAY
 WHO'S PROPERTY IS THE ALLEY.
  
 6) PLEASE INDICATE WHICH ELEVATORS
 WILL BE STRETCHER ACCESSIBLE.
  
 7) AN EXIT DISCHARGE LINE GOES
 THROUGH THE LOADING DOCK.
  
 8) THE TRAVEL DISTANCE LINE ON PAGE
 AO-4 FOR STAIRS # 3 GOES THROUGH A
 PARKING SPACE.
  
 9) A KNOX-BOX WILL BE REQUIRED FOR THE
 BUILDING.
  
 10) SEVERAL DOOR SWINGS MAY BE
 IMPROPER ON THE ROOF PLAN DUE TO THE
 AMOUNT OF OCCUPANTS PROPOSED.
  
 11) BATHROOMS ON ROOF APPEAR TO BLOCK
 EXIT ACCESS ON PAGE AO-10.
  
 12) BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS WILL
 APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 13) PLEASE INDICATE HOW ALL OF THE
 REQUIREMENTS OF FBC 412 IS BEING MET.
  
 14) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF 6" HIGH
 NUMBERS ARE REQUIRED.
  
 15) CDX PLYWOOD IS BEING USED. AGAIN
 BE ADVISED THE BUILDING IS LOCATED
 IN THE FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY.
  
 16) BUILDING WILL BE CONSIDERED A
 HIGH-RISE BUILDING FOR PURPOSES OF
 DETERMINING CODE COMPLIANCE.
  
 17) PLEASE EXPLAIN PURPOSE OF COVERED
 TERRACE ON PAGE A5-4.
  
 18) ELEVATOR WARNING SIGNS ARE REQUIRED
 AT ELEVATORS.
  
 19) TACTILE SIGNAGE REQUIRED AT EXITS.
  
 20) THE FIRE COMMAND ROOM ON PAGE
 M2.01 DOES NOT RELATE WITH OTHER
 PAGES ON THE DRAWINGS.
  
 21) PLEASE DISPLAY ALL WINDOWS AND
 PANELS THAT ARE PLANNED TO MEET THE
 SMOKE CONTROL NOTE BOX LOCATED ON
 THE MECHANICAL PLANS.
  
 22) THE WORDING "ANTICPATED STACK
 EFFECT" IS TO BE ADDED TO THE
 MECHANICAL SMOKE CONTROL PAGES.
  
 23) THE GENERATOR EXHAUST SHALL BE
 LOCATED A MINIMUM OF 10 FEET FROM
 WALL OPENINGS OR MAKE UP AIR
 LOCATIONS.
  
 24) THE FIRE COMMAND LOCATION ON
 ELECTRICAL DRAWINGS DO NOT RELATE TO
 OTHER DRAWINGS.
  
 25) EXIT SIGN ARROWS POINTING WRONG
 DIRECTION ON PAGE E2.13.
  
 26) ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
  
 27) THE FIRE COMMAND ROOM IN WRONG
 LOCATION ON PAGE FA2.01.
  
 28) THE FIRE DEPARTMENT CONNECTION
 SHOWN ON PAGE C-10 DOES NOT RELATE
 TO OTHER DRAWINGS.
  
 29) TAMPER SWITCHES, CHAIN AND LOCKS
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 30) ALL DEMOLITION, CONSTRUCTION,
 AND RENOVATION TO COMPLY WITH NFPA 241.
  
 31) PARKING GARAGE TO COMPLY WITH
 NFPA 88 A.
  
 32) PLEASE PROVIDE A DETAILED DRAWING
 OF WHAT THE FIRE SMOKE CONTROL WILL
 LOOK LIKE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2008-03-12 Cont ID  
Sent By mperson Date 2008-03-12 Time 16:26 Rev Time 0.00
Received By mperson Date 2008-03-12 Time 16:26 Sent To PC
Notes
2008-03-12 16:36:24REVISION SHEET P4.16: "OK" CHANGE NAT/GAS DELIVERY
 PRESSURE TO 4 PSI AND DESIGN SYSTEM TO "TRACPIPE DESIGN
 AND INSTALLATION GUIDE SECTION 7.1, TABLE PD-1"
  
 ****************PROVISO****************
 THESE TWO AREAS ARE NOT APPLICABLE REFERENCE REVISED
 LONGEST RUN AND TOTAL BTU TABLE.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2008-02-08 Cont ID  
Sent By mperson Date 2008-02-08 Time 11:40 Rev Time 0.00
Received By mperson Date 2008-02-08 Time 11:40 Sent To PC
Notes
2008-02-08 11:42:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
  
 **PREVIOUS PLAN REVIEW COMMENTS**
  
 1. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED**
 SHEET P4.16: SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 ***THE RESUBMITTED REVISION STILL ARE NOT CLEARLY
 INDICATING THE CORRESPONDING LENGTHS TO ALL CUT
 SECTIONS OF PIPE. PLESE REFERENCE THE RED CIRCLED AREA
 AND YELLOW HIGH LIGHTED PIPES WITH NO CORRESPONDING
 LENGTHS.
  
 ****NOTE: REVISED PLANS ARE DESIGNED FROM TRACPIPE
 FLEXIBLE GAS PIPING DESIGN GUIDE AND INSTALLATION
 INSTRUCTIONS SECTION 3.2D-ALTERNATE SIZING METHOD: SUM
 OF PRESSURE LOSS CALCULATIONS.
 (3) STARTING AT THE METER AND WORKING OUTWARD THE
 PRESSURE LOSS FOR EACH LEG IS SUMMED UP UNTIL THE
 FARTHEST APPLIANCE IS REACHED.
  
 ****THE REVISED GAS PLANS ARE NOT INDICATING THE
 PRESSURE LOSS FOR EACH LEG PER TRACPIPE DESIGN GUIDE
 NOR ARE THERE ANY CALCULATIONS BEING INDICATED FOR
 PRESSURE LOSS FOR EACH LEG. COMMENT #1 NEEDS TO BE
 ADDRESSED AND PRESSURE LOSS FOR EACH LEG NEEDS TO BE
 CALCULATED AND INDICATED ON THE PLANS.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **OK** COMMENT ADDRESSED
  
 5. **NO COMMENT RESPONSE, NOTE: ITEMS A, B, C, AND D,
 HAVE BEEN ADDRESSED HOWEVER THERE ARE ISSUES WITH THE
 MP REGULATORS**
  
 AT A MINIMUM THE REVISED PLANS SHALL REFLECT WHAT IS
 INSTALLED AND THEY DO NOT. PLEASE CORRECT THE PLANS TO
 REFLECT THE FOLLOWING ON ALL AREAS OF THE PLAN SHEET.
 PER FBC FUEL GAS SECTION *401.1, SCOPE.
  
 "APPLIANCE LOAD TABLE"
  
 A- **OK** COMMENT ADDRESSED
  
 B- **OK** COMMENT ADDRESSED
  
 C- **OK** COMMENT ADDRESSED.
  
 D- **OK** COMMENT ADDRESSED.
  
 ****NOTE: THERE ARE STILL CONCERNS WITH THE MP
 REGULATORS.
  
 NOTE: PER MAXITROL ([email protected]) THE 325-7 IS
 ONLY RATED FOR 900,000 BTU'S. THE 325-7 WOULD NEED A
 MINIMUM OF 1 PSI ON THE INLET AND THE 210 CAN WORK AT
 14" W.C.PRESSURE. THE 210 SERIES IS NOT A DEAD END LOCK
 UP.
  
 ****RESUBMITTED REVISED PLANS ARE INDICATING ONLY
 700,000 BTU'S FOR THE POOL/SPA HEATERS, HOWEVER
 MAXITROL STATES FROM THEIR TEC SUPPORT THAT THERE
 REGULATORS SHOULD NOT BE USED. AT THE CAPACITIES BEING
 USED ON THIS SYSTEM THEY DO NOT MAKE A DEAD END LOCKUP
 REGULATOR. A BETTER CHOICE WOULD BE ANOTHER COMPANY
 SUCH AS ACTARIS OR INVENSYS.
  
 **WITH THE FACTS BEING STATED FROM MAXITROL NEITHER
 REGULATOR IS ACCEPTABLE DUE TO THE PRESSURE LOSS OF THE
 SYSTEM (42.024 WATER COL. PRESSURE DROP OF SYSTEM WHICH
 LEAVES LESS THAN 0.5 PSI AT THE REGULATORS), LOAD
 CAPACITY OF REGULATORS (325-7 RATED 900,000 BTU), AND
 210 SERIES NOT BEING A DEAD END LOCK UP, WHICH MEANS
 UNDER STATIC CONDITIONS WHEN NO GAS IS FLOWING, OUTLET
 PRESSURE WILL RISE TO LINE PRESSURE.
  
 ****PER TRACPIPE DESIGN GUIDE: FOR A 2 PSI SYSTEM, THE
 PROPER DROP IS USUALLY 1 PSI FOR THIS PART OF THE
 SYSTEM.
 NOTE: THE REVISED GAS RISER DESIGN PRESSURE LOSS
 INDICATED ON THE PLANS IS 42.024 WATER COL., 1 PSI
 WATER COL IS 28. PER TRACPIPE DESIGN GUIDE THE REVISED
 GAS SYSTEM EXCEEDS THERE LIMIT BY 14.024 WATER COL.
  
 **IT IS SUGGESTED THAT SYSTEM DELIVERY PRESSURE BE
 INCREASE TO 5 PSI AND THE PROPER MP REGULATORS BE
 INSTALLED AFTER CONFERRING WITH THE MANUFACTURER. THREE
 COPIES OF THE MP REGULATOR MANUFACTURER'S SPECIFICATION
 SHEETS WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY ARE REQUIRED.
  
 6. **OK** COMMENT ADDRESSED.
  
 7. **OK** COMMENT ADDRESSED
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2008-01-23 Cont ID  
Sent By mperson Date 2008-01-24 Time 15:45 Rev Time 0.00
Received By mperson Date 2008-01-23 Time 15:45 Sent To PC
Notes
2008-01-23 16:57:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 NOTE: IN ORDER TO EXPIDITE THE GAS REVISION FOR THE
 BUILDING C/O, CHIEF PLUMBING INSPECTOR LARRY WAGNER
 FIELD INSPECTED ALL GAS APPLIANCES TO VERIFY BTU LOAD
 ON THE APPLIANCE NAME PLATES AND ALSO TO VERIFY THE MP
 REGULATORS MAKE AND MODEL NUMBER INSTALLED PER THE
 APPLIANCES. THOSE COMMENTS WILL FOLLOW THE PREVIOUS
 PLAN REVIEW COMMENTS AS NEW COMMENTS:
  
 **PREVIOUS PLAN REVIEW COMMENTS**
  
 1. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED**
 SHEET P4.16: SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 ***THE RESUBMITTED REVISION STILL ARE NOT CLEARLY
 INDICATING THE CORRESPONDING LENGTHS TO ALL CUT
 SECTIONS OF PIPE. PLESE REFERENCE THE RED CIRCLED AREA
 AND YELLOW HIGH LIGHTED PIPES WITH NO CORRESPONDING
 LENGTHS.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED**
 SHEET P4.16: PLEASE CORRELATE THE LONGEST RUN PER
 COMMENT #1.
 NOTE: UNTIL COMMENT #1 IS PROPERLY ADDRESSED THIS
 COMMENT WILL CONTINUE TO APPEAR.
  
 **NEW COMMENTS PER FIELD INSPECTION AND APPLIANCE
 SUBMITTALS**
  
 5. AT A MINIMUM THE REVISED PLANS SHALL REFLECT WHAT
 IS INSTALLED AND THEY DO NOT. PLEASE CORRECT THE PLANS
 TO REFLECT THE FOLLOWING ON ALL AREAS OF THE PLAN
 SHEET. PER FBC FUEL GAS SECTION *401.1, SCOPE.
  
 "APPLIANCE LOAD TABLE"
  
 A- POOL/SPA HEATER (2) @300 CFH (EA.) TOTAL BTU'S =
 600,000 OR 600 CFH.
  
 B- BOILER = 1,480,000 BTU'S OR 1480 CFH.
  
 C- WATER HEATER = 1,050,000 BTU'S OR 1050 CFH.
  
 D- WATER HEATER = 1,050,000 BTU'S OR 1050 CFH.
  
 NOTE: PER MAXITROL ([email protected]) THE 325-7 IS
 ONLY RATED FOR 900,000 BTU'S. THE 325-7 WOULD NEED A
 MINIMUM OF 1 PSI ON THE INLET AND THE 210 CAN WORK AT
 14" W.C.PRESSURE. THE 210 SERIES IS NOT A DEAD END LOCK
 UP.
  
 **WITH THE FACTS BEING STATED FROM MAXITROL NEITHER
 REGULATOR IS ACCEPTABLE DUE TO THE PRESSURE LOSS OF THE
 SYSTEM (42.024 WATER COL. PRESSURE DROP OF SYSTEM WHICH
 LEAVES LESS THAN 0.5 PSI AT THE REGULATORS), LOAD
 CAPACITY OF REGULATORS (325-7 RATED 900,000 BTU), AND
 210 SERIES NOT BEING A DEAD END LOCK UP, WHICH MEANS
 UNDER STATIC CONDITIONS WHEN NO GAS IS FLOWING, OUTLET
 PRESSURE WILL RISE TO LINE PRESSURE.
  
 **IT IS SUGGESTED THAT SYSTEM DELIVERY PRESSURE BE
 INCREASE TO 5 PSI AND THE PROPER MP REGULATORS BE
 INSTALLED AFTER CONFERRING WITH THE MANUFACTURER. THREE
 COPIES OF THE MP REGULATOR MANUFACTURER'S SPECIFICATION
 SHEETS WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY ARE REQUIRED.
  
 6. SHEET P4.16 KEY NOTES: #11 IS INDICATING THE WRONG
 WATER HEATER MAKE PER THE SUBMITTAL. THE CORRECT WATER
 HEATER MAKE IS "RBI LCD 1050" @ 1,050,000 BTU'S.
  
 7. SHEET P4.16 KEY NOTES: #12 IS INDICATING THE WRONG
 BOILER MAKE PER THE SUBMITTALS. THE CORRECT BOILER MAKE
 IS "RBI LCD 1480 @ 1,480,000 BTU'S.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-01-14 Cont ID  
Sent By mperson Date 2008-01-14 Time 11:12 Rev Time 0.00
Received By mperson Date 2008-01-14 Time 11:12 Sent To PC
Notes
2008-01-14 13:14:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 1. SHEET P4.16: SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE. **THE RESUBMITTED
 PLANS STILL ARE NOT CLEARLY INDICATING THE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 PLEASE REFERENCE THE RED CIRCLED AREA AND YELLOW HIGH
 LIGHTED PIPES WITH NO CORRESPONDING LENGTHS.
  
 2. SHEET P4.16: PER FBC-2004 FUEL GAS, SECTION *409.4
 MP REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 **RESUBMITTED PLANS ARE NOT INDICATING THESE REQUIRED
 VALVES. NOTE: THE INDICATED MANIFOLD VALVE IS NOT
 ACCEPTABLE FOR THIS AND SHOULD BE DELETED.
  
 3. SHEET P4.16: THE 3" COPPER VENT UP THRU ROOF OFF
 THE 2" GAS SUPPLY PIPE MAKES NO SENSE. THE 2 PSI GAS
 PRESSURE WILL BE LOST THROUGH THIS DESIGN. PLEASE
 CORRECT THIS ON THE RESUBMITTAL. PER SECTION *401.1,
 SCOPE.
  
 4. SHEET P4.16: PLEASE CORRELATE THE LONGEST RUN PER
 COMMENT #1. **THE ADDED SUM OF THE INDICATED
 CORRESPONDING LENGTHS OF CUT SECTIONS OF PIPE ON THIS
 REVISION SUBMITTAL IS 472'-7", THE INDICATED LONGEST
 RUN ON THE PLANS IS NOW 470'-0". UNTIL COMMENT #1 IS
 PROPERLY ADDRESSED THIS FIGURE WILL AGAIN BE WRONG.
 NOTE: THE RESUBMITTED PLANS WITH THE CALCULATION "
 MAXIMUM ALLOWABLE PRESSURE DROP 1.5 PSI (42" W.C.)
 AGAIN IS WRONG PER THE ADDED SUM OF THE 1ST SECTION OF
 PIPE WHICH IS NOW 269'-7". HOWEVER UNTIL PLANS ARE
 COMPLETELY CORRELATED THIS TABLE WILL CONTINUE TO BE
 WRONG. PER SECTION *401.1, SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL/REVISION REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-01-03 Cont ID  
Sent By mperson Date 2008-01-03 Time 11:43 Rev Time 0.00
Received By mperson Date 2008-01-03 Time 11:43 Sent To PC
Notes
2008-01-03 13:34:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 **PREVIOUS REVIEW COMMENTS**
  
 1. **COMMENT NOT ADDRESSED**
 SHEET P4.16 SHOW THE LENGTHS OF PIPE FROM THE METER TO
 THE FIRST 8'-0" RISER AND SHOW THE LENGTHS OF PIPE FROM
 THE 200'-0" TO THE REGULATOR DOWNSTREAM OF ITEM (A). SO
 THE TOTAL DEVELOPED LENGTH CAN BE VERIFIED.
  
 2. SHEET P4.16 SUBMIT THE COMPUTATIONS FOR THE
 EQUATION USED TO SIZE THE PIPE PER SECTION 402.3(2) SO
 THAT ALL FIGURES AND OUT COME CAN BE VERIFIED BY AN
 INDEPENDENT ENGINEER.
 **THE RESUBMITTED PLANS WITH THE CALCULATION "MAXIMUM
 ALLOWABLE PRESSURE DROP 1.5 PSI (42"W.C.)" IS WRONG
 WHERE THE "SECTION (FEET)" IS. THE INDICATED 237'
 MEASUREMENT INDICATED PER THE INDICATED CORRESPONDING
 LENGTHSOF CUT SECTIONS OF PIPE IS WRONG THAT SECTION
 OF PIPING PER THE INDICATED CORRESPONDING LENGTHS IS
 267' WITH A PD OF 38.982. HOWEVER UNTIL COMMENT #1 IS
 ADDRESSED AND THE PLANS ARE CORRELATED THIS COMPUTATION
 CAN NOT PASS. CAN THESE ALLOWABLE PRESSURE DROPS BE
 DONE IN SECTIONS AS INDICATED ON THE PLANS OR SHOULD IT
 BE PER THE LONGEST LENGTH OF THE SYSTEM. THE INDICATED
 7.1 TRAC PIPE TABLE IS NOT CLEAR ON HOW THIS TABLE
 WORKS, PLEASE CLARIFY.
  
 **NEW COMMENTS**
  
 3. SHEET P4.16 PLEASE CORRELATE THE LONGEST RUN PER
 COMMENT #1. ** THE INDICATED LONGEST RUN OF 468'-0" IS
 WRONG PER THE INDICATED CORRESPONDING LENGTHS OF CUT
 SECTION OF PIPE IS 470'-7", HOWEVER UNTIL COMMENT #1 IS
 ADDRESSED AND THE PLANS ARE CORRELATED A GAS PLAN
 REVIEW CAN NOT BE COMPLETED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON (IN KEN STEVENS ABSENCE DUE TO
 VACATION)
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 17:21 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 17:21 Sent To  
Notes
2007-12-04 17:36:47DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P4.16 SHOW THE LENGTHS OF PIPE FROM THE METER TO
 THE FIRST 8'0" RISER AND SHOW THE LEGHTS OF PIPE FROM
 THE 200'0" TO THE REGULATOR DOWNSTREAM OF ITEM (A). SO
 THE TOTAL DEVELOPED LENGHT CAN BE VERIFIED.
  
 2. SHT P4.1.6 SUBMIT THE COMPUTATIONS FOR THE EQUATION
 USED TO SIZE THE PIPE PER SECTION 402.3 (2) SO THAT ALL
 FIGURES AND OUTCOME CAN BE VERIFIED BY AN INDEPENDANT
 ENGINEER.
  
 3. SUBMIT THE CALCULATIONS TO AN INDEPENDENT ENGINEER
 FOR VERIFICATION AND THEN RESUBMIT THE GAS REVISION
 WITH THE INDEPENDENT ENGINEERS FINDINGSFOR REVIEW.
  
 4. SHT P4.1.6 INDICATE THE MATERIAL FOR EACH SECTION OF
 PIPE AS SOME OF THE PIPING WAS CHANGED FROM BLACK IRON
 PIPE TO CSST PIPE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-04-05 Cont ID  
Sent By kstevens Date 2007-04-05 Time 18:35 Rev Time 0.00
Received By kstevens Date 2007-04-05 Time 18:34 Sent To  
Notes
2007-04-05 18:38:46REVISION PASSED/PROVISO
 REFERENCE: FBC-2001 FUEL GAS
  
 1. CHANGES TO THE GAS LINE ROUTING SHOWN ON SHT P2.02A
 REQUIRES A REVISION TO THE GAS RISER DIAGRAM. SUBMIT
 THE FOLLOWING:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 15:51 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 15:51 Sent To G
Notes
2008-03-11 15:52:04TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 14:47 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 14:47 Sent To P
Notes
2008-02-01 14:47:47TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:24 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:24 Sent To G
Notes
2007-12-21 16:24:22TO KEN STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 11:34 Sent To M
Notes
2007-12-06 11:34:20TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 12:51 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 12:51 Sent To  
Notes
2007-11-06 08:19:18TO "COMM" BD#15
2007-10-30 12:52:09WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 11:48 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 11:48 Sent To  
Notes
2007-11-09 14:03:24TO "COMM" BD#22
2007-10-15 11:48:40WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 11:26 Sent To B
Notes
2007-10-16 14:45:12 
 DOCUMENTATION FOR RECORDING OF AGREEMENT TO PROVIDE
 MONIES CONVEYED TO THE CONDO ASSOCIATION TO HOLD IN
 ESCROW FOR PROVISION OF BALCONY RAMPS AS REQUIRED.
2007-10-15 11:26:46TO "JERALD SMITH"

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 15:03 Sent To M
Notes
2007-09-06 15:03:49TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 14:52 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 14:52 Sent To M
Notes
2007-09-06 14:52:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 15:22 Sent To  
Notes
2007-09-11 09:06:52TO "COMM' BD#32--TAKEN FROM "COMM" BD, AND ROUTED TO
 "RBROWN" DESK
2007-08-22 15:22:41WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 10:07 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 10:07 Sent To M
Notes
2007-08-15 10:08:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 13:27 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 13:27 Sent To M
Notes
2007-08-06 13:27:52TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 14:07 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 14:07 Sent To  
Notes
2007-08-14 14:57:18TO "COMM" BD#29
2007-07-30 14:07:30WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 18:07 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 18:07 Sent To P
Notes
2007-07-28 18:07:49TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 15:38 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 15:38 Sent To P
Notes
2007-07-24 15:38:45TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 17:15 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 17:15 Sent To P
Notes
2007-07-19 17:15:26TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 17:14 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 17:14 Sent To B
Notes
2007-07-19 17:14:49TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 17:07 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 17:07 Sent To  
Notes
2007-08-01 13:40:30TO "COMM" BD#17
2007-07-19 17:08:28WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 09:46 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 09:46 Sent To B
Notes
2007-07-10 09:46:51TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 15:19 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 15:19 Sent To M
Notes
2007-07-03 15:20:13TO "HMOSER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 15:20 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 15:20 Sent To  
Notes
2007-07-09 14:39:587/9/07---PLANS ROUTED TO KEN STEVENS TODAY
2007-06-21 15:22:13WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 11:00 Sent To M
Notes
2007-06-01 11:00:30TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 11:29 Sent To  
Notes
2007-05-29 11:30:03WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 09:28 Sent To P
Notes
2007-05-29 09:28:41TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 10:03 Sent To  
Notes
2007-05-14 10:03:33WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 10:04 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 10:04 Sent To M
Notes
2007-04-30 10:04:33TO "RREGUIERO" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 15:32 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 15:32 Sent To B
Notes
2007-04-20 15:33:13TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 15:56 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 15:56 Sent To M
Notes
2007-04-16 15:57:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 15:30 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 15:30 Sent To M
Notes
2007-04-12 15:31:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 15:24 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 15:24 Sent To P
Notes
2007-04-12 15:25:06TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 15:01 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 15:01 Sent To E
Notes
2007-04-12 15:04:25TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2007-04-05 Cont ID  
Sent By spalmer Date 2007-04-05 Time 17:07 Rev Time 0.00
Received By spalmer Date 2007-04-05 Time 17:07 Sent To E
Notes
2007-04-05 17:07:20TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2007-03-25 Cont ID  
Sent By adarroug Date 2007-03-25 Time 13:47 Rev Time 0.00
Received By adarroug Date 2007-03-25 Time 13:47 Sent To P
Notes
2007-03-25 13:47:37TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 11:57 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 11:57 Sent To B
Notes
2007-03-23 11:57:20TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 16:26 Sent To M
Notes
2007-03-22 16:26:57TO "RREGUIERO" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 16:48 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 16:48 Sent To FIRE
Notes
2007-03-19 16:49:10TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 16:10 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 16:10 Sent To P
Notes
2007-03-19 16:12:471 REV, EXPEDITED TO "KSTEVENS"THE OTHER "P" REV TO
 "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 11:30 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 11:30 Sent To M
Notes
2007-03-14 11:30:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 15:48 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 15:48 Sent To P
Notes
2007-03-10 15:48:42TO "P' BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 10:19 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 10:19 Sent To  
Notes
2007-03-02 09:56:59TO "COMM" BD#56
2007-03-01 10:19:15WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 14:27 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 14:27 Sent To P
Notes
2007-02-13 14:27:42TO "PSHCMITZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 11:04 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 11:04 Sent To M
Notes
2007-01-17 11:04:57TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 15:27 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 15:27 Sent To  
Notes
2007-01-19 09:36:53TO "COMM" BD#32
2007-01-04 15:29:17TO "JLEECH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 16:23 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 16:23 Sent To ENG
Notes
2006-10-14 16:23:57TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 08:16 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 08:14 Sent To  
Notes
2006-10-10 08:15:59TO"RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 14:49 Sent To  
Notes
2006-09-05 00:00:00TO "COMM" BD#17
2006-08-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 11:32 Sent To B
Notes
2006-08-16 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 16:29 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 16:29 Sent To B
Notes
2006-07-27 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 16:51 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 16:51 Sent To B
Notes
2006-06-07 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 09:47 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 09:47 Sent To B
Notes
2006-04-10 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 08:53 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 08:53 Sent To B
Notes
2006-03-30 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 17:43 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 17:43 Sent To B
Notes
2006-03-21 00:00:00TO RBROWN DESK

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 10:54 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 10:54 Sent To B
Notes
2006-03-17 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 18:35 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 18:35 Sent To B
Notes
2006-03-09 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 19:20 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 19:20 Sent To B
Notes
2006-03-02 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 14:17 Sent To B
Notes
2006-02-28 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2006-02-25 Cont ID  
Sent By adarroug Date 2006-02-25 Time 13:07 Rev Time 0.00
Received By adarroug Date 2006-02-25 Time 13:07 Sent To FIRE
Notes
2006-02-25 00:00:00TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2006-02-24 Cont ID  
Sent By adarroug Date 2006-02-24 Time 09:52 Rev Time 0.00
Received By adarroug Date 2006-02-24 Time 09:52 Sent To B
Notes
2006-02-24 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 16:18 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 16:18 Sent To B
Notes
2006-02-15 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2006-02-14 Cont ID  
Sent By adarroug Date 2006-02-14 Time 10:53 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 10:53 Sent To B
Notes
2006-02-14 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2006-02-07 Cont ID  
Sent By adarroug Date 2006-02-07 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-02-07 Time 14:22 Sent To B
Notes
2006-02-07 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2006-01-24 Cont ID  
Sent By adarroug Date 2006-01-24 Time 09:56 Rev Time 0.00
Received By adarroug Date 2006-01-24 Time 09:56 Sent To  
Notes
2006-05-25 00:00:005/25/06-ROUTED TO "RBROWN" DESK
2006-02-15 00:00:00TO "COMM" BD#54
2006-01-24 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 13:39 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 13:39 Sent To B
Notes
2006-01-23 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-01-05 Cont ID  
Sent By adarroug Date 2006-01-05 Time 13:54 Rev Time 0.00
Received By adarroug Date 2006-01-05 Time 13:54 Sent To B
Notes
2006-01-05 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 10:32 Sent To B
Notes
2005-12-19 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2005-11-08 Cont ID  
Sent By adarroug Date 2005-11-08 Time 09:12 Rev Time 0.00
Received By adarroug Date 2005-11-08 Time 09:12 Sent To B
Notes
2005-11-08 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 09:31 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 09:31 Sent To B
Notes
2005-10-12 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 17:06 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 17:06 Sent To B
Notes
2005-10-11 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 16:34 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 16:34 Sent To B
Notes
2005-09-27 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 14:23 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 14:23 Sent To B
Notes
2005-09-20 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 14:21 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 14:21 Sent To B
Notes
2005-09-12 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2005-09-09 Cont ID  
Sent By adarroug Date 2005-09-09 Time 15:12 Rev Time 0.00
Received By adarroug Date 2005-09-09 Time 15:12 Sent To B
Notes
2005-09-09 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 18:00 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 18:00 Sent To  
Notes
2005-09-01 00:00:00TO "COMM" BD#42/PLANS ON RACK/3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 19:12 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 19:12 Sent To B
Notes
2005-08-23 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-08-17 Cont ID  
Sent By adarroug Date 2005-08-17 Time 16:25 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 16:25 Sent To B
Notes
2005-08-17 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-08-15 Cont ID  
Sent By adarroug Date 2005-08-15 Time 15:23 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 15:23 Sent To B
Notes
2005-08-15 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-08-04 Cont ID  
Sent By adarroug Date 2005-08-04 Time 11:47 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 11:47 Sent To B
Notes
2005-08-04 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 14:08 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 14:08 Sent To M
Notes
2005-07-22 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 13:51 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 13:51 Sent To  
Notes
2005-07-25 00:00:00TO "COMM" BD#17
2005-07-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 11:40 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 11:40 Sent To B
Notes
2005-07-18 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 15:10 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 15:10 Sent To E
Notes
2005-07-06 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 08:42 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 08:42 Sent To B
Notes
2005-06-08 00:00:00SENT TO ANA MARIA (ZONING)
  
  
2005-05-24 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 08:03 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 08:03 Sent To M
Notes
2005-05-24 00:00:00TO "PKRAUSS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-17 Cont ID  
Sent By adarroug Date 2005-05-17 Time 08:18 Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 16:47 Sent To  
Notes
2005-05-17 00:00:00TO "COMM" BD#3/TOP OF RES.RACK
2005-05-04 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 13:22 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 13:21 Sent To B
Notes
2005-04-29 00:00:00TO "RBROWN" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-26 Cont ID  
Sent By csiegber Date 2004-10-26 Time 14:31 Rev Time 0.00
Received By csiegber Date 2004-10-26 Time 14:30 Sent To  
Notes
2004-11-19 00:00:00TAKEN OFF COMMERCIAL BOARD, 3 ROLLS
 STILL ON RACK PENDING CITY COMMISSION
 MEETING RE: SHARED OWNERSHIP OF THE
 ALLEY FOR UNITY OF TITLE.WILL PROCESS
 ON 12/1/12 IF ALL IS IN ORDER.
2004-10-26 00:00:00TO COMM BD#44 (3 ROLLS ON RACK)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 14:05 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 14:05 Sent To  
Notes
2004-08-16 00:00:00TO COMM BD#30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 11:07 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 11:07 Sent To  
Notes
2004-07-02 00:00:00TO COMM BD#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-06 Cont ID  
Sent By alange Date 2004-03-30 Time 10:01 Rev Time 0.00
Received By rbrown Date 2004-03-30 Time 10:01 Sent To  
Notes
2004-03-30 00:00:00TO COMMERCIAL BD. #26ON SHELF NEAR
 ART'S AREA

Review Stop M MECHANICAL (A/C)
Rev No 31 Status P Date 2007-12-21 Cont ID  
Sent By rregueir Date 2007-12-21 Time 14:43 Rev Time 0.00
Received By rregueir Date 2007-12-21 Time 14:37 Sent To PC
Notes
2007-12-21 14:45:55MECH REV 20 PG M2.01

Review Stop M MECHANICAL (A/C)
Rev No 30 Status P Date 2007-11-17 Cont ID  
Sent By rregueir Date 2007-11-17 Time 15:58 Rev Time 0.00
Received By rregueir Date 2007-11-17 Time 15:56 Sent To  
Notes
2007-11-17 15:57:53M2.02 REV 11, M3.04 REV 7, M8.01 REV 5: OK

Review Stop M MECHANICAL (A/C)
Rev No 29 Status F Date 2007-11-17 Cont ID  
Sent By rregueir Date 2007-11-17 Time 15:56 Rev Time 0.00
Received By rregueir Date 2007-11-17 Time 15:40 Sent To  
Notes
2007-11-17 15:54:58M2.01 REVISION 18: DENIED.
 OUTSIDE AIR INTAKE FOR HP0.4 IS DIRECTLY ADJACENT TO A
 STREET OR ALLEY. MECHANICAL AND GRAVITY OUTSIDE AIR
 INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS IN ACCORDANCE WITH FBC,M 401.5.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 28 Status P Date 2007-09-17 Cont ID  
Sent By rregueir Date 2007-09-17 Time 09:04 Rev Time 0.00
Received By rregueir Date 2007-09-17 Time 08:35 Sent To  
Notes
2007-09-17 08:36:00STAIR PRESSURE T & B REPORT.

Review Stop M MECHANICAL (A/C)
Rev No 27 Status P Date 2007-09-17 Cont ID  
Sent By rregueir Date 2007-09-17 Time 09:30 Rev Time 0.00
Received By rregueir Date 2007-09-15 Time 15:49 Sent To  
Notes
2007-09-17 09:35:11MECH REV M2.01,M5.02,M8.01,M8.03,M8.04

Review Stop M MECHANICAL (A/C)
Rev No 26 Status P Date 2007-08-22 Cont ID  
Sent By rregueir Date 2007-08-22 Time 09:29 Rev Time 0.00
Received By rregueir Date 2007-08-21 Time 19:39 Sent To  
Notes
2007-08-22 09:30:00REVISED M2.03, M5.02 AND M8.04 PASSED

Review Stop M MECHANICAL (A/C)
Rev No 25 Status F Date 2007-08-22 Cont ID  
Sent By rregueir Date 2007-08-22 Time 09:04 Rev Time 0.00
Received By rregueir Date 2007-08-15 Time 17:06 Sent To E
Notes
2007-08-22 09:04:12REVISION M2.01 ADDED FSD
 ----------------DENIED-----------------
  
 PLAN SHOWS NEW TRANSFER DUCTOVER DOUBLE-DOORS WITH
 FSD. THE DEDIGNATION OF THE DAMPER IS FSD1.1 AND IT HAS
 THE NOTATION OF (N.C.). THIS IS THE COMMON ABBREVIATION
 FOR 'NORMALLY CLOSED' WHEN RELATED TO FIRE/SMOKE
 DAMPERS. THIS INFORMATION IS IN CONFLICT WITH THE
 FIRE/SMOKE DAMPER SCHEDULE ON M5.02, WHERE FSD1.1 IS
 SHOWN TO BE NORMALLY OPEN AND OPEN WHEN THERE IS NO
 POWER. PLEASE CLARIFY THE INTENT AND REQUIRED
 FUNCTIONALITY OF THIS DAMPER. COORDINATE WITH FSD
 SCHEDULE.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 24 Status P Date 2007-07-14 Cont ID  
Sent By rregueir Date 2007-07-14 Time 10:15 Rev Time 0.00
Received By rregueir Date 2007-07-14 Time 08:40 Sent To  
Notes
2007-07-14 10:15:05REVISED M2.01, M2.03, M2.05(6), M2.05(7), M2.08(6),
 M2.08(7)

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2007-06-02 Cont ID  
Sent By rregueir Date 2007-06-02 Time 08:49 Rev Time 0.00
Received By rregueir Date 2007-06-02 Time 08:34 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 22 Status F Date 2007-05-30 Cont ID  
Sent By rregueir Date 2007-05-30 Time 09:09 Rev Time 0.00
Received By rregueir Date 2007-05-29 Time 14:08 Sent To  
Notes
2007-05-30 09:10:51SCOPE OF WORK RELATED TO GENERATOR EXHAUST IS NOT
 CLEAR. JOB MEETING WITH ARCHITECT IS SCHEDULED FOR 5/30
 TO DISCUSS DESIGN WITH ARCHITECT.
  
 RONLD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2007-05-29 Cont ID  
Sent By rregueir Date 2007-05-29 Time 14:05 Rev Time 0.00
Received By rregueir Date 2007-05-29 Time 11:10 Sent To P
Notes
2007-05-29 14:06:45M.301B NEW SHEET, M3.06, M8.04 REVISED. MECH PAGES
 REMOVED AND FILED. PLUMBING PAGES SENT TO PLUMBING
 INBOX.

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2007-04-30 Cont ID  
Sent By rregueir Date 2007-04-30 Time 17:49 Rev Time 0.00
Received By rregueir Date 2007-04-30 Time 17:04 Sent To PC
Notes
2007-04-30 17:49:32REVISED/NEW SHEETS M3.01A, M3.12, M3.20 OK
  
 M3.19 PROVISO: MISSING FIRE DAMPER IN 14X6 TRANSFER
 DUCT. REVISE AND RESUBMIT.
  
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 19 Status F Date 2007-04-25 Cont ID  
Sent By rregueir Date 2007-04-25 Time 16:55 Rev Time 0.00
Received By rregueir Date 2007-04-25 Time 14:29 Sent To  
Notes
2007-04-25 16:55:24---------------DENIED-------------------
  
 1. M2.01 AND M2.03: GENERATOR EXHAUST PLAN VIEW DOES
 NOT MATCH WHAT IS SHOWN ON ELEVATION VIEW. PLEASE
 COORDINATE DRAWINGS. ALSO, PLEASE PROVIDE INSTALLATION
 INSTRUCTIONS AS NECESSARY TO DETERMINE WHETHER NEW
 EXHAUST DESIGN WILL MEET THE MAX. 2" BACK PRESSURE
 REQUIREMENT.
  
 2. M2.01 AND M2.03: MUST ALSO REVISE THESE PAGES ON
 GENERATOR PERMIT #06041193
  
 3. M3.01: OK
  
 4. M3.01A: WHERE IS 1ST FLOOR LEVEL PLANS FOR THESE
 LOFTS?
  
 5. M3.12: ONLY 2 COPIES PROVIDED. RESUBMIT WITH 3
 COPIES.
  
 6. M3.19 AND M3.20: MISSING FIRE AND/OR SMOKE DAMPERS
 IN SEVERAL LOCATIONS, BOTH PAGES.
  
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2007-03-23 Cont ID  
Sent By rregueir Date 2007-03-23 Time 15:39 Rev Time 0.00
Received By rregueir Date 2007-03-22 Time 19:07 Sent To  
Notes
2007-03-23 15:38:39NEW SHEETS M3.13-3.18 DUCT LAYOUT FOR 8TH FLOOR
 EXCLUDING CORRIDORS.
  
 ****************PROVISO*****************
  
 RETURN TRANSFERS ARE NOT DESIGNED TO MEET THE
 EXCEPTIONS OF FBC,M 601.4. UNLESS THEY ARE DESIGNED TO
 MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED TO
 VERIFY BALANCED RETURN.
  
 NOTE: SEE PAGES M2.13,M2.14 FOR CORRIDOR DUCT PLAN.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 17 Status F Date 2007-03-20 Cont ID  
Sent By rregueir Date 2007-03-20 Time 09:25 Rev Time 0.00
Received By rregueir Date 2007-03-20 Time 08:54 Sent To  
Notes
2007-03-20 09:25:38PAGES M3.12 AND 3.13 ISSUED AS NEW SHEETS BEING USED TO
 REVISE EXISTING SHEETS. THERE IS NO WAY TO DISCERN WHAT
 CHANGES WERE MADE. PLEASE RESUBMIT REVISIONS WHICH
 RELATE TO EXISTING PAGES THAT ARE BEING CHANGED WITH
 REVISED AREAS CLEARLY MARKED .
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2007-03-20 Cont ID  
Sent By rregueir Date 2007-03-20 Time 08:54 Rev Time 0.00
Received By rregueir Date 2007-03-20 Time 08:11 Sent To  
Notes
2007-03-20 08:54:16MECH REVISIONS PAGES M3.04 AND M3.07 RECEIVED 2/26/07

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2007-01-30 Cont ID  
Sent By tgordon Date 2007-01-30 Time 14:49 Rev Time 0.25
Received By tgordon Date 2007-01-30 Time 14:49 Sent To FIRE
Notes
2007-01-30 15:02:20SUBMITTAL FOR SMOKE CONTROL PANELS.

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2007-01-06 Cont ID  
Sent By hmoser Date 2007-01-06 Time 12:28 Rev Time 0.00
Received By hmoser Date 2007-01-06 Time 12:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2006-09-18 Cont ID  
Sent By hmoser Date 2006-09-18 Time 10:05 Rev Time 0.00
Received By hmoser Date 2006-09-18 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 12 Status F Date 2006-09-07 Cont ID  
Sent By hmoser Date 2006-09-07 Time 14:10 Rev Time 0.00
Received By hmoser Date 2006-09-07 Time 15:04 Sent To  
Notes
2006-09-07 00:00:00PLAN DENIED
 REVISONS NOT MARKED ON PLANS PAGE M2.02
 AND M2.04.PAGE M3.03,M3.04,M3.05,M7.01
 OK.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 11 Status F Date 2006-06-22 Cont ID  
Sent By hmoser Date 2006-06-22 Time 09:48 Rev Time 0.00
Received By hmoser Date 2006-06-22 Time 09:48 Sent To  
Notes
2006-06-22 00:00:00PLAN DENIED
 NO MECHANICAL PLANS SHOWING LOCATION OF
 FUEL TANK,FUEL PIPING FROM FUEL TANK TO
 THE GENERATOR.PLEASE REFER TO TABLE
 1302.3 FBC(M)2004.PLEASE SEE BUILDING
 NOTES MECHANICAL CODE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2006-03-01 Cont ID  
Sent By pkrauss Date 2006-03-01 Time 06:40 Rev Time 0.00
Received By pkrauss Date 2006-02-28 Time 15:01 Sent To  
Notes
2006-03-01 00:00:00PROVISO:
 REVISION; PLAN SHEETS M2.01, M2.03, AND
 M5.02
  
 1.PLAN SHEET M2.01, PLEASE LOCATE
 FRESH AIR INTAKES TO THE FIRE PUMP ROOM
 AND THE SWITCHGEAR ROOMS AS HIGH AS
 POSSIBLE.PER 2001 FBC 401.5.1, INTAKE
 OPENINGS SHALL BE LOCATED A MINIMUM OF
 10 FT FROM NOXIOUS CONTAMINANTS SUCH AS
 LOADING DOCKS.PLEASE ALSO PROVIDE CO
 SENSORS IN THESE ROOMS.
  
 2.PLEASE NOTE, THE TERMINATION OF THE
 MUFFLER EXHAUST FROM THE GENERATOR SHALL
 COMPLY WITH 2005 NFPA 110 CHAPTER 7
 SECTION 7.10.2, EXHAUST SYSTEM SHALL
 TERMINATE IN SUCH A MANNER THAT TOXIC
 FUMES CONNOT REENTER A BUILDING OR
 STRUCTURE THROUGH WINDOWS, AIR
 VETILATION INTLETS OR THE ENGINE AIR
 INTAKE SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status N Date 2005-10-17 Cont ID  
Sent By pkrauss Date 2005-10-17 Time 07:45 Rev Time 0.55
Received By pkrauss Date 2005-10-17 Time 07:45 Sent To  
Notes
2005-10-17 00:00:00PLEASE NOTE DOORS SUBMITTED FOR THE A/C
 CLOSET ARE ACCEPTABLE BUT ARE ONLY
 REQUIRED TO COMPLY WITH 2001 FBC CHAPTER
 2:
  
 NONCOMBUSTIBLE BUILDING MATERIAL. A
 MATERIAL WHICH MEETS EITHER OF THE
 FOLLOWING REQUIREMENTS:
  
 1. MATERIALS WHICH PASS THE TEST
 PROCEDURE SET FORTH IN ASTM E 136.
  
 2. MATERIALS HAVING A STRUCTURAL BASE
 OF NONCOMBUSTIBLE MATERIALS AS
 DEFINED IN 1, WITH A SURFACING NOT
 MORE THAN 1/8 INCH (3.17 MM) THICK
 WHICH HAS A FLAMESPREAD RATING NOT
 GREATER THAN 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84.
  
 THE TERM NONCOMBUSTIBLE DOES NOT APPLY
 TO THE FLAMESPREAD CHARACTERISTICS
 OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSED AS
 NONCOMBUSTIBLE WHICH IS SUBJECT TO
 INCREASE IN COMBUSTIBILITY OR
 FLAMESPREAD RATING BEYOND THE LIMITS
 HEREIN ESTABLISHED THROUGH THE
 EFFECTS OF AGE, MOISTURE OR OTHER
 ATMOSPHERIC CONDITIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2005-08-03 Cont ID  
Sent By hmoser Date 2005-08-03 Time 19:03 Rev Time 0.00
Received By hmoser Date 2005-08-03 Time 19:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 06:52 Rev Time 0.40
Received By pkrauss Date 2005-07-25 Time 19:56 Sent To  
Notes
2005-07-26 00:00:00SUBMITTAL FOR SPECIFIC DRYERS WITH
 LETTER FROM THE ENGINEER - PLEASE NOTE,
 LETTER INDICATES WITH 4" RIGID DUCT THE
 DRYER IS CAPABLE OF VENTING 140 FT., THE
 SUBMITTAL DATA INDICATES 150 FT WITH 0
 90 DEGREE BENDS.5 FOOT REDUCTION
 REQUIRED FOR EACH 90 AND 5 FT FOR TWO 45
 DEGREE BENDS.SPECIFIC DRYERS TO BE
 INSTALLED FOR FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-07-06 Cont ID  
Sent By pkrauss Date 2005-07-06 Time 14:19 Rev Time 5.00
Received By pkrauss Date 2005-07-06 Time 14:19 Sent To  
Notes
2005-07-06 00:00:00REVISION
 PLANS APPROVED WITH THE EXCEPTION OF THE
 DRYER BOOSTER FANS 7-1-05.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2005-05-03 Cont ID  
Sent By pkrauss Date 2005-05-03 Time 14:29 Rev Time 0.40
Received By pkrauss Date 2005-05-03 Time 14:29 Sent To  
Notes
2005-05-03 00:00:00SUBMITTAL BOOK/PER CONVERSATION W/OSCAR
 BEHNCKE ON 5-3-05:
 DRYER BOOSTER FAN APPROVAL IS PENDING
 MANUFACTURER'S APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-11-09 Cont ID  
Sent By pkrauss Date 2004-11-09 Time 10:33 Rev Time 2.00
Received By pkrauss Date 2004-11-05 Time 16:32 Sent To  
Notes
2004-11-09 00:00:00PROVISO:
  
 1.PLAN SHEET M6.04, NOTE INDICATES
 "DRYER SHALL BE INCAPACITATED IF
 BOOSTER FAN FAILS".ELECTRICAL PLANS DO
 NOT SPECIFY THIS CONDITION.
  
 PLEASE PROVIDE SUBMITTAL SHOWING THE
 CONTROL CIRCUIT INDICATING DRYER FEED
 BEING OPENED ON FAN FAILURE,
 (AUXILIARY CONTACT).
  
 2.PLEASE NOTE, PLAN SHEET M8.01
 INDICATES THE GARAGE EXHAUST SYSTEM &CO
 SENSORS SHALL BE CONNECTED TO THE
 EMERGENCY POWER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-09-17 Cont ID  
Sent By pkrauss Date 2004-09-17 Time 14:47 Rev Time 2.15
Received By pkrauss Date 2004-09-17 Time 06:43 Sent To  
Notes
2004-09-17 00:00:00DENIED:
 REFERENCE RESPONSE LETTER DATED AUGUST
 12, 2004:
 RESPONSE #2, FIRE DAMPER REMOVED FROM
 GENERATOR EXHAUST.OPENINGS ON THE
 EXTERIOR WALL ARE TO BE PROTECTED.THE
 ORIGINAL COMMENT DID NOT STATE THAT A
 FIRE DAMPER COULD NOT BE ON THE
 GENERATOR BUT ASKED FOR THE MANUFACTURER
 SUBMITTAL FOR THIS APPLICATION.
  
 PLEASE CLARIFY COMMENT ON PLAN SHEET
 M8.01. GARAGE WILL NOT BE A PART OF THE
 SMOKE CONTROL SYSTEM, THEREFOR WILL NOT
 BE TIED INTO THE EMERGENCY POWER.HOW
 WILL THE GARAGE COMPLY WITH THE
 REQUIREMENT FOR VENTILATION AS PER
 2001 FBC(M) 403.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-08-04 Cont ID  
Sent By pkrauss Date 2004-07-13 Time 13:54 Rev Time 4.50
Received By pkrauss Date 2004-07-13 Time 13:54 Sent To  
Notes
2004-07-13 00:00:00DENIED:
 SUBMITTAL BOOK DOES NOT HAVE A SUBMITTAL
 FOR THE GENERATOR OR THE BOILER.
  
 1.PLAN SHEET M2.01 GENERATOR,
 DEMENSIONS GIVEN FROM THE MIDDLE OF THE
 ALLEY IS 10" (INCHES) SHOULD READ 10'
 (FEET).
  
 2.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE GENERATOR.PLEASE NOTE PLAN
 SHEET M2.01 INDICATES A FIRE DAMPER AT
 THE RADIATOR EXHAUST.IS THIS ALLOWED
 BY THE MANUFACTURER?
  
 3.M2.01MUFFLER EXHAUST PIPE, PROVIDE
 INFORMATION FROM THE MANUFACTURER THAT
 THE LENGTH OF THE EXHAUST WILL NOT HAVE
 AN ADVERSE EFFECT ON THE GENERATOR.
  
 4.PROVIDE ELEVATION (BOP) OF THE
 MUFFLER PIPE.
  
 5.M2.01 30" X 10" INTAKE DUCT INTO THE
 A/C CLOSET & EXERCISE ROOM, DUCT
 PENETRATES A RATED WALL THEREFORE A
 FIRE DAMPER IS REQUIRED.
  
 6.M2.02 CONDENSING UNITS INSTALLED
 TIGHT TO DECK.PLEASE PROVIDE
 ELEVATION.
  
 7.REFERENCE COMMENT #10 ON THE
 PREVIOUS REVIEW;DRYER SHOULD BE
 INCAPACITATED SHOULD THE BOOSTER FAN
 FAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-03 Cont ID  
Sent By pkrauss Date 2004-04-29 Time 16:35 Rev Time 8.20
Received By pkrauss Date 2004-04-30 Time 15:35 Sent To  
Notes
2004-04-29 00:00:00DENIED:
 1.PLAN SHEET M2.01, SMOKE CONTROL
 NOTE INDICATES COMPLAINCE WITH 412.5 #1
 OF THE 2001 FBC, SUCH WINDOWS, PANELS &
 CONTROLS SHALL BE CLEARLY IDENTIFIED ON
 THE PLAN.
  
 2.2001 FBC(M) 401.5, OUTSIDE AIR
 EXHAUST AND INTAKES SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM LOT LINES.
 OPENINGS THAT ARE AJACENT TO THE STREET
 OR PUBLIC WAY SHALL BE MEASURED FROM
 THE CENTERLINE OF THE STREET.PLEASE
 NOTE, EXHAUST OPENING SHALL BE SITUATED
 AS NOT RECIRCULATE INTO THE FRESH AIR
 INTAKES.
  
 3.PLEASE CLARIFY 96" X 96" LOUVER
 LOCATED BY THE LOADING DOCK.IS IT THE
 INTENT OF THIS LOUVER SUPPLYING MAKE-UP
 AIR INTO THE GARAGE OR EXHAUST, PLEASE
 CLARIFY.2001 FBC(M) 501.3 & 401.5.1.
  
 4.CLARIFY FUNCTION OF CF0.9.
  
 5.OPENINGS TO THE ALLEY - PROTECTION
 THROUGH A RATED ASSEMBLY,PLEASE
 CLARIFY.REFERENCE 2001 FBC 705.1
 THROUGH 705.1.1.4.SEE ALSO COMMENT #5
 BY ASST FIRE MARSHALL, MIKE CARSILLO.
  
 6.PLAN SHEET M2.01 30" X 10" DUCT
 TEMINATING ABOVE THE DOOR (O.A.?),
 PLEASE CLARIFY RATING OF THIS WALL.
  
 7.PLAN SHEET M2.03, NOTE LOCATION OF
 INTAKE LOUVERS IN RELATION WITH
 SEF0.10.PER 2001 FBC(M) 401.5.1,
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM NOXIOUS OR
 HAZARDOUS CONTAMINANT.
  
 8.PLAN SHEET M2.08 & DETAIL ON PLAN
 SHEET M6.04 DRYER EXHAUST, PLAN
 INDICATES THE BOTTOM OF THE SHAFT
 TERMINATING IN THE GARAGE.PLANS DO
 NOT INDICATE CLEANOUTS AS REQUIRED PER
 2001 FBC(M) 505.3. DRYER EXHAUST SHALL
 NOT PENETRATE FIRE RATED ASSEMBLIES PER
 2001 FBC(M) 504.2.FIRE DAMPERS LOCATED
 AT THE BOTTOM OF THE SHAFT ARE NOT
 ACCEPTABLE.
  
 9.DRYER EXHAUST SHAFT SHALL COMPLY
 WITH NFPA 13 SUB-SECTION 8.14.2.
  
 10. SHEET M2.14, 10" CONDENSER WATER
 SUPPLY AND RETURN FROM ROOF.PER 2001
 FBC(M) 1206.1.1, IN A HYDRONIC SYSTEM,
 FLUID SHALL NOT ENTER THE TEE THROUGH
 THE BRANCH SIDE.
  
 10. PLAN SHEET M3.01 KEYNOTES #1 INLINE
 BOOSTER FAN, PROVIDE SUBMITTAL & UL
 LISTING.PROVIDE INFORMATION AS TO
 STEPS TAKEN SHOULD BOOSTER FAN FAIL?
  
 11. PLAN SHEET M8.01 SMOKE CONTROL
 PLEASE INDICATE IF THE ELEVATOR SHAFTS
 WILL PRESSURIZE.
  
 12. PLAN SHEET M8.02 DETAIL INDICATES
 CORRIDOR EXHAUST WHEREAS PLAN M2.01
 INDICATES COMPLIANCE BY WINDOWS AND
 PANELS (412.5 #1). PLEASE CLARIFY.
  
 13. O.A. REQUIREMENTS FOR THE CONDO
 UNITS, PROVIDE TEST DATA FROM THE
 MANUFACTURER SHOWING "ACTUALS" FOR THE
 RATE OF FILTRATION.PROVIDE THIS
 INFORMATION FOR EACH WINDOW & DOOR FOR
 EACH UNIT.
  
 14.O.A. SCHEDULE DOES NOT INDICATE
 THAT UNITS MEET THE REQUIREMENT AS
 LISTED ON THE SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 22 Status P Date 2008-01-09 Cont ID  
Sent By kstevens Date 2007-12-14 Time 09:52 Rev Time 0.00
Received By kstevens Date 2007-12-12 Time 18:52 Sent To  
Notes
2008-01-09 09:55:44REVISIONS OK - SHEETS P2.01, P2.01A, P2.02, P2.07,
 P2.08, P2.09, P2.10, P2.11, P2.12, P2.14, P2.17, P2.18,
 P4.04, P4.05, P4.05A, P4.14, P4.15, P5.01

Review Stop P PLUMBING
Rev No 21 Status F Date 2007-07-17 Cont ID  
Sent By kstevens Date 2007-07-17 Time 10:16 Rev Time 0.00
Received By kstevens Date 2007-07-17 Time 10:16 Sent To  
Notes
2007-07-17 10:23:49REVISIONDENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 ******FROM PREVIOUS DENIED REVISION REVIEW
  
 1. OK - DELETED
  
 2. SHT P2.07 KEY NOTE #2 INDICATES A 6" SANITARY LINE
 FROM THE FLOOR ABOVE. THE FLOOR ABOVE AND THE FLOOR
 BELOW DO NOT INDICATE A 6" SANITARY LINE IN THIS
 LOCATION. PLEASE CLARIFY. SECTION 104.2.1.
 ****NOT ADDRESSED/NO RESPONSE
  
 3. SHT P2.07 REVISION 3 BETWEEN COLUMNS 5 & 6 AND
 COLUMNS C & D DOES NOT INDICATE ANY CHANGE FROM
 PREVIOUS REVISION. PLEASE CLARIFY.
 ****NOT ADDRESSED/NO RESPONSE
  
 4. OK
  
 5. SHT P2.105 RWL DESIGNATIONS, (NUMBERS), HAVE BEEN
 REVISED TO BE 3" OR 4" STORM RISERS. PLEASE INDICATE
 WHY THE RWL DESIGNATIONS HAVE BEEN DELETED FROM THIS
 FLOOR. SECTION 104.2.1.
 ****NOT ADDRESSED/NO RESPONSE
  
 6. SHT P4.14 RISER DIAGRAM SHOWS A TRENCH DRAIN
 CONNECTING TO A 4" EMERGENCY DRAIN, BUT ALSO TO A 4"
 DECK DRAIN. SEPARATE SYSTEMS ARE REQUIRED PER SECTION
 1107.2.REVISION 5 FOR THIS AREA DOES NOT REFLECT THE
 FLOOR PLAN LAYOUT FOR THE DECK DRAIN & PLANTER DRAIN
 SHOWN ON SHT P2.07. THE SQUARE FOOTAGE AND DRAIN
 LAYOUTS ARE DIFFERENT ON THE FLOOR PLAN AND THE RISER
 DIAGRAM. PLEASE CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 ****RESPONSE NOTED, BUT THE BACKWATER VALVE AND SOME
 PIPING ARE STILL SHOWN ON THE RISER DIAGRAM. RISER DOES
 NOT REFLECT THE DECK PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 20 Status P Date 2007-07-17 Cont ID  
Sent By kstevens Date 2007-07-17 Time 10:15 Rev Time 0.00
Received By kstevens Date 2007-07-17 Time 10:15 Sent To  
Notes
2007-07-17 10:16:27REVISION OK--SHT P2.02A

Review Stop P PLUMBING
Rev No 19 Status F Date 2007-06-14 Cont ID  
Sent By kstevens Date 2007-06-14 Time 10:11 Rev Time 0.00
Received By kstevens Date 2007-06-14 Time 10:11 Sent To  
Notes
2007-06-14 10:38:14REVISIONDENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P2.07 SHOWS A TRENCH DRAIN CONNECTING TO A 4"
 EMERGENCY DRAIN, BUT ALSO TO A 4" DECK DRAIN. SEPARATE
 SYSTEMS ARE REQUIRED PER SECTION 1107.2 AND THE PRIMARY
 DRAIN AND THE SECONDARY DRAINS SHALL NOT CONNECT TO THE
 SAME EMERGENCY DRAIN LINE. PLEASE INDICATE THE REASON
 FOR THE BACKWATER VALVE.
  
 2. SHT P2.07 KEY NOTE #2 INDICATES A 6" SANITARY LINE
 FROM THE FLOOR ABOVE. THE FLOOR ABOVE AND THE FLOOR
 BELOW DO NOT INDICATE A 6" SANITARY LINE IN THIS
 LOCATION. PLEASE CLARIFY. SECTION 104.2.1.
  
 3. SHT P2.07 REVISION 3 BETWEEN COLUMNS 5 & 6 AND
 COLUMNS C & D DOES NOT INDICATE ANY CHANGE FROM
 PREVIOUS REVISION. PLEASE CLARIFY.
  
 4. SHT P2.10 KEY NOTES SHOW NEW NUMBERS 3 THRU 6, BUT
 ARE NOT INDICATED AS REVISIONS WITH CLOUDS OR A
 NUMBERED TRIANGLE. PLEASE INDICATE ALL REVISIONS WITH A
 CLOUD AND A NUMBERED TRIANGLE.
  
 5. SHT P2.105 RWL DESIGNATIONS, (NUMBERS), HAVE BEEN
 REVISED TO BE 3" OR 4" STORM RISERS. PLEASE INDICATE
 WHY THE RWL DESIGNATIONS HAVE BEEN DELETED FROM THIS
 FLOOR. SECTION 104.2.1.
  
 6. SHT P4.14 RISER DIAGRAM SHOWS A TRENCH DRAIN
 CONNECTING TO A 4" EMERGENCY DRAIN, BUT ALSO TO A 4"
 DECK DRAIN. SEPARATE SYSTEMS ARE REQUIRED PER SECTION
 1107.2.REVISION 5 FOR THIS AREA DOES NOT REFLECT THE
 FLOOR PLAN LAYOUT FOR THE DECK DRAIN & PLANTER DRAIN
 SHOWN ON SHT P2.07. THE SQUARE FOOTAGE AND DRAIN
 LAYOUTS ARE DIFFERENT ON THE FLOOR PLAN AND THE RISER
 DIAGRAM. PLEASE CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 18 Status P Date 2007-05-17 Cont ID  
Sent By kstevens Date 2007-05-17 Time 09:54 Rev Time 0.00
Received By kstevens Date 2007-05-17 Time 09:54 Sent To  
Notes
2007-05-17 09:57:44REVISION OK - SKETCH # SKP-1
  
 SKETCH NO: SKP-1 APPROVED W/PROVISO. THE SANITARY AND
 STORM RISER DIAGRAMS SHALL BE REVISED TO REFLECT THE
 CHANGES FROM THIS REVISION, (NO. 11).
  
 REVISION SHT P4.01 APPROVED WITH A PROVISO: A REVISION
 IS REQUIRED FOR SHT P4.01 SHOWING THE VENT FOR THE6"
 HUB DRAIN AND THE FLOOR LEVEL FOR THE HUB DRAIN SHALL
 BE INDICATED. SEE COMMENTS FROM PREVIOUS REVISION,
 (#6),REVIEWDATED 2-7-7.

Review Stop P PLUMBING
Rev No 17 Status F Date 2007-05-03 Cont ID  
Sent By kstevens Date 2007-05-03 Time 18:39 Rev Time 0.00
Received By kstevens Date 2007-05-03 Time 18:38 Sent To  
Notes
2007-05-03 18:49:07DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 SOVENT DESIGN MANUAL NO. 802
  
 1. SHT P4.02 SOVENT RISERS S/131 & S/133 AN AERATOR IS
 REQUIRED FOR THE 4" FLOOR DRAIN AT THE TOP OF THE
 STACK.DESIGN MANUAL PAGE 10 (C) AND PAGE 15 DRAWING
 2.
  
 2. SHT P4.02 SOVENT RISER S/96 HAS BEEN DELETED. THIS
 RISER IS STILL SHOWN ON THE FLOOR PLAN P216. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 3. SHT P4.04 SOVENT RISER S/110 INDICATES A REVENT FROM
 RISER S/113. SINCE RISERS S/113 AND S/114 HAVE BEEN
 CHANGED, THE REVENT DOES NOT CONNECT FROM RISER S/113.
 PLEASE CORRELATE VENTING INFORMATION. SECTION 104.2.1.
  
 4. SHT P4.04 SOVENT RISER S/111 THE PRL LINE SHALL
 CONNECT TO THE VERTICAL PORTION OF THE SOVENT STACK,
 NOT THE HORIZONTAL SECTION AS SHOWN AT THE OFFSET ON
 THE PENTHOUSE LEVEL. PAGE 18 OF THE DESIGN MANUAL NO.
 802.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 16 Status P Date 2007-05-03 Cont ID  
Sent By kstevens Date 2007-05-03 Time 18:51 Rev Time 0.00
Received By kstevens Date 2007-05-03 Time 18:51 Sent To  
Notes
2007-05-03 18:53:14REVISIONS APPROVED FOR SHEETS P2.15, P2.16, P2.18 &
 P4.03
2007-04-05 18:56:58 
  
  

Review Stop P PLUMBING
Rev No 15 Status P Date 2007-04-06 Cont ID  
Sent By kstevens Date 2007-04-06 Time 07:14 Rev Time 0.00
Received By kstevens Date 2007-04-05 Time 07:14 Sent To  
Notes
2007-04-06 07:15:10 
  
  
  
 REVISION OK - SHT P2.01A-REVISIONS REQUIRED FOR THE
 WATER RISER &STORM RISER DIAGRAMS TO REFLECT CHANGES
 INDICATED ON THIS REVISION.
  
  
  
  
  
 REVISION OK - SHT P2.02A-REVISIONS REQUIRED FOR THE
 WATER RISER, STORM RISER & GAS RISER DIAGRAMS TO
 REFLECT CHANGES INDICATED ON THIS REVISION.
  
  
  
  
  
 REVISION OK - SHT P2.03A-REVISIONS REQUIRED FOR THE
 WATER RISER, CONDENSATE RISER & STORM RISER DIAGRAMS TO
 REFLECT CHANGES INDICATED ON THIS REVISION.
  
  
  
  
  
 REVISION OK - SHT P2.04A-REVISIONS REQUIRED FOR THE
 WATER RISER, CONDENSATE RISER & STORM RISER DIAGRAMS TO
 REFLECT CHANGES INDICATED ON THIS REVISION.
  
  
  
  
  

Review Stop P PLUMBING
Rev No 14 Status F Date 2007-04-06 Cont ID  
Sent By kstevens Date 2007-04-06 Time 07:11 Rev Time 0.00
Received By kstevens Date 2007-04-06 Time 07:11 Sent To  
Notes
2007-04-06 07:13:08REVISION DENIED
 REFERENCE FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
  
 1. REVISION DENIED SHT P4.01-AN INDIRECT WASTE
 DOWNSTREAM OF STACK S/100 WHERE STACKS S/98, S/99 &
 S/100 CONNECT SHOWS A FLOOR SINK WITH NO PIPING TO THE
 BUILDING DRAIN. SECTION 104.2.1.-THE AIR ADMITTANCE
 VALVE FOR THE 6" HUB DRAIN REQUIRES A RELIEF VENT PER
 SECTION 917.3.2.-THE VENT PIPING AT RISER S/5 IS
 CONNECTING TO THE SANITARY BRANCH LINE. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 13 Status P Date 2007-03-23 Cont ID  
Sent By kstevens Date 2007-03-23 Time 10:59 Rev Time 0.00
Received By kstevens Date 2007-03-22 Time 18:52 Sent To  
Notes
2007-03-23 11:00:18REVISIONS OK - SHTS P4.05 & P4.05A

Review Stop P PLUMBING
Rev No 12 Status P Date 2007-03-12 Cont ID  
Sent By kstevens Date 2007-03-12 Time 14:28 Rev Time 0.00
Received By kstevens Date 2007-03-12 Time 14:28 Sent To  
Notes
2007-03-12 14:29:59SHT P4.05 NEW SHEET REVISION - RISER S/1 PER ENGINEER
 IS A 3" RISER, BUT 4" IS SHOWN. PROVISO FOR INSPECTIONS
 AND A REVISIONS IS REQUIRED.

Review Stop P PLUMBING
Rev No 11 Status F Date 2007-03-05 Cont ID  
Sent By kstevens Date 2007-03-05 Time 18:45 Rev Time 0.00
Received By kstevens Date 2007-03-03 Time 17:04 Sent To  
Notes
2007-03-05 18:59:43REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 SOVENT DESIGN MANUAL NO. 802
  
 1. SHT P2.15:
 A. RISERS S/9 & RWL 8 ARE MISLABELED. SECTION
 104.2.1.
 B. RISER S/12 HAS BEEN CHANGED TO S/5. CLARIFY.
 SECTION 104.2.1.
 C. REVISIONS 6,7, & 8 ARE NOT INDICATED
 D. IDENTIFY LINE BEHIND THE LAV IN UNIT B1 2B/2B JUST
 RIGHT OF COL. LINE 8/B. SECTION 104.2.1.
 E. IDENTIFY LINES, (13), AT COL LINE 9 BETWEEN COL'S A
 & B, AND COL LINE A BETWEEN COL'S 9 & 10 AND COL LINE D
 BETWEEN COL 9 & 10. SECTION 104.2.1.
  
 2. SHT P2.16:
 A. RISER S/11 AN AERATOR IS REQUIRED. PAGE 15 DRAWING
 2.
 B. RWL'S 65, 66, & 67. PLEASE INDICATE THE LOCATION OF
 THE RISERS. ONLY THE RISER DESIGNATIONS ARE
 INDICATED.SECTION 104.2.1.
 C. RISER S/59 CONNECTS WHERE? SECTION 104.2.1.
  
 3. SHT P2.17:
 A. WHICH STACK DOES THE VENT ON COL LINE 1 BETWEEN COL
 LINES H & J CONNECT TO? SECTION 104.2.1.
 B. A SECONDARY ROOF DRAIN IS REQUIRED FOR THE ROOF
 AREA TO THE RIGHT OF THE COOLING TOWERS. (3"RD 373SF).
 SECTIONS 1107.1 & 1107.2.
 C. SHOW THE SQUARE FOOTAGE OF THE AREA LEFT OF THE
 STAIRS #36 & SHOW THE LOCATION OF THE SECONDARY ROOF
 DRAIN. WILL THE AREA OF THIS ROOF SECTION DRAIN ONTO
 THE ROOF TERRACE TO THE SOUTH? PLEASE CLARIFY. TABLE
 1106.3 & SECTION 104.2.1.
 D. INDICATE THE SECONDARY ROOF DRAINS FOR ALL
 WALKWAYS. SECTIONS 1107.1 & 1107.2.
 E. CHECK THE ADDITION OF THE SQUARE FOOTAGE FOR THE
 ROOF AREA NORTH OF COL. LINE H/1. SECTION 104.2.1 &
 TABLE 1106.3..
  
 4. SHT P2.18:
 A. A DOOR INTO A PLANTER IS INDICATED RIGHT & SOUTH OF
 THE SPA. (PD 62SF). PLEASE CLARIFY. SECTION 104.2.1.
 B. A SECONDARY DRAIN IS REQUIRED AT ROOF SECTION, (3"
 RD112SF), JUST SOUTH OF STAIR #35. SECTIONS 1107.1 &
 1107.2.
 C. CHECK THE ADDITION FOR (4"RD 981SF) TO THE LEFT OF
 THE MECHANICAL ROOM. SECTION 104.2.1 & TABLE 1106.3.
 D. CHECK THE ADDITION FOR (4"RD 798SF) COL LINE B LEFT
 OF COL LINE 18. SECTION 104.2.1 & TABLE 1106.3.
 E. ROOF DRAIN SHOWN IN THE WALLS OF STAIRS #33 & #34.
 PLEASE CLARIFY. SECTION 104.2.1.
 F. CHECK THE ADDITION FOR THE ROOF DRAINS AT COL LINE
 H BEHIND STAIRS #33 & #34. SECTION 104.2.1 & TABLE
 1106.3.
  
 5. SHT P4.02:
 A. RISERS S/131 & S133 AN AERATOR IS REQUIRED FOR THE
 4"FD. PAGE 15 DRAWING 2 SOVENT DESIGN MANUAL 802.
 B. RISER S/25 IS NOT SHOWN ON SHT P4.05. PLEASE
 CLARIFY. SECTION 104.2.1.
 C. RISER S/24 DOUBLE WASH MACHINES MEZZ. LEVEL.
 INDICATE MAXIMUM 15' FROM THE CENTERLINE OF THE STACK
 TO THE CENTERLINE OF THE MOST REMOTE WASH MACHINE. PAGE
 33 DRAWING #20 SOVENT DESIGN MANUAL 802.
  
 6. SHT P403:
 A. RISER S/42 VENT REQUIRED FOR THE 6" FFD. SECTION
 901.2.1.
 B. A REVISION IS REQUIRED FOR SHT P4.01 SHOWING THE
 CONNECTION OF THE 6" FFD TO A STACK. SECTION 104.2.1.
 C. RISER S/63 2" FLOOR DRAIN CONNECTION IS NOT
 APPROVED AS SHOWN. THIS IS AN "S-TRAP". SECTION
 1002.3(5). TRAP SHALL BE CONNECTED TO THE STACK ABOVE
 THE CEILING.
 D. RISER S/79 FLOOR DRAINS CONNECTION NOT APPROVED. AN
 AERATOR IS REQUIRED PER PAGE 15 DRAWING 2 OF THE SOVENT
 DESIGN MANUAL 802.
  
 7. SHT P404:
 A. RISER 2/110 INDICATES "2 INCH VENT FROM S/113".
 S/113 & S/114 HAVE BEEN CHANGED AND NOW THE 2" VENT IS
 SHOWN CONNECTING TO RISER S/114. PLEASE CORRELATE
 RISERS. SECTION 104.2.1.
  
 8. SHT P4.05:
 A. RISER S/96 AN AERATOR IS REQUIRED FOR THE
 CONNECTION TO THE STACK FROM THE TOILET ROOMS ON THE
 ROOF. PAGE 15 DRAWING 2 SOVENT DESIGN MANUAL 802.
  
 9. SHT P405A:
 A. RISERS S/1, S/2, S/3 - A 5" VENT IS REQUIRED TO
 RISER S/1 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 B. RISERS S/5, S/6 - A 4" VENT IS REQUIRED AFTER THE
 CONNECTION TO S/5 AND THRU THE ROOF. PAGE 42 DETAIL
 A-32.
 C. RISERS S/96, S/97 - A 5" VENT IS REQUIRED THRU THE
 ROOF. THE VENT SHALL TERMINATE 6" ABOVE THE FLOOD RIM
 OF THE HIGHEST FIXTURE. PLEASE INDICATE ON THE PLANS.
 SECTION 905.4.
 D. RISERS S/38, S/43, S/44 - A 4" VENT IS REQUIRED
 AFTER S/43 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 E. RISERS S/98, S/99 - A 4" VENT IS REQUIRED AFTER
 S/98 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 F. RISERS S/59, S/60 - A 5" VENT IS REQUIRED AFTER
 S/60 & THRU THE ROOF. PAGE 42 DETAIL A-32.
 G. RISERS S/84, S/85, S/87, S/128, S/129 - A 5" VENT
 IS REQUIRED AFTER S/128 & THRU THE ROOF. PAGE 42 DETAIL
 A-32.
 H. RISERS S/110, S/112 DO NOT REFLECT THE FLOOR PLAN.
 ALSO INDICATE WHAT STACK THE KITCHEN SINK VENT COMES
 FROM. SECTION 104..2.1.
 I. RISERS S/119, S/120, S/123 - A 5" VENT IS REQUIRED
 AFTER THE CONNECTION FROM RISERS S/119 & S/120 & THRU
 THE ROOF. PAGE 42 DETAIL A-32.
  
 INFORMATIONAL: SEE RED LINE MARK-UPS ON ONE SET OF
 PLANS. THIS WILL HELP IDENTIFY AREAS OF COMMENT. PLEASE
 RETURN THIS SET TO HELP EXPEDITE THE REVIEW PROCESS
 WHEN THE REVISIONS ARE RESUBMITTED FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. ALSO PLEASE
 SUBMIT THE SHEETS WITH RED LINE REMARKS TO
 HELP EXPEDITE THE REVIEW.THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 10 Status F Date 2007-02-20 Cont ID  
Sent By pschmitz Date 2007-02-20 Time 14:44 Rev Time 0.00
Received By pschmitz Date 2007-02-20 Time 14:44 Sent To PC
Notes
2007-02-20 14:45:44RETURNED TO CONTRACTOR INCOMPLETE PLUMBING PLANS,
 ISOMETRIC REQUIRED.

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-02-07 Cont ID  
Sent By kstevens Date 2007-02-07 Time 14:58 Rev Time 0.00
Received By kstevens Date 2007-02-07 Time 14:58 Sent To  
Notes
2007-02-07 14:59:26REVISIONS OK--SHTS P2.01, P2.01A, P4.06.

Review Stop P PLUMBING
Rev No 8 Status F Date 2007-02-07 Cont ID  
Sent By kstevens Date 2007-02-07 Time 14:37 Rev Time 0.00
Received By kstevens Date 2007-02-07 Time 14:37 Sent To  
Notes
2007-02-07 14:58:09REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT P4.01 SANITARY RISER DIAGRAM. (REVISION 6), 6"
 HUB DRAIN NOT VENTED. SECTION 901.2.1. PLEASE INDICATED
 WHICH FLOOR THE 6" HUB DRAIN WILL BE LOCATED ON.--
 6" HUB DRAIN ON THE FIRST FLOOR INDICATES AN AAV VENT.
 THIS AAV VENT REQUIRES A RELIEF VENT PER SECTION
 917.3.2.--THE HORIZONTAL BLDG SANITARY DRAIN
 DOWNSTREAM OF RISER "G" IS INDICATED AS A 4" DRAIN.
 RISER "G" IS INDICATED AS 6". PER SECTION 704.2 THE
 SIZE OF THE DRAINAGE PIPE SHALL NOT BE REDUCED IN THE
 DIRECTION OF FLOW. SHOW ALL DFU'S AS THEY ACCUMULATE IN
 THE SYSTEM IN ALL REVISED DRAINAGE PIPING. TABLES
 710.1(1) & 710.1(2).-- THE 6" BUILDING DRAIN
 DOWNSTREAM OF WHERE THE BRANCH LINE TO RISER "G"
 CONNECTS TO THE BUILDING DRAIN IS INDICATED AS 6".
 AFTER ALL DFU'S ARE ADDED UP, (MAXIMUM 700 DFU@6"),I
 BELIEVE 8" WILL BE REQUIRED.--ADJUST ALL
 ACCUMULATED DFU'S DOWNSTREAM OF BOTH THE NEW 6" HUB
 DRAINS TO THE BUILDING SEWER CONNECTION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-03-15 Cont ID  
Sent By kstevens Date 2006-03-15 Time 18:27 Rev Time 0.00
Received By kstevens Date 2006-03-15 Time 18:27 Sent To  
Notes
2006-03-15 00:00:00REVISION OK SHEETS P201, P201A, P203

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-10-09 Cont ID  
Sent By pschmitz Date 2005-10-09 Time 05:36 Rev Time 0.00
Received By pschmitz Date 2005-10-09 Time 05:36 Sent To  
Notes
2005-10-09 00:00:00STORM DRAIN REVISIONS

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-07-09 Cont ID  
Sent By kstevens Date 2005-07-09 Time 07:29 Rev Time 3.25
Received By kstevens Date 2005-07-08 Time 17:53 Sent To  
Notes
2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
  
 1. ALL SHEETS, ALL REVISIONS SHALL BE
 CLOUDED AND NUMBERED. THE PRACTICE OF
 INDICATING A REVISION NUMBER FOR THE
 ENTIRE SHEET WHEN THERE ARE JUST A FEW
 CHANGES IS NOT ACCEPTABLE. SOME SHEETS
 HAVE 10 OR 12 CHANGES AND ALL SYSTEMS ON
 THE SHEET HAVE TO BE REVIEWED AND THIS
 PROCESS IS TIME CONSUMING. BECAUSE OF
 THE VOLUME OF PLANS TO BE REVIEWED, THE
 REVIEWER CAN NOT HUNT THROUGH THE ENTIRE
 SHEET AND ALL SYSTEMS TO LOCATE CHANGES.
 2. MAKE SURE ALL REVISION DESIGNATION
 NUMBERS ARE SHOWN ON THE SHEET. EXAMPLE
 SHEET NUMBERP2.02 INDICATES REVISION #6,
 BUT NO REVISION NUMBER 6 WAS LOCATED ON
 THE SHEET. THAT SHEET WILL BE DENIED
 UNTIL REVISION #6 IS SHOWN ON THE SHEET.
 SECTIONS 104.2.1 AND 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-11-06 Cont ID  
Sent By kstevens Date 2004-11-06 Time 14:31 Rev Time 2.00
Received By kstevens Date 2004-11-06 Time 14:31 Sent To  
Notes
2004-11-06 00:00:00PASSED/PROVISO
  
 AERATOR AND DEAERATOR FITTINGS SHALL BE
 APPROVED. SECTION 303

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-08-28 Cont ID  
Sent By kstevens Date 2004-08-28 Time 13:42 Rev Time 10.00
Received By kstevens Date 2004-08-27 Time 17:57 Sent To  
Notes
2004-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 CITY WPB CODE
  
 1) FROM PREVIOUS REVIEW: (15)
 SHT P4.12 DETAIL #2 DOES NOT REFLECT THE
 FLOOR PLAN AT SECOND BATHROOM (ROOM 119)
 DETAIL #4 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM (ROOM 119)
 2) SHT P4.14 STORM DRAIN COLLECTION ISO.
 SHOW THE FIRE STANDPIPE DRAINING IN THE
 STORY WATER SYSTEM. THIS IS NOT APPROVED
 PER CITY CODE SECTION 90-203(A). FIRE
 STANDPIPE DRAIN SHALL CONNECT INDIRECTLY
 TO SANITARY.
 3) ALL AERATORS AND DEAERATORS SHALL
 MEET THE STANDARDS AND SPECIFICATIONS OF
 ASTM A74-98 & A888-98 ASTM AND 301-97
 CISPI. SUBMIT INFORMATION SHOWING FITT-
 INGS HAVE MET THESE STANDARDS AS INDICA-
 TED BY A RECOGNIZED TESTING AGENCY.
 CHAPTER 14 FBC-2001.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-24 Cont ID  
Sent By kstevens Date 2004-07-24 Time 07:56 Rev Time 12.50
Received By kstevens Date 2004-07-21 Time 18:56 Sent To  
Notes
2004-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW: SHT A1.14 SEC-
 ONDARY DRAINS FOR ROOF DRAINS NOT SHOWN.
 SEE SECTIONS OF ROOF AT COLS. 5-7/B-C &
 15-16/B-C1. NO SECONDARY DRAINS SHOWN
 FOR THESE UPPER ROOFS. SECTION 104.2.1.
 2) FROM PREVIOUS REVIEW: SHTS A1.15,
 A1.16, & A1.17 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107. SHOW SF FOR EACH
 SECTION, ADDED 1/2 AREA FOR ALL VERTICAL
 WALLS INCLUDING PARAPETS, ALL SF FOR ALL
 ROOFS THAT DRAIN TO ROOF FROM ABOVE. -
 SHTS P2.17 & P2.18 SEE ROOF AREA ABOVE
 MECH/ELEVATOR/TOILET ROOMS ECT. NO INFOR
 MATION SHOWN FOR THE PRIMARY & SECONDARY
 ROOF DRAINS FOR THESE UPPER ROOFS. IF
 THESE ROOFS DRAIN TO SECTIONS OF THE
 ROOF BELOW THEN THOSE AREAS NEED TO RE-
 FLECT THE EXTRA SF. SHOW LOCATIONS OF
 THE ROOF DRAINS OF THE UPPER ROOFS.
 SECTION 104.2.1.
 5) FROM PREVIOUS REVIEW: SHT A9.1 DE-
 TAILS A,C, & E SHOW FLUSH CONTROL PER
 11-4.16.5. - ALSO NOTE THAT DETAIL "D"
 MENS TOILET AND DETAIL "F" MENS & WOMENS
 TOILETS FLUSH CONTROLS ARE ON THE WRONG
 SIDE.
 8) FROM PREVIOUS REVIEW: SHTS A9.4 THRU
 A9.15 SHOW CLEAR FLOOR SPACE FOR WATER
 CLOSETS AS REQUIRED ON PAGE 7.43 OF THE
 FHA DESIGN MANUAL.
 9) FROM PREVIOUS REVIEW: SHTS A9.4 THRU
 A9.15 WHERE APPLICABLE CORRECT THE FOLL-
 OWING ISSUES:
 B) INTERIOR ELEVATION SHALL REFLECT THE
 KEY PLAN WHEN SHOWING MEASUREMENTS FOR
 THE CENTERLINE OF THE TOILET OFF THE
 WALL OR ADJACENT FIXTURES/VANITY. SECT-
 ION 104.2.1.
 C) UNITS WITH SPECIFICATION "B" SHOW
 CLEAR FLOOR SPACE IN EACH BATHROOM. IN-
 DICATE WHICH BATHROOM WILL COMPLY AND
 SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED
 FIXTURES. FHA DESIGN MANUAL SEC. 104.2.1
 D) THE 18" FROM THE CENTERLINE OF THE
 W/C TO THE WALL IS AN ABSOLUTE MEASURE-
 MENT. SEE PAGE 6.5 FHA DESIGN MANUAL.
 E) SOME UNITS DO NOT SHOW AN ELEVETION
 FOR THE WATER CLOSET. IF THE BATHROOM
 DESIGNATED TO COMPLY DOES NOT HAVE AN
 ELEVATION FOR THE W/C, PLEASE SUBMIT THE
 ELEVATION. SECTION 104.2.1.
 12) NEW COMMENTS FROM RESPONSE: THE
 FOLLOWING SANITARY RISERS SHOWN ON THE
 SANITARY COLLECTION ISOMETRIC WERE NOT
 FOUND ON RISER SHEETS. S/124, S/125,
 S/126, S/127, S/128, S/129, & S/130. -
 THE FOLLOWING RISERS WERE NOT FOUND ON
 THE SANT. COLLECTION ISOMETRIC. S/48, &
 S/76. - S/75RISER SHOWS 10 DFU'S ON
 P4.03, BUT ON SHT P4.01 IT SHOWS 35 DFU
 - SANT. RISER "D", RISER S/70 SHOWS NO
 DFU'S ADD TO SYSTEM (100) - RISER "B",
 ARE THERE 2 S/29'S ? - RECALCULATE DFU'S
 ON RISER "G" - PLEASE CLARIFY AND CORRE-
 LATE PLANS. SECTION 104.2.1.
 15) FROM PREVIOUS REVIEW: SHT P4.12,
 DETAIL #2 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM. (ROOM 119).
 DETAIL #4 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM. (ROOM 119).
 16) FROM PREVIOUS REVIEW: SHT S P4.13 &
 P4.14 STORM COLLECTION ISOMETRIC, INDIC-
 ATE PIPE SIZE AND SHOW SF AS THEY ACCUM-
 ULATE IN THE SYSTEM. TABLES 1106.2 AND
 1106.3. CHECK SIZINT AT "K" RISER. DOES
 NOT CORRELATE.
 19) FROM PREVIOUS REVIEW: TRASH CHUTE
 WASH DOWN LINES ARE NOT SHOWN. SECTION
 104.2.1.
 20) FROM PREVIOUS REVIEW: SWIMMING POOL
 LINE NOT SHOWN. SECTION 104.2.1.
 21) FROM PREVIOUS REVIEW: THE FOLLOWING
 INFORMATION IS REQUIRED FOR APPLICATION
 FOR SEPARATE GAS PERMIT.
 F) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA-54, NFPA-58, AND THE
 FBC-2001 FUEL GAS CODE SEC. 402.2
 ***NEW COMMENT - MANUF. SHEETS REQUIRED
 FOR PRESSURE REGULATORS FROM 2LB SYSTEM
 TO LOW PRESSURE REQUIRED AT EACH GAS
 FIXTURE. SECTION 410.
 24) FROM PREVIOUS REVIEW: SHOW APPORVAL
 FOR SOVENT SYSTEM BY AN APPROVED TESTING
 AGENCY. SHOW TESTING FOR FLOW RATES.
 SECTION 104.2.1.
 25) FROM PREVIOUS REVIEW: MANY SANITARY
 RISERS DO NOT COMPLY WITH REQUIREMENTS
 INDICATED ON SHT. P5.02. SECTION 104.2.1
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-27 Cont ID  
Sent By kstevens Date 2004-04-24 Time 12:31 Rev Time 23.00
Received By kstevens Date 2004-04-24 Time 12:31 Sent To  
Notes
2004-04-24 00:00:00PLAN REVIEW DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1) SHT A1.14 SECONDARY DRAINS FOR ROOF
 DRAINS AND FOR FLOOR DRAINS AT TERRACES
 ARE NOT SHOWN. PLEASE SHOW ALL SECONDARY
 DRAINS. SECTION 104.2.1
 2) SHTS A1.15, A1.16, & A1.17 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106, AND 1107
 WITH ALL SUBSECTIONS. SHOW SQUARE FEET
 FOR EACH SECTION, ADDED 1/2 AREA FOR ALL
 VERTICAL WALLS INCLUDING PARAPETS, ALL
 SQUARE FEET FOR ALL ROOFS THAT DRAIN TO
 ROOF FROM ABOVE. SHOW LOCATION OF ALL
 SECONDARY ROOF DRAINS.
 3) SHT A1.17 ROOF SCUPPER DETAIL #7 AND
 DETAIL #4 NO HEIGHT AND WIDTH SHOWN ON
 DETAILS.
 4) SHT A9.0 BACKING NOT SHOWN FOR THE
 FOOT OF THE TUB, AND NO BACKING SHOWN
 FOR THE SHOWER.
 5) SHT A9.1 DETAILS A,C, & E INDICATE
 THE HEIGHT FOR W/C, & LAV. SHOW FLUSH
 CONTROL PER CHAPTER 11, SECTIONS 4.16.3,
 4.19.2, AND 4.16.5.
 6) SHT A9.1 DETAILS B, D, & F INDICATE
 MEASUREMENT TO CENTERLINE OF FIXTURES
 OFF WALL FOR WATER CLOSET AND LAV.
 7) SHTS A9.2 THRU A9.35 ALL LOFTS, INDI-
 CATE MEASUREMENTS TO CENTERLINE OF FIX-
 TURES FOR W/C AND LAV OFF WALL FOR ACC-
 ESSIBLE TOILET ROOMS, HEIGHT OF LAVS AND
 W/C, FLUSH CONTROL. (SEE COMMENT #5).
 8) SHTS A9.4 THRU A9.15 SHOW CLEAR FLOOR
 SPACE FOR ALL REQUIRED BATHROOM FIXTURES
 PER PAGES 7.43, 7.47, & 7.53 OF THE FHA
 DESIGN MANUAL.
 9) SHTS A9.4 THRU A9.15 WHERE APPLICABLE
 CORRECT THE FOLLOWING ISSUES:
 A) ALL LAVS WITH PARALLEL APPROACH, THE
 LAV SHALL BE CENTERED ON THE 48" SIDE OF
 THE CLEAR FLOOR SPACE AND SHALL BE A MIN
 OF 2' OFF WALL OR 30" OFF ADJACENT FIX-
 TURE.
 B) INTERIOR ELEVATION SHALL REFLECT THE
 KEY PLAN WHEN SHOWING MEASUREMENTS FOR
 THE CENTERLINE OF THE TOILET OFF THE
 WALL OR ADJACENT FIXTURES/VANITY.
 C) UNITS WITH SPECIFICATION "B" SHOW
 CLEAR FLOOR SPACE IN EACH BATHROOM. IN-
 DICATE WHICH BATHROOM WILL COMPLY AND
 SHOW CLEAR FLOOR SPACE FOR ALL REQUIRED
 FIXTURES.
 D) THE 18" FROM THE CENTERLINE OF THE
 W/C TO THE WALL IS AN ABSOLUTE MEASUR-
 MENT. SEE PAGE 6.5
 E) SOME UNITS DO NOT SHOW AN ELEVATION
 FOR THE WATER CLOSET. IF THE BATHROOM
 TO BE DESIGNATED TO COMPLY DOES NOT HAVE
 AN ELEVATION FOR THE W/C, PLEASE SUBMIT
 THE ELEVATION.
 10) ALL PLUMBING SHEETS, THE CERTIFICATE
 OF AUTHROIZATION IS REQUIRED ON THE
 TITLE BLOCK PER FAC 61G15-23.002(2) -
 FS 471.025.
 11) SHTS P2.01 & P2.02 WATER DISTRIBUT-
 ION LINE SHOWS THE PUMP PRESSURE OUT OF
 THE DOMESTIC PUMP, BUT THEN DROPS DOWN
 TO STREET PRESSURE AND THEN BACK UP TO
 PUMP PRESSURE. PLEASE CLARIFY. SECTION
 104.2.1
 12) SHT P4.01 SANT. COLLECTION ISOMETRIC
 SHOW PIPE SIZE AND DFU'S AS THEY ACCUMU-
 LATE IN THE SYSTEM.
 13) SHT P4.08 DETAIL #1 SHOWS 2 WASH
 MACHINES. PLEASE CLARIFY. SEC 104.2.1.
 14) NO WATER ISOMETRICS FOR UNITS "B4",
 "B7", OR "TH-1" (L-8).
 15) SHT P4.12:
 DETAIL #1 NO WATER SUPPLY SHOWN FOR LAVS
 OR TUB/SHOWER.
 DETAIL #2 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM.
 DETAIL #4 DOES NOT REFLECT THE FLOOR
 PLAN AT SECOND BATHROOM.
 16) SHTS P4.13 AND P4.14 STORM COLLECT-
 ION ISOMETRIC, INDICATE PIPE SIZE AND
 SHOW SQUARE FEET AS THEY ACCUMULATE IN
 THE SYSYTE. TABLES 1106.2 AND 1106.3.
 17) SUBMIT CONDENSATE RISER DIAGRAMS AND
 A CONDENSATE COLLECTION ISOMETRIC SHOW-
 ING ALL PIPE SIZES AND TERMINATION POINT
 FOR CONDENSATE. SECTION 104.2.1
 18) SHTS P2.13 & P2.14 SHOW WATER DIST.
 TO BE IN THE CEILING OF THE 7TH FLOOR.
 SHT P407 INDICATES WATER DIST. PIPING TO
 BE IN 8TH FLOOR CEILING. PLEASE CLARIFY.
 SECTION 104.2.1
 19) TRASH CHUTE WASH DOWN LINE ARE NOT
 SHOWN. BACKFLOW PROTECTION REQUIRED FOR
 THESE LINES.
 20) SWIMMING POOL FILL LINE NOT SHOW.
 BACKFLOW PROTECTION REQUIRED FOR THIS
 LINE.
 21) BACKFLOW PROTECTION REQUIRED FOR
 WATER SUPPLY LINE TO COOLING TOWER.
 SUBMIT DETAIL SHOWING PROTECTION.
 22) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR APPLICATION FOR SEPARATE GAS PER-
 MIT REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G) IF WELDED PIPE PRIOR TO ISSUING GAS
 PERMIT, THE WELDER SHALL PROVIDE A PICT-
 URE IDENTIFICATION, WELDING CERTIFICAT-
 ION AND WELDING PROCEDURE.
 23) SUBMIT DESIGN MANUAL 101 REFERENCED
 ON SHEET P5.02. SECTION 104.2.1
 24) SHOW APPROVAL FOR SYSTEM BY AN APP-
 ROVED TESTING AGENCY. SHOW TESTING FOR
 FLOW RATES. SECTION 104.2.1.2
 25) MANY RISERS DO NOT COMPLY WITH THE
 REQUIREMENTS INDICATED ON SHEET P5.08
 SECTION 104.2.1
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A SET
 OF PLUMBING PLANS HAS BEEN HIGHLIGHTED
 DURING REVIEW AND IF POSSIBLE THIS SET
 SHOULD BE RETURNED. THIS WILL HELP TO
 EXPIDITE THE NEXT PLUMBING REVIEW. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 12 Status P Date 2007-11-05 Cont ID  
Sent By mflis Date 2007-11-05 Time 13:37 Rev Time 0.00
Received By mflis Date 2007-11-05 Time 13:37 Sent To E
Notes
2007-11-05 13:39:02ZONING REVIEW: PASSED
  
 REVISION TO SITE PLAN / FIRST FLOOR PLAN FOR PARKING
  
 * RELOCATED GROUND FLOOR ADA-ACCESSIBLE PARKING
 * ADDITIONAL ADA PARKING PROVIDED ON UPPER FLOORS
 * TWO (2) ADA PARKING SPACES REQUIRED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 11 Status P Date 2007-09-13 Cont ID  
Sent By mflis Date 2007-09-13 Time 09:25 Rev Time 0.00
Received By mflis Date 2007-09-13 Time 09:25 Sent To  
Notes
2007-09-13 09:26:21ZONING REVIEW: PASSED
  
 * ADA HANDICAP PARKING REVISIONS: RELOCATE PARKING - 1
 ADA VAN-ACCESSIBLE @ GROUND LEVEL; 1 ADA ACCESSIBLE
 SECOND LEVEL PARKING
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 10 Status F Date 2007-09-04 Cont ID  
Sent By mflis Date 2007-09-04 Time 09:23 Rev Time 0.00
Received By mflis Date 2007-09-04 Time 09:23 Sent To  
Notes
2007-09-04 09:24:44ZONING REVIEW: FAILED
  
 * SEE PREVIOUS COMMENTS: ADA SPACES SHALL BE 12'-0"
 WIDE WITH 5'-0" ACCESS AISLE. REVISED DRAWINGS DO NOT
 SHOW THIS.
 * CONFIRM NUMBER OF ACCESSIBLE PARKING SPACES REQUIRED
 FOR GROUND FLOOR LIVE-WORK IS (2)
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 9 Status F Date 2007-08-13 Cont ID  
Sent By mflis Date 2007-08-13 Time 18:38 Rev Time 0.00
Received By mflis Date 2007-08-13 Time 18:38 Sent To  
Notes
2007-08-13 18:39:55ZONING REVIEW: FAILED
  
 * PARKING TO BE REVISED AND RELOCATED; MUST PROVIDE
 12'-0" ADA PARKING SPACES WITH 5'-0" WIDE AISLE.
 * MAX SLOPE PERMITTED IS 1:50 IN ANY DIRECTION FOR
 AISLE.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 8 Status N Date 2007-02-26 Cont ID  
Sent By astelly Date 2007-02-26 Time 14:18 Rev Time 0.00
Received By astelly Date 2007-02-26 Time 14:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 7 Status N Date 2007-01-29 Cont ID  
Sent By mflis Date 2007-01-29 Time 13:51 Rev Time 0.00
Received By mflis Date 2007-01-29 Time 13:51 Sent To  
Notes
2007-01-29 13:57:56ZONING REVIEW: NOT REQUIRED
  
 FP AND E REVISION SHEETS ONLY. NO OTHER ARCHITECTURAL
 CHANGES REVIEWED OR APPROVED.
  
 MATT FLIS 822-1445

Review Stop Z ZONING
Rev No 6 Status F Date 2006-11-20 Cont ID  
Sent By astelly Date 2006-11-20 Time 09:46 Rev Time 0.00
Received By astelly Date 2006-11-20 Time 09:46 Sent To  
Notes
2006-11-20 09:52:04PLEASE SUBMIT THESE DRAWINGS TO THE ENGINEERING
 DEPARTMENT FOR REVIEW. THE ZONING REVIEW WILL FOLLOW
 ENGINEERING .

Review Stop Z ZONING
Rev No 5 Status P Date 2005-06-29 Cont ID  
Sent By aaponte Date 2005-06-29 Time 15:01 Rev Time 0.00
Received By aaponte Date 2005-06-24 Time 15:05 Sent To  
Notes
2005-06-29 00:00:00PROVISO:
 1. TREES ON QUADRILLE BOULEVARD SHALL BE
 LIVE OAKS SUB SPECIE HIGH-RISE.
 2. REPLACE LIVE OAKS ON EVERNIA STREET
 BY DAHOON HOLY.

Review Stop Z ZONING
Rev No 4 Status P Date 2004-11-12 Cont ID  
Sent By aaponte Date 2004-11-12 Time 12:11 Rev Time 0.00
Received By aaponte Date 2004-11-12 Time 12:11 Sent To  
Notes
2004-11-12 00:00:00PROVISO:
 CO SHALL NOT BE ISSUED UNITL OPEN SPACE
 IS COMPLETED AND PIECE OF ART IS PLACE
 ON THE OPEN SPACE.

Review Stop Z ZONING
Rev No 3 Status F Date 2004-09-17 Cont ID  
Sent By rbrown Date 2004-11-09 Time 11:36 Rev Time 0.00
Received By aaponte Date 2004-09-17 Time 17:04 Sent To  
Notes
2004-09-17 00:00:001. MEZZANINE WINDOWS ON LOFT-8 ARE NOT
 DEPICTED ON THE FLOOR PLAN.
 2.WEST ELEVATION (A4-3) NEEDS THE SAME
 BASE LINE THAN NORTH AND EAST ELEVATIONS
 3.ALUMINIUM LOVERS SHOULD BE DESIGN AS
 PART OF THE OVERALL ELEVATION DESIGN
 A4-2 SOUTH ELEVATION.
 PROVISO: WINDOW TINT SHALL BE CLEAR OR
 LIGHTLY TINTED. PLEASE CONFIRM YOU ARE
 IN COMPLIANCE WITH THIS REGULATION.

Review Stop Z ZONING
Rev No 2 Status F Date 2004-07-27 Cont ID  
Sent By aaponte Date 2004-07-26 Time 16:32 Rev Time 0.00
Received By aaponte Date 2004-07-26 Time 15:42 Sent To  
Notes
2004-07-27 00:00:001.ACCORDING WITH THE ACHITECTURAL DESIGN
 GUIDELINES, LIVE/WORK UNITS AT GROUND
 LEVEL HAVE TO HAVE A MINIMUM TWO FEET
 KICK PLATE UNDER THE STOREFRONT AND
 THE HUNG WINDOWS.
 2.PARALLEL PARKING SPACES SHALL BE 22'
 LONG AND END PARKING SPACES CAN BE 20'
 LONG. PLEASE ADJUST TREE SPACING
 ACCORDINGLY.
 3.LANDSCAPE DRAWINGS ARE NOT UPDATED TO
 REFLECT NEW INFORMATION ON SHEET A1-15.
 4. REMOVE CLUSTER PLANTING OF PALMS ON
 CORNER OF DIXIE AND EVERNIA. REPLACE
 WITH HARDSCAPE AND ADDITIONAL SHADE TREE
 5. IN RELATION WITH THE PUBLIC OPEN
 SPACE, THE DRAWINGS SHOULD DEPICT THE
 LOCATION OF THE DRINKING FOUNTAIN AS
 REQUIRED BY THE PUBLIC OPEN SPACE DESIGN
 GUIDELINES.
 6. MEZZANINE WINDOWS ON LOFT-8 ARE NOT
 DEPICTED ON THE FLOOR PLAN.
 7.COLUMNS AT THE BASE SEEM RANDOMLY
 PLACED, PLEASE REVISE.
 PROVISO: 1. ART PIECE IN THE PUBLIC
 OPEN SPACE MUST BE IN PLACE PRIOR TO CO.
 PLEASE CONTACT J. GOLDBERG FOR APPROVAL.
 2. WINDOW TINT SHALL BE CLEAR OR LIGHTLY
 TINTED. OPAQUE, REFLECTIVE OR DARK
 TINTING IS NOT PERMITTED.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By aaponte Date 2004-04-20 Time 08:45 Rev Time 2.00
Received By aaponte Date 2004-04-20 Time 08:45 Sent To  
Notes
2004-04-20 00:00:001. PURSUANT TO ART. IV SECTION 94-113(A)
 (6) STORIES AT SIDEWALK LEVEL SHALL BE
 NO LESS THAN 12 FEET FROM FINISH FLOOR
 TO FINISH CEILING AND SUCH STORIES SHALL
 NOT EXCEED 20 FEET IN HEIGHT FROM
 FINISH FLOOR TO FINISH FLOOR. THE FIRST
 FLOOR UNITS ON DIXIE HIGHWAY EXCEED THE
 MAXIMUM HEIGHT ALLOWED FINISHED FLOOR
 TO FINISHED FLOOR.
 2.PURSUANT TO ART. IV SECTION 94-113(B)
 (7), PLEASE CONFIRM THAT THE BUILDING
 SETBACK ALLOWS A SIDEWALK OF 8 FEET FOR
 QUADRILLE BOULEVARD.
 3. IN RELATIN WITH THE ARCHITECTURAL
 DESIGN GUIDELINES, ARTICLE IV SECTION 94
 -107(F)(1), WE HAVE THE FOLLOWING
 COMMENTS:
 - PLEASE REVIEW THE ARTICULATION BETWEEN
 THE ALLEY OPENING ON THE WEST ELEVATION
 AND THE BALCONIES IN THE UPPER FLOOR,
 THE OPENING SHOULD BE CENTERED TO BE
 CONSISTENT WITH THE ELEVATION DESIGN.
 - PLEASE REVIEW THE ARTICULATION BETWEEN
 THE NON-STRUCTURAL COLUMNS ON THE FIRST
 FLOOR AND THE BALCONIES ON THE ENDS ON
 THE SECOND FLOOR (A4-0)
 - A NON-STRUCTURAL COLUMN IS MISSING ON
 THE ENDS OF THE NORTH ELEVATION.
 4. IN RELATION WITH THE ROOF TERRACE WE
 HAVE THE FOLLOWING COMMENTS:
 - PURSUANT TO ARTICLE IV SECTION 94-107
 (5)(E), THE OVERALL ROOF TERRACE HAS TO
 BE 15% LANDSCAPE, AND THE PRIVATE
 TERRACES SHALL BE INCLUDED IN THE AREA
 CALCULATION. PLEASE PROVIDE INFORMATION
 TO CONFIRM YOU ARE IN COMPLIANCE WITH
 THIS REQUIREMENT.
 5. IN RELATION WITH THE PUBLIC OPEN
 SPACE, THE DRAWINGS SHOULD DEPICT THE
 LOCATION OF THE DRINKING FOUNTAIN AS
 REQUIRED BY THE PUBLIC OPEN SPACE DESIGN
 GUIDELINES.