Plan Review Details - Permit 04031569
Plan Review Stops For Permit 04031569
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-10 Cont ID  
Sent By lsmith Date 2004-05-10 Time 15:45 Rev Time 1.00
Received By lsmith Date 2004-05-10 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-03 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 14:03 Rev Time 2.50
Received By lsmith Date 2004-05-03 Time 14:05 Sent To  
Notes
2004-05-03 00:00:00BUILDING PLANS REVIEW FAILED:
  
 1.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. BEFORE A PERMIT CAN BE ISSUED IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE PERMIT SETS OF PLANS MUST BE
 STAMPEDBY THAT OFFICE AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 3. A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN B ISSUED.
  
 THE VALUE OF THE HOUSE HAS BEEN UPGRADED
 AND ADDITIONAL FEES OF $554.37 ARE DUE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 14:03 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 14:03 Sent To B
Notes
2004-05-08 00:00:00********* REVISION/ PROVISO ********
  
 1)NOTE: PLEASE CORRELATE PANELS/SCHEDULE
 S AND RISER DIAGRAM. POOL PANEL IS STILL
 MISSING FROM RISER.??
 PANELS ON PANEL SCHEDULES ARE STILL
 SHOWN AS MLO?, YET RISER SHOWS MCB.
  
 2)NOTE: PLEASE SEE MISSING RECEPT IN
 BEDRM #4. 210.52 2' OF WALL.
  
 3)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE REVISE PLANS FOR ABOVE COMMENTS
 BEFORE ROUGH ELECTRICAL INSPECTION.
 SUBMIT FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-05-07 Time 10:48 Rev Time 0.50
Received By dpalmer Date 2004-04-12 Time 16:09 Sent To M
Notes
2004-04-12 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE RISER DOES NOT
 INDICATE ANY MAINS? PANELS ARE SHOWN AS
 MLO. RISER SHOWS METER ONLY, PLEASE
 SHOW OCP.
  
 2)NOTE: PLEASE SEE PANEL 'B' SHOWS A
 POOL PANEL BUT IS NOT SHOWN ON RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-06-17 Time 10:17 Rev Time 0.00
Received By csiegber Date 2004-06-17 Time 10:16 Sent To P
Notes
2004-06-17 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 10:48 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 10:48 Sent To E
Notes
2004-05-07 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-05-03 Cont ID  
Sent By mmclean Date 2004-05-07 Time 08:47 Rev Time 0.00
Received By csiegber Date 2004-03-30 Time 09:42 Sent To  
Notes
2004-04-01 00:00:00TO Z
 4/01/2004TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-13 Cont ID  
Sent By dpalmer Date 2004-04-12 Time 16:09 Rev Time 0.35
Received By pkrauss Date 2004-04-13 Time 14:10 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-01 Cont ID  
Sent By jleech Date 2004-07-01 Time 19:20 Rev Time 0.50
Received By jleech Date 2004-07-01 Time 19:20 Sent To  
Notes
2004-07-01 00:00:00PLUMBING RISER DIAGRAM AS BUILTS

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-06-17 Time 10:17 Rev Time 0.33
Received By jleech Date 2004-04-15 Time 16:50 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-01 Cont ID  
Sent By alange Date 2004-03-30 Time 09:42 Rev Time 0.00
Received By mmclean Date 2004-04-01 Time 10:57 Sent To I
Notes
***NONE***