Plan Review Details - Permit 04031266
Plan Review Stops For Permit 04031266
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-04-05 Cont ID  
Sent By kstevens Date 2004-04-02 Time 14:16 Rev Time 0.50
Received By lsmith Date 2004-04-05 Time 14:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-31 Cont ID  
Sent By lsmith Date 2004-03-30 Time 07:51 Rev Time 0.33
Received By btrobaug Date 2004-03-31 Time 10:53 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 12:02 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 12:02 Sent To P
Notes
2004-04-12 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-30 Cont ID  
Sent By lsmith Date 2004-03-30 Time 07:51 Rev Time 0.00
Received By lsmith Date 2004-03-30 Time 07:51 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-25 Cont ID  
Sent By mmclean Date 2004-03-29 Time 16:01 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 11:18 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-04-23 Cont ID  
Sent By kstevens Date 2004-04-22 Time 18:52 Rev Time 0.50
Received By kstevens Date 2004-04-22 Time 17:12 Sent To  
Notes
2004-04-23 00:00:00PASSED/PROVISO
  
 FIELD INSPECTOR SHALL VERIFY LISTING ON
 POOL HEATER. - EXTERNAL HARTFORD LOOP IS
 REQUIRED FOR WATER RETENTION REQUIRED BY
 FBC-2001 SECTION 424.2.14.2

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-16 Cont ID  
Sent By kstevens Date 2004-04-16 Time 17:01 Rev Time 1.00
Received By kstevens Date 2004-04-16 Time 17:01 Sent To  
Notes
2004-04-16 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PIPING ISOMETRIC ON SHEET 1 0F 6 IS
 SIGNED & SEALED BY AN ENGINEER. ANY
 CHANGES TO A SIGNED AND SEALED SET OF
 PLANS SHALL BE SIGNED AND SEALED BY THE
 ENGINEER OF RECORD.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL) - RESPONSE
 NOTED, BUT MANUF. SHEETS SHALL BE SUB-
 MITTED FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-04-12 Time 12:02 Rev Time 0.50
Received By kstevens Date 2004-04-02 Time 14:16 Sent To B
Notes
2004-04-02 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) FILTER AND PIPING ISOMETRIC ON SHEET
 1 OF 6 DOES NOT SHOW A POOL HEATER, BUT
 THERE IS A SHEET ATTACHED SHOWING A
 RHEEM HEAT PUMP. PLEASE CLAIRFY IF THERE
 IS A POOL HEATER AND IF SO THE ISOMETRIC
 SHALL REFLECT THIS. - ALSO IF THERE IS A
 HEAT PUMP SEE THE FOLLOWING COMMENTS.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-29 Cont ID  
Sent By csiegber Date 2004-03-25 Time 11:18 Rev Time 0.00
Received By mmclean Date 2004-03-29 Time 16:01 Sent To I
Notes
***NONE***