Plan Review Details - Permit 04031202
Plan Review Stops For Permit 04031202
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-30 Cont ID  
Sent By alange Date 2004-04-30 Time 11:07 Rev Time 0.66
Received By alange Date 2004-04-30 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-26 Cont ID  
Sent By jleahy Date 2004-04-29 Time 15:06 Rev Time 0.66
Received By alange Date 2004-04-26 Time 08:37 Sent To  
Notes
2004-04-26 00:00:00DENIED
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PRODUCT APPROVAL FOR PREMDOR ENTRY
 DOOR NOT LISTED ON DCA PRODUCT APPROVAL
 WEB SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SEPERATE ROOFING PERMIT REQUIRED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-29 Cont ID  
Sent By alange Date 2004-04-30 Time 11:07 Rev Time 0.45
Received By jleahy Date 2004-04-29 Time 15:04 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-29 Time 08:50 Rev Time 0.50
Received By dpalmer Date 2004-04-20 Time 17:46 Sent To B
Notes
2004-04-20 00:00:00************ UNSAT ******************
  
 1)NOTE: PLANS CONTAINING A TITLE BLOCK
 FROM AN ARCH MUST BE SIGNED, DATED AND
 SEALED UNDER FS 481.221
  
 2)NOTE: PLEASE PROVIDE LOAD CALCULATION
 ON EXSITING 60A SERVICE SHOWN.215.5
 220
  
 3)NOTE: PLEASE INDICATE DISC MEANS AT
 DEATCHED BLDG PER 225.31
 GROUNDING ELECTRODE SYSTEM AT DEATCHED
 BLDG TO INCLUDE A MIN OF FOOTER STEEL,
 AND ANY METALLIC WATER PIPE? 250.50,
 250.32
  
 4)NOTE: PLEASE SEE O/B DISCLOSURE
 STATEMENT WHICH IS IN PACKAGE.
 SIGNATURE FROM OWNER IS NOT ORIGINAL,
 YET IS NOTORIZED?
  
 5)NOTE: PLEASE SEE ELECTRICAL PLAN
 SHOWS ELECTRICAL FOR GARAGE COMING FROM
 AN EXISTING 60A ELECTRICAL SERVICE AT
 AN APT. PLEASE SEE ALL OTHER PLANS DO
 NOT CORRELATE.
 PLEASE SUBMIT A COMPLETED RISER DIAGRAM
 FOR EXSITING AND NEW BEING ADDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-29 Cont ID  
Sent By csiegber Date 2004-04-29 Time 08:50 Rev Time 0.00
Received By csiegber Date 2004-04-29 Time 08:50 Sent To E
Notes
2004-04-29 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-20 Time 10:24 Rev Time 0.00
Received By alange Date 2004-04-20 Time 10:24 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 11:37 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 11:37 Sent To Z
Notes
2004-04-12 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 09:39 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 09:39 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-20 Cont ID  
Sent By aaponte Date 2004-04-20 Time 09:28 Rev Time 0.00
Received By aaponte Date 2004-04-20 Time 09:28 Sent To  
Notes
2004-04-20 00:00:00PROVISO: CONFIRM SETBACKS FROM
 CENTERLINE OF ALLEY

Review Stop Z ZONING
Rev No 1 Status F Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-12 Time 11:37 Rev Time 0.00
Received By aaponte Date 2004-04-01 Time 13:59 Sent To  
Notes
2004-04-01 00:00:00THE PROJECT REQUIRES UNITY OF TITLE.
 THE DRAWINGS ARE NOT PROPERLY
 DIMENSIONED TO CONFIRM THEADDITION IS
 COMPLYING WITH THE REQUIRED REAR SETBACK