Plan Review Details - Permit 04031091
Plan Review Stops For Permit 04031091
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-10 Cont ID  
Sent By jwitmer Date 2004-06-10 Time 08:04 Rev Time 2.22
Received By jwitmer Date 2004-06-10 Time 07:34 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-13 Cont ID  
Sent By csiegber Date 2004-06-01 Time 11:19 Rev Time 1.00
Received By jwitmer Date 2004-05-13 Time 12:52 Sent To  
Notes
2004-05-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031091
 ADD: 801 VILLAGE BLVD/ 307
 CONT: STORETECH INC
 TEL: (561)901-1937
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 A) THEPLANS INDICATE A EXPOSURE "C",
 THE BUILDING IS LOCATED IN A "B" WIND
 EXPOSURE, YOU MAY DESIGN TO THE MORE
 RESTRICTIVE "C" ZONE BUT THE MULTIPLIER
 OF 1.21 WILL BE USED FOR WIND PRESSURES.
  
 NOTE NO PRODUCT APPROVALS HAVE BEEN SUB-
 MITTED 1ST OR 2ND REVIEW!!
  
 B) THE INTERNAL PRESSURE COEFFICIENT
 IS ALSO INCORRECT, IT SHOULD BE .18 FOR
 ENCLOSED STRUCTURES.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED STOREFRONT WINDOWS
 B) STOREFRONT DOORS
 C) STORM SHUTTERES REQUIRED IF GLAZING
 HAS NOT MET LARGE MISSLE IMPACT
 TESTING.
  
 3) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 5) ******REMOVE ALL VOIDED SHEETS FROM
 PLANS******* RETAIN (1) SET OF VOIDED
 PAGES.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-09 Cont ID  
Sent By jwitmer Date 2004-04-09 Time 09:49 Rev Time 0.00
Received By jwitmer Date 2004-04-09 Time 10:12 Sent To  
Notes
2004-04-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031091
 ADD: 801 VILLAGE BLVD# 307
 CONT: RCC ASSOCIATES
 TEL: (954)325-7273
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED STOREFRONT WINDOWS
 B) STOREFRONT SWING DOORS
 C) STORM SHUTTERS IF GLAZING NOT TESTED
 FOR LARGE MISSLE IMPACT.
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 5) CHANGES IN LEVEL 11-4.5.2 CHANGES IN
 LEVEL UP TO 1/4 IN. MAY BE VERTICAL AND
 WITHOUT EDGE TREATMENT. CHANGES IN LEVEL
 BETWEEN 1/4IN AND 1/2IN SHALL BE BEVELED
 WITH A SLOPE NO GREATER THAN 1:2.
 CHANGES GREATER THAN 1/2IN SHALL BE
 ACCOMPLISHED BY MEANS OF A RAMP THAT
 COMPLIES WITH 11-4.7 OR 11-4.8.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 15:42 Rev Time 0.50
Received By dpalmer Date 2004-05-08 Time 15:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-14 Cont ID  
Sent By dpalmer Date 2004-04-14 Time 07:19 Rev Time 0.75
Received By dpalmer Date 2004-04-14 Time 07:19 Sent To  
Notes
2004-04-14 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQ'D ON TITLE BLOCK FOR
 ENGINEER AND ENGINEERING FIRM.
 PLEASE INCLUDE NAME(S) AND ALL LICENSE
 #'S AS REQ'D INCLUDING CA#.
 PLEASE BE SURE RAISED SEALED IS CLEAR
 AND VISABLE.PLEASE SEE PLUMB REVIEW FOR
 THIS COMMENTALSO.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE "B"
 INDICATES SHOW WINDOW AND SIGN CIRCUIT
 AS SEPARATE YET, PLANS INDICATE BOTH ON
 CIRCUIT B-9? PLEASE CORRELATE.
  
 3)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE REQ'D BY
 OTHER TRADES TO VERIFY PREVIOUS.
 PLEASE SEE OTHER REVIEWERS NOTES.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 5)NOTE: PLEAS VERIFY LOCATION OF NEW
 MAIN DISC? PLEASE ALSO VERIFY WHERE
 NEW MAIN IS BEING FED FROM? SAME FPL
 TRANSFORMER? 230.72, 230.2
  
 6) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-08-05 Cont ID  
Sent By nmccray Date 2004-08-05 Time 10:31 Rev Time 0.00
Received By nmccray Date 2004-08-05 Time 10:31 Sent To  
Notes
2004-08-05 00:00:00REVISION TO FIRE SPRINKLER PLAN PERMIT #
 04060220 DATED 7-19-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-07-22 Time 14:17 Rev Time 0.00
Received By mcarsill Date 2004-05-14 Time 08:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-03-26 Cont ID  
Sent By mcarsill Date 2004-03-26 Time 16:04 Rev Time 0.00
Received By mcarsill Date 2004-03-26 Time 16:04 Sent To  
Notes
2004-03-26 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEMOLITION DEBRIS IS TO BE
 REMOVED FROM THE BUILDING DAILY.
  
 3) FIRE SPRINKLER HEADS ARE REQUIRED
 IN THE WALK-IN COOLERS AND FREEZERS.
  
 4) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 14:17 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 14:17 Sent To FIRE
Notes
2004-07-22 00:00:00REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-01 Cont ID  
Sent By csiegber Date 2004-06-01 Time 11:19 Rev Time 0.00
Received By csiegber Date 2004-06-01 Time 11:19 Sent To B
Notes
2004-06-01 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-05 Time 11:23 Rev Time 0.00
Received By csiegber Date 2004-05-05 Time 11:23 Sent To  
Notes
2004-05-05 00:00:00TO COMM BD#56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 16:28 Sent To  
Notes
2004-03-19 00:00:00COMM BD#33

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-11 Cont ID  
Sent By kstevens Date 2004-05-26 Time 10:17 Rev Time 0.40
Received By pkrauss Date 2004-05-11 Time 06:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-10 Cont ID  
Sent By pkrauss Date 2004-04-10 Time 12:39 Rev Time 0.50
Received By pkrauss Date 2004-04-10 Time 12:37 Sent To  
Notes
2004-04-10 00:00:00PROVISO:
 ROOF CURB SHALL BE A MINIMUM OF 8"
 ABOVE THE ROOF SURFACE PER 2001 FBC
 1511.7.
  
 PLEASE PROVIDE INFORMATION ON THE
 CONDENSATE; LINE SIZE, PIPE MATIERIAL
 AND TERMINATION.PER CITY CODE SECTION
 90-125 (5), CONDENSATE SHALL TERMINATE
 TO STORM DRAIN NOT THE SANITARY. PLEASE
 CLARIFY.
  
 SEPARATE PERMIT REQUIRED FOR WALK-IN
 COOLER/FREEZERS AND COOLERS WITH REMOTE
 CONDENSERS.PROVIDE MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-05-26 Cont ID  
Sent By kstevens Date 2004-05-26 Time 10:16 Rev Time 1.25
Received By kstevens Date 2004-05-26 Time 10:16 Sent To M
Notes
2004-05-26 00:00:00SEPARATE GAS PLANS AND PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-05-22 Cont ID  
Sent By kstevens Date 2004-05-22 Time 07:56 Rev Time 1.00
Received By kstevens Date 2004-05-22 Time 07:56 Sent To  
Notes
2004-05-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) COMMENTS FROM PREVIOUS REVIEW HAVE
 NOT BEEN ADDRESS. COMMENT NUMBER SHALL
 REMAIN THE SAME TO AVOID CONFUSION.
 3) SHT A-3 SPECIFICATION WORK SHEETS RE-
 FERED TO BY DBPR STAMP (3) SHALL BE SUB-
 MITTED. 1 COPY WITH EACH SET OF PLANS.
 SECTION 104.2.1.
 5) SHT A-3 S-13 GREASE INTECEPTOR NOT
 APPROVED UNDER SINK.(ALSO SEE SHEET P-3)
 ALSO PER RODNEY COMPO A SAMPLE POINT IS
 REQUIRED ON SANITARY BLDG DRAIN PRIOR TO
 DRAINING INTO TOILET ROOMS. (SEE ATTACH-
 ED SHEET). SHOW LOCATION OF SAMPLE POINT
 ON RISER DIAGRAM AND ON FLOOR PLAN.
 WASTE ORD. #2938-96.
 7) SHT P-3 PLUMBING SPECIFICATIONS #7,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. PDI-WH 201/SECTION 604.9
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 *******NOTE: NO NOT REMOVE SHT A3 OF 8
 AS THIS SHEET HAS THE DBPR STAMP********
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-24 Cont ID  
Sent By kstevens Date 2004-03-24 Time 18:32 Rev Time 1.50
Received By kstevens Date 2004-03-24 Time 18:32 Sent To  
Notes
2004-03-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED.
 2) SHT A-2 ALL CAPPED AND DEMO'ED PLUMB-
 ING LINES SHALL BE INSPECTED PRIOR TO
 COVERING.
 3) SHT A-3 SPECIFICATION WORK SHEETS RE-
 FERED TO BY DBPR STAMP (3) SHALL BE SUB-
 MITTED. 1 COPY WITH EACH SET OF PLANS.
 SECTION 104.2.1
 4) SHTS A-3 & P-1 FIXTURE SCHEDULE, X5A
 SHOWS QUANTITY 2, NONE FOUND. PLEASE
 CLAIRFY. SECTION 104.2.1
 5) SHT A-3 S-13 GREASE INTECEPTOR NOT
 APPROVED UNDER SINK. CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE, WASTE
 ORD. 2938-96 @ (561) 837-4074 FOR GREASE
 INTECEPTOR REQUIREMENTS.
 6) SHT P-2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. SECT-
 ION 604.9
 7) SHT P-3 PLUMBING SPECIFICATIONS #7,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. PDI-WH 201/SECTION 604.9
 8) AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THIS SPACE. INSTALLED
 A MAXIMUM OF 4' ABOVE THE FLOOR FOR
 SERVICING AND CERTIFICATION. SECTION
 608.13.2
 9) SHT P-3 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED PER SECTION
 607.3.2
 10) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - INITIALS ARE NOT ACCEPTABLE
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 THE SEAL SHALL BE PRESSED SO THAT IT CAN
 BE READ. UNABLE TO READ NAME OF ENGINEER
 AND TYPE OF PROFESSIONAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]