Plan Review Details - Permit 04031071
Plan Review Stops For Permit 04031071
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-26 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 18:14 Rev Time 0.77
Received By jwitmer Date 2004-04-26 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By jwitmer Date 2004-04-06 Time 17:40 Rev Time 0.55
Received By jwitmer Date 2004-04-06 Time 17:40 Sent To  
Notes
2004-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031071
 ADD: 2501 BRISTOL DR A-10
 CONT: PAUL DAVIS
 TEL: (561)248-7149
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)ALL INFORMATION, DRAWINGS, SPECIFI-
 CATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 2) PLEASE PROVIDE TYPE OF BUSINESS/
 OCCUPANCY.
  
 3) INDICATE WHAT WORK IS TO BE COMPLETED
 UNDER THIS PERMIT?
  
 4)WILL THERE BE A DROPPED CEILING, IF SO
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 ADDITIONAL COMMENTS MAY RESULT FROM THIS
 REVIEW, A THROUGH REVIEW CAN NOT BE
 ACCOMPLISHED AT THIS TIME!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 18:14 Rev Time 0.33
Received By dpalmer Date 2004-04-28 Time 18:07 Sent To B
Notes
2004-04-28 00:00:00*** PROVISO /NOTES ****
  
 1)NOTE: PLEASE SUBMIT REVISED PANEL
 SCHEDULE WITH CORRELATING CIRCUITS
 AND FULLY VIABLE PANEL SCHEDULE.
 PLEASE SUBMIT ANY OTHER CHANGES.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-21 Cont ID  
Sent By csiegber Date 2004-04-28 Time 10:23 Rev Time 0.25
Received By dpalmer Date 2004-04-21 Time 05:52 Sent To  
Notes
2004-04-21 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE THAT THIS A COMM
 BLDG AND REQ'S ALL CIRCUITING TO BE
 SHOWN ON PLANS AND CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 2) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42 ETC
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 4)NOTE: PLEASE SEE FBC 104.2.1, PERSON
 RESPONSIBLE FOR PLAN, IS TO HAVE NAME
 AND SIGNATURE ON PLANS.
  
 5)NOTE: PLEASE SEE 210.62 FOR NEW/OR
 EXSITNG REQ'D WINDOW RECEPTS FOR
 ADVERTISING/ SIGNAGE ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 13:24 Rev Time 0.50
Received By btrobaug Date 2004-04-06 Time 13:24 Sent To  
Notes
2004-04-06 00:00:00 
 PLEASE SUBMIT PLANS,ELECTRICAL
 CALCULAT-IONS FOR THE INTENDED SCOPE OF
 WORK PER 104.1.3, 104.2.1 FLORIDA
 BUILDING CODE, 2001 AND 215.5 NEC 2002.
 THIS WORK MUST BE PERMITTED TO, AND
 INSTALLED BY AN ELECTRICAL CONTRACTOR
 PURSUANT TO CHAPTER
 489 FLORIDA STATUTES.
  
 PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SIZE PER 215.5.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-15 Cont ID  
Sent By mcarsill Date 2004-04-15 Time 13:39 Rev Time 0.00
Received By mcarsill Date 2004-04-15 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-07 Cont ID  
Sent By mcarsill Date 2004-04-07 Time 13:20 Rev Time 0.00
Received By mcarsill Date 2004-04-07 Time 13:20 Sent To  
Notes
2004-04-07 00:00:001) PLEASE DISPLAY REQUIRED EXITS,
 EXIT SIGNS, AND EMERGENCY LIGHTING.
  
 2) PLEASE INDICATE OCCUPANCY TYPE
 AND OCCUPANT LOADS.
  
 3) PLEASE DISPLAY ALL TENANT DEMISING
 WALLS.
  
 4) PLEASE DISPLAY ALL FIRE EXTINGUISHERS
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 10:23 Sent To E
Notes
2004-04-28 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-28 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 16:06 Sent To  
Notes
2004-04-14 00:00:00TO COMM BD#33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 11:53 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 11:53 Sent To  
Notes
2004-03-19 00:00:00TO COMM BD#20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-04-20 Cont ID  
Sent By pkrauss Date 2004-04-20 Time 12:15 Rev Time 0.35
Received By pkrauss Date 2004-04-20 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 10:29 Rev Time 0.40
Received By pkrauss Date 2004-04-06 Time 09:45 Sent To  
Notes
2004-04-06 00:00:00DENIED:
 1.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 2.PROVIDE MANUFACTURER SUBMITTAL FOR
 THE NEW C.U. STAND, SHALL COMPLY WITH
 2001 FBC 1511.7 FOR THE HEIGHT
 REQUIREMENT ABOVE THE FINISHED ROOF.
 (SEE ATTACHED).
  
 3.PLEASE SUBMIT OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-04-12 Cont ID  
Sent By pkrauss Date 2004-04-12 Time 13:49 Rev Time 0.05
Received By pkrauss Date 2004-04-12 Time 13:49 Sent To  
Notes
2004-04-12 00:00:00NO PLUMBING INDICATED OR PLUMBING
 CONTRACTOR/


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved