Plan Review Details - Permit 04031063
Plan Review Stops For Permit 04031063
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-23 Cont ID  
Sent By jwitmer Date 2004-04-23 Time 12:38 Rev Time 0.55
Received By jwitmer Date 2004-04-23 Time 12:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By jwitmer Date 2004-04-06 Time 17:10 Rev Time 0.55
Received By jwitmer Date 2004-04-06 Time 17:10 Sent To  
Notes
2004-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031063
 ADD: 1609 S DIXIE# 3
 CONT: SARRI CONSTRUCTION
 TEL: (561)315-9376
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 11-4.35.2 THE MINIMUM CLEAR OPENING FOR
 A DRESSING ROOM WITH A CURTAIN IS 32".
  
 11-4.35.4 EVERY ACCESSIBLE DRESSING ROOM
 SHALL HAVE A 24"X48" BENCH FIXED TO THE
 WALL ALONG THE LONGER DIMENSION.
 BENCH SHALL BE MOUNTED BETWEEN 17" &
 19".
  
 PROVIDE ADDITIONAL INFORMATION AS TO
 HOW THE SOFFIT FRAMING IS ATTACHED TO
 WHAT STRUCTURE ABOVE? AT WHAT SPACING?
 WHAT TYPE OF FAASTENERS?
  
 HOW WILL ACCESS TO AIR HANDLIER BE
 ACHIEVED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 07:45 Rev Time 0.25
Received By dpalmer Date 2004-06-17 Time 07:45 Sent To FIRE
Notes
2004-06-17 00:00:00PLEASE SEE CIRCUITING ON PANEL SCHEDULE
 STILL SHOWS EM/EXT LTS ON THEIR OWN
 CIRCUIT. PLEASE SEE 700.12E

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-05-06 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 15:51 Rev Time 0.25
Received By dpalmer Date 2004-05-06 Time 16:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:27 Rev Time 0.33
Received By dpalmer Date 2004-04-27 Time 20:09 Sent To  
Notes
2004-04-27 00:00:00*** PROVISO ***REVISION***
  
 1)NOTE: PLEASE SHOW ALL NEW CIRCUITING
 ON PLANS AND CORRELATE WITH PANEL
 SCHEDULE.
 THIS IS REQ'D BEFORE ROUGH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-27 Time 13:55 Rev Time 0.33
Received By dpalmer Date 2004-04-20 Time 19:02 Sent To  
Notes
2004-04-20 00:00:00************* UNSAT *********
  
 PLEASE SEE NOTES FROM FIRST REVIEW, SOME
 HAVE NOT BEEN ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM LTS.
  
 3)NOTE: PLEASE SHOW TRK LT CALCS.220.12B
  
 4)NOTE: PLEASE SEE 600.5, NO OTHER OUT-
 -LETS ETC PERMITTED ON SIGN CIRCUIT.
 SHOW WINDOW(S) ARE SEPARATE PER 210.62
 AND MAY NOT SERVE AS THE SAME WITH SIGN.
  
 5)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B) GIVEN AS NOTICE. THIS IS GIVEN ON
 2ND REVIEWS W/ SAME COMMENTS.
  
 NEW NOTE:
 PLANS REQ'D TO BE SIGNED BY THE PERSON
 RESPONSIBLE FOR PLANS. FBC 104.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-12 Cont ID  
Sent By dpalmer Date 2004-04-12 Time 11:02 Rev Time 0.50
Received By dpalmer Date 2004-04-12 Time 11:02 Sent To  
Notes
2004-04-12 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE INCLUDE ALL NEW CIRCUIT-
 -ING ON PLANS AND CORRELATE WITH A SUB-
 -MITTED PANEL SCHEDULE.
 PLEASE ALSO INCLUDE SIZE OF PANEL.
  
 2)NOTE: PLEASE SHOW TRACK LT CALCS PER
 210.12B.
  
 3)NOTE: PLEASE VERIFY IF RECEPTS SHOWN
 ARE FOR SHOW WINDOWS. 210.62
  
 4)NOTE: PLEASE VERIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5?
  
 5)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR EM/EXT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-06-21 Cont ID  
Sent By nmccray Date 2004-06-21 Time 10:24 Rev Time 0.00
Received By nmccray Date 2004-06-21 Time 10:24 Sent To  
Notes
2004-06-21 00:00:00REVISION DATED 6-15-04 (ELECTRICAL)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-16 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 07:45 Rev Time 0.00
Received By mcarsill Date 2004-04-16 Time 15:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-07 Cont ID  
Sent By mcarsill Date 2004-04-07 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2004-04-07 Time 14:12 Sent To  
Notes
2004-04-07 00:00:001) PLEASE SHOW ALL ILLUMINATED EXIT
 SIGNS AND EMERGENCY LIGHTS.
  
 2) PLEASE DISPLAY ALL FIRE EXTINGUISHERS
  
 3) PLEASE INDICATE HOURLY RATINGS OF
 ANY TENANT SEPARATION WALLS.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 5) PLEASE PROVIDE DETAILS ON LOCKING
 DEVICES FOR FRONT DOORS.
  
 6) PLEASE PROVIDE CEILING HEIGHTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 15:51 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 15:51 Sent To E
Notes
2004-06-15 00:00:00TO DP DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:27 Rev Time 0.00
Received By csiegber Date 2004-05-05 Time 14:27 Sent To E
Notes
2004-05-05 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 13:55 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 13:54 Sent To E
Notes
2004-04-27 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 08:02 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 08:02 Sent To  
Notes
2004-04-16 00:00:00TO COMM BD#61

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:16 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:16 Sent To  
Notes
2004-03-19 00:00:00TO COMM BD#64