Plan Review Details - Permit 04031030
Plan Review Stops For Permit 04031030
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-13 Cont ID  
Sent By dpalmer Date 2004-05-13 Time 10:33 Rev Time 2.00
Received By lsmith Date 2004-05-06 Time 08:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-05-06 Time 05:40 Rev Time 0.00
Received By lsmith Date 2004-04-28 Time 09:07 Sent To  
Notes
2004-04-28 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. A NOTICE OF COMMENCEMENT MUST BE
 FILED AND A COPY SUBMITTEDBEFORE A
 PERMIT CAN BE ISSUED.
  
 2. SHOW DESIGN PRESSURES ON PAGE 1 OF
 PLANS FOR THE WINDOWS/DOORS.
  
 3. SHOW DOOR FROM GARAGE TO LAUNDRY IS
 SOLID CORE OR INSULATED PER FBC.
  
 4. SHOW ATTIC ACCESS ON PLANS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-13 Cont ID  
Sent By dpalmer Date 2004-05-13 Time 10:31 Rev Time 0.50
Received By dpalmer Date 2004-05-13 Time 09:53 Sent To B
Notes
2004-05-13 00:00:00*** NOTES REDLINED ***
  
 1)NOTE: PLEASE SEE MISSING SD LEADING
 TO FLR ABOVE. NFPA-72
  
 2)NOTE: PLEASE SEE 210.52 FOR A COUPLE
 OF RECEPTS MISSING.
  
 3)NOTE: NO LOW VOLTAGE SHOWN ON PLANS,
 WILL REQUIRE SEPARATE PLANS AND PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-12 Time 10:20 Rev Time 0.25
Received By dpalmer Date 2004-05-06 Time 05:36 Sent To B
Notes
2004-05-06 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. PLEASE SEE THAT THE SECOND FLR
 ELECTRICAL PLAN WAS NOT SUBMITTED FOR
 REVIEW.
 PLEASE ALSO NOTE THERE IS NO ELECTRICAL
 RISER DIAGRAM, PANEL SCHEDULE(S) ETC.
 215.5
 A COMPLETE REVIEW CAN NOT BE DONE AT
 THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:12 Rev Time 0.75
Received By btrobaug Date 2004-04-01 Time 10:23 Sent To M
Notes
2004-04-01 00:00:00 
 DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SUBMIT A FULL SET OF PLANS FOR
 REVIEW. THE SECOND FLOOR ELECTRICAL
 PLAN, LOAD CALC'S, PANEL
 SCHEDULE AND ELECTRICAL NOTES ARE
 MISSING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 10:19 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 10:19 Sent To E
Notes
2004-05-12 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:12 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 15:12 Sent To E
Notes
2004-05-04 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-03-25 Time 11:03 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:53 Sent To  
Notes
2004-03-25 00:00:00TO SFD RACK/E
2004-03-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-01 Time 10:35 Rev Time 0.30
Received By pkrauss Date 2004-04-05 Time 11:47 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-04-12 Cont ID  
Sent By pkrauss Date 2004-04-05 Time 11:47 Rev Time 0.25
Received By jleech Date 2004-04-12 Time 17:20 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-25 Cont ID  
Sent By mmclean Date 2004-03-25 Time 11:03 Rev Time 0.00
Received By mmclean Date 2004-03-25 Time 11:03 Sent To I
Notes
***NONE***