Plan Review Details - Permit 04030950
Plan Review Stops For Permit 04030950
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-03 Cont ID  
Sent By jwitmer Date 2004-08-03 Time 09:32 Rev Time 2.22
Received By jwitmer Date 2004-08-03 Time 09:32 Sent To PC
Notes
2004-08-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030950
 ADD: 753 N COGRESS AV
 CONT: WCI COMMUNITIES INC
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE DETAILS OF HOW TRANSITION WIL
 L BE MADE FROM RETAINING WALL TO THE
 DOOR OPENING OF THE SALES TRAILER. ACCES
 SIBLE OPENING MUST MEET REQUIREMENTS OF
 CHANGE INLEVEL 11-4.3.8. THIS COMMENT
 IS #6 FROM FIRST REVIEW.
  
 2) COMMENT#8 FROM 1ST REVIEW, S-4 FASTEN
 ER SCHEDULE IS FOR THE HIGH VELOCITY
 HURRICANE ZONE CORRECT. NOTE WIRE LATH
 IS APPLIED AS TO 2504.2.2. WHICH REFERS
 TO ASTM C-1063 HORIZONTAL 3/8" RIB LATH
 REQUIRES NAILS TO BE ENBEDED 1 3/4" INTO
 HORIZONTAL FRAMING MEMBERS @ EACH RIB
 (4") O.C. ASA AN EXAMPLE.
  
 3) COMMENT# 10 FROM 1ST REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
 C) BAHAMA SHUTTERS
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-16 Cont ID  
Sent By jwitmer Date 2004-04-16 Time 16:43 Rev Time 4.50
Received By jwitmer Date 2004-04-16 Time 15:03 Sent To  
Notes
2004-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030950
 ADD: 753 N CONGRESS AV
 CONT: WCI COMMUNITIES INC
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING CAPACITY.
 REQUIRED TEST AND RECOMMENDATIONS
 SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) SALES TRAILER;ACCESSIBLE ROUTE
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. INDICATE THE ACCESSIBLE ROUTE
 FROM PUBLIC TRANSPORTATION.
  
 4)ACCESSIBLE ROUTE SIDEWALKS:SLOPE
 THE SHEET S-2 INDICATES THE SLOPE OF
 THESIDEWALKS. 11-4.3.7 CROSS SLOPE IS
 NOT
 TO EXCEED 1:50. PLANS INDICATE FOR A
 60" WIDE SIDEWALK TO BE 2 1/4".
  
 5) S-1 INDICATES THE USE OF A RETAINING
 WALL ON THREE SIDES OF THE BUILDING.
 SHOW COMPLIANCE WITH 1804.6.3.1
 OPENINGSSHALL BE ARRANGED TO PROVIDE
 CROSS VENTILATION. PROVIDE INFORMATION
 ON HOW CROSS VENTILATION SHALL OCCUR.
  
 6) PROVIDE DETAIL OF HOW TRANSITION WILL
 BE MADE FROM RETAINING WALL TO DOOR OPEN
 ING OF SALES CENTER. ACCESSIBLE OPENING
 MUST MEET REQUIREMENTS OF CHANG IN LEVEL
 11-4.3.8.
 SHEET A-5 DETAIL5 INDICATES A THRESHOLD
 BUT THERE IS NO CORRELATION TO LOCATION
 OF TRAILER SIDEWALL OR RETAINING WALL.
  
 7) THE TOWER STRUCTURES NEED TO INDICATE
 THE WIND DESIGN CRITERIA OF WHICH THEY
 ARE DESIGNED:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 THE INTERNAL PRESSURE COEFFICIENT WILL
 BE FORE A OPEN BUILDING NOT ANENCLOSED
  
 8) S-4 FASTENER SCHEDULES ARE FOR THE
 HIGH VELOCITY HURRICANE ZONES, WE ARE
 NOT LOCATED IN THIS ZONE.
  
 9) 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS,CONCRETE/ WOOD,
 WOOD/ WOOD
 B) BAHAMA SHUTTER
 C) ROOFING ASSEMBLY
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-21 Cont ID  
Sent By dpalmer Date 2004-06-21 Time 11:25 Rev Time 0.33
Received By dpalmer Date 2004-06-21 Time 11:16 Sent To  
Notes
2004-06-21 00:00:00******** UNSAT **************
  
 1)NOTE: PLEASE SEE NOW A RISER DIAGRAM
 IS BEING SUBMITTED FOR REVIEW.
 PLEASE CORRELATE PANEL SCHEDULE AND
 RISER DIAGRM.
 PANEL SCHEDULE INDICATES ONLY PANEL 'C',
 BEING FED, YET RISER ALSO SHOWS PANEL
 "B".?
  
 2)NOTE: PLEASE NOTE GROUNDING FOR TRAIL-
 -ERS. PLEASE ALSO SEE 550.32
  
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-13 Cont ID  
Sent By dpalmer Date 2004-04-13 Time 17:59 Rev Time 0.33
Received By dpalmer Date 2004-04-13 Time 17:59 Sent To  
Notes
2004-04-13 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 FOR TRAILER HOOK-UP. PLEASE PROVIDE
 PLAN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-06-18 Cont ID  
Sent By mcarsill Date 2004-06-18 Time 13:39 Rev Time 0.00
Received By mcarsill Date 2004-06-18 Time 13:39 Sent To  
Notes
2004-06-18 00:00:001) PREVIOUS PLAN REVIEW COMMENTS
 HAVE NOT BEEN ADDRESSED. PLEASE
 PROVIDE WRITTEN COMMENTS AT NEXT
 SUBMITTAL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-19 Cont ID  
Sent By mcarsill Date 2004-03-19 Time 14:29 Rev Time 0.00
Received By mcarsill Date 2004-03-19 Time 14:28 Sent To  
Notes
2004-03-19 00:00:001) PLEASE INDICATE HOW LONG THE
 TEMPORARY SALES CENTER WILL BE AT
 THE PROPOSED LOCATION.
  
 2) BUILDING ADDRESS REQUIRED ON SALES
 CENTER.
  
 3) PORTABLE FIRE EXTINGUISHER REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 10:39 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 10:39 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#41

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-16 Cont ID  
Sent By mmclean Date 2004-06-17 Time 16:08 Rev Time 0.00
Received By mjacobs Date 2004-06-16 Time 15:02 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-16 Cont ID  
Sent By mmclean Date 2004-03-30 Time 16:57 Rev Time 0.00
Received By csiegber Date 2004-03-17 Time 11:52 Sent To  
Notes
2004-03-17 00:00:00TO COMM BD#32

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-02 Cont ID  
Sent By pkrauss Date 2004-04-02 Time 11:08 Rev Time 0.20
Received By pkrauss Date 2004-04-02 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-02 Cont ID  
Sent By kstevens Date 2004-07-02 Time 09:39 Rev Time 1.00
Received By kstevens Date 2004-07-02 Time 09:39 Sent To  
Notes
2004-07-02 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) HEALTH DEPT PERMIT REQUIRED FOR THE
 HOLDING TANK. SECTION 101.4.7
 (CONTRACTOR INDICATED THAT THEY WILL
 WAIT FOR SEWER HOOK SOME TIME IN SEPT.
 C/O OF TRAILER WILL BE HELD UP UNTILL
 THE SANITARY CAN BE HOOKED UP TO SEWER
 LATERAL).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By kstevens Date 2004-03-23 Time 14:05 Rev Time 0.33
Received By kstevens Date 2004-03-23 Time 14:05 Sent To  
Notes
2004-03-23 00:00:00DENIED
 REFERENCE: WPB CITY CODE
 PBC HEALTH DEPT.
  
 1) SEPTIC TANKS AND DRAIN FIELDS ARE NOT
 APPROVED IN THE CITY OF WEST PALM BEACH.
 WHEN SEWER IS AVAILABLE TO A PROPERTY
 SERVED, A DIRECT CONNECTION SHALL BE
 MADE TO THE SEWER. SECTION 90-123(C)(E)
 2) IF HOLDING TANKS ARE TO BE USED,
 CONTACT HEALTH DEPT PERMITTING. FRANK
 LOMBARDO (561) 233-5139. PROVIDE SIZE
 OF TANK, SITE PLAN, AND APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-06-17 Cont ID  
Sent By mmclean Date 2004-06-17 Time 16:08 Rev Time 0.00
Received By mmclean Date 2004-06-17 Time 16:08 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-30 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:02 Rev Time 0.00
Received By mmclean Date 2004-03-30 Time 16:57 Sent To I
Notes
2004-03-30 00:00:00DENIED, NEED LANDSCAPE PLANS THAT MEETS
 ZONING CODE. MUST PULL A SEPERATE PERMIT
 FOR SIGN OR NEED TO PROVIDE INFORMATION
 FOR SIGN.
 ENGINEER MUST REVIEW DRIVEWAY FOR MODEL
 HOME WITH APPROVAL
 PER ERIC SCHNEIDER, SENIOR PLANNER
 659-8031 MM