Plan Review Details - Permit 04030886
Plan Review Stops For Permit 04030886
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-07 Cont ID  
Sent By jwitmer Date 2004-06-07 Time 15:36 Rev Time 2.22
Received By jwitmer Date 2004-06-07 Time 15:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By jleech Date 2004-05-29 Time 10:25 Rev Time 1.00
Received By alange Date 2004-04-05 Time 10:39 Sent To  
Notes
2004-04-05 00:00:00DENIED
  
 1.PRODUCT APPROVALS FOR ROOFING
 HAVE NOT BEEN SUBMITTED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3.BUILDING VALUATION TOO LOW.
 ADJUSTEDTO $4500.00 PER PHONE
 CONVERSATION WITH MR. CHILDRESS.
 ADDITION PERMIT FEES ARE DUE.
  
 4.SHOW ROOF SHEATHING SIZE AND
 FASTENINING SCHEDULE.
  
 5.AWNINGS WILL REQUIRE A SPERATE
 PERMIT.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-20 Cont ID  
Sent By dpalmer Date 2004-05-20 Time 14:28 Rev Time 0.33
Received By dpalmer Date 2004-05-20 Time 14:28 Sent To P
Notes
2004-05-20 00:00:00REDLINED 250.32/250.50
 210.12

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:46 Rev Time 0.33
Received By dpalmer Date 2004-05-03 Time 16:39 Sent To B
Notes
2004-05-03 00:00:00***********UNSAT **********
  
 PLEASE SEE NOTES FROM FIRST REVIEW.\
  
 1)NOTE: PLEASE PROVIDE ALL INFORMATION
 AS REQ'D UNDER NEC 225.31, 250.32
 RISER DIAGRAM/FEED ETC. 215.5
 PLEASE PROVIDE MIN CIRCUIT INFORMATION
 ON PANEL SCHEDULE. 210.12/ 210.52/210.11
 C3 ETC.
  
 2)NOTE: PLEASE SEE FS 481.221 A FULL/
 COMPLETE SIGNATURE IS REQ'D. INITIALS
 ARE NOT PERMITTED. PLEASE PROVIDE COPIES
 OF LICENSE/ DRIVERS LICENSE TO VERIFY
 LEGAL SIGNATURE.
  
 3)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:42 Rev Time 0.50
Received By btrobaug Date 2004-03-29 Time 17:38 Sent To P
Notes
2004-03-29 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SHOW COMPLIANCE WITH 225.31,
 250.30, AND 250.32(D). DICONNECTING
 MEANS AND GROUNDING. 2002 NEC.
  
 PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:46 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 13:46 Sent To E
Notes
2004-05-19 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-19 Cont ID  
Sent By csiegber Date 2004-04-19 Time 11:45 Rev Time 0.00
Received By csiegber Date 2004-04-19 Time 11:45 Sent To P
Notes
2004-04-19 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:42 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 08:42 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-16 Cont ID  
Sent By mmclean Date 2004-03-22 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 11:29 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-02 Cont ID  
Sent By kstevens Date 2004-03-30 Time 18:23 Rev Time 0.15
Received By pkrauss Date 2004-04-02 Time 16:01 Sent To B
Notes
2004-04-02 00:00:00NO MECHANICAL PLANS OR WORK SUBMITTED
 WITH PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-05-29 Cont ID  
Sent By dpalmer Date 2004-05-20 Time 14:28 Rev Time 0.25
Received By jleech Date 2004-05-29 Time 10:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-03 Cont ID  
Sent By pschmitz Date 2004-05-03 Time 13:19 Rev Time 1.50
Received By pschmitz Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-30 Cont ID  
Sent By csiegber Date 2004-04-19 Time 11:45 Rev Time 0.33
Received By kstevens Date 2004-03-30 Time 18:23 Sent To M
Notes
2004-03-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 CITY CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) OUTSIDE SHOWER DRAIN NOT APPROVED.
 NO RAIN WATER CAN DRAIN TO SANITARY.
 2) SECTION 909.1 ONLY THE FIXTURES FROM
 THE BATHROOM GROUP SHALL DRAIN INTO THE
 WET VENT HORIZONTAL DRAIN OF THE BATH-
 ROOM FIXTURES. ALL OTHE FIXTURES SHALL
 CONNECT DOWNSTREAM OF THE WET VENT. SEE
 RED LINE CORRECTIONS ON SHT A-1.
 3) INITIALS NOT ACCEPTABLE ON SEAL. FULL
 SIGNATURE REQUIRED. 61G1-16.003 FAC, AND
 FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-16 Time 11:30 Rev Time 0.00
Received By mmclean Date 2004-03-22 Time 16:23 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved