Plan Review Details - Permit 04030734
Plan Review Stops For Permit 04030734
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-10 Cont ID  
Sent By alange Date 2004-05-10 Time 08:55 Rev Time 0.75
Received By alange Date 2004-05-10 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By pschmitz Date 2004-05-09 Time 15:16 Rev Time 1.00
Received By alange Date 2004-04-05 Time 08:47 Sent To  
Notes
2004-04-05 00:00:00DENIED
 1.SHOW WINDOW AND DOOR BUCK DETAIL.
 BUCKS SHALL BE INSTALLED ACCORDING TO
 FBC 1707.4.4.2UNLESS OTHERWISE TESTED,
 BUCKS SHALL EXTEND BEYOND THE INTERIOR
 FACE OF THE WINDOW OR DOOR FRAME SUCH
 THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED.
  
 2.SHOW DOOR RATING FOR DOOR #1.
  
 3.SUBMIT ENERGY CALCULATIONS.
  
 4.SHOW INTERIOR WALL FRAMING DETAIL
 AT OLD GARAGE DOOR LOCATION AND ALSO
 SHOW THICKNESS OF DRYWALL USED.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-04 Cont ID  
Sent By dpalmer Date 2004-05-04 Time 17:56 Rev Time 0.33
Received By dpalmer Date 2004-05-04 Time 17:46 Sent To P
Notes
2004-05-04 00:00:00**** REDLINED PLANS***
  
 VERIFY OCP AND AWG FOR AHU'S, DO NOT
 SEEM TO CORRELATE W/ LOAD CALCS.
 PLEASE SEE 424.3B
  
 PLEASE SEE 250.66 FOR GEC, SHOWS #6??
  
 SD'S REQ'D INSIDE AND OUTSIDE RM, THIS
 IS AN ADAPTABLE SLEEPING RM.,
 NFPA-72 8-1
 PLEASE ALSO PROVIDE ARC FAULT PROTECTION
 PER 210.12
  
 ABOVER ITEMS REDLINED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By csiegber Date 2004-05-04 Time 08:57 Rev Time 0.50
Received By btrobaug Date 2004-03-29 Time 07:31 Sent To  
Notes
2004-03-29 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE. THIS IS REQUIRED
 BECAUSE THE DWELLING IS STILL
 CONSIDERED A RESIDENCE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 08:57 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 08:57 Sent To E
Notes
2004-05-04 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-27 Cont ID  
Sent By mmclean Date 2004-05-03 Time 15:11 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 14:16 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:43 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 08:43 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-16 Cont ID  
Sent By mmclean Date 2004-03-22 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 10:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-01 Cont ID  
Sent By kstevens Date 2004-03-29 Time 18:39 Rev Time 0.35
Received By pkrauss Date 2004-03-31 Time 16:38 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-09 Cont ID  
Sent By pschmitz Date 2004-05-09 Time 15:16 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By dpalmer Date 2004-05-04 Time 17:56 Rev Time 0.50
Received By kstevens Date 2004-03-29 Time 18:36 Sent To M
Notes
2004-03-29 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 PLUMBING
  
 1) CLEANOUT REQUIRED NEAR JUNCTION OF
 BUILDING DRAIN AND BUILDING SEWER.
 SECTION 708.3.5
 2)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 3) IMPRESSION FROM SEAL ON SHEET P100
 UNREADABLE. PLEASE PRESS SEAL TO MAKE
 SEAL LEGIBLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-05-03 Cont ID  
Sent By mmclean Date 2004-05-03 Time 15:11 Rev Time 0.00
Received By mmclean Date 2004-05-03 Time 15:11 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-04-27 Time 14:22 Rev Time 0.00
Received By mmclean Date 2004-03-19 Time 15:43 Sent To I
Notes
2004-03-22 00:00:00DENIED, CORNER LOT MUST BE 12.5FT.NEED
 2 COPY OF SURVEY SHOWING THE SETBACKS.
 CALLED CONTR LEFT MSG