Plan Review Details - Permit 04030726
Plan Review Stops For Permit 04030726
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-03-21 Cont ID  
Sent By shill Date 2005-03-21 Time 15:30 Rev Time 1.00
Received By shill Date 2005-03-16 Time 16:23 Sent To PC
Notes
2005-03-21 00:00:00REVISION DATED 3/10/05, NEW ROOFING
 PRODUCT APPROVALS AND TEST REPORT

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-03-09 Cont ID  
Sent By shill Date 2005-03-09 Time 16:50 Rev Time 1.00
Received By shill Date 2005-03-09 Time 16:41 Sent To PC
Notes
2005-03-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL FOR THE NOA030421.06
 SUBMITTED, FAC9B72.
  
 2.)THE USE OF THE LIGHTWEIGHT CONCRETE
 CONFLICTS WITH THE PLAN.REVISE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-12-03 Cont ID  
Sent By shill Date 2004-12-03 Time 16:53 Rev Time 0.00
Received By shill Date 2004-12-03 Time 16:52 Sent To PC
Notes
2004-12-03 00:00:00S1, DRYWALL REPAIRS (HURRICANES)
 11/24/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-10-13 Cont ID  
Sent By shill Date 2004-10-13 Time 10:53 Rev Time 2.00
Received By shill Date 2004-10-13 Time 10:50 Sent To  
Notes
2004-10-13 00:00:00LESS THAN 50% IMPROVEMENT DUE TO
 REPLACEMENT MATERIAL COST
  
 REVISION 7/26/04, COLUMN LINES 11-22

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-25 Time 14:44 Rev Time 4.00
Received By shill Date 2004-08-02 Time 09:14 Sent To I
Notes
2004-08-02 00:00:00****CORRECTIONS****
 REVISION; ADD COLUMNS 12-22 TO SCOPE
 OF WORK (ALREADY INCLUDED IN COST)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)TO AVOID CONFUSION, RENUMBER THE
 PAGES.FOR INSTANCE, THERE SHOULD
 NOT BE TWO PAGE S1S, ONE SHOWING
 COLUMNS 1-11, ANOTHER SHOWING 12-22.
  
 2.)ADDITIONAL PERMITS REQUIRED
 (MECHANICAL, ELECTRIC).
  
 3.)SHOW COMPLIANCE WITH CHAPTER 11
 (ACCESSIBILITY) FOR THE HABITABLE AREAS
 AND DECK INCLUDING ACCESSIBLE ENTRANCE
 (ELEVATION OF GRADE, ENTRY), DOOR
 WIDTHS, CLEAR FLOOR SPACE, ETC.PLANS
 SHOULD CLEARLY SHOW EITHER EXISTING
 CONDITIONS WHICH ARE CURRENTLY CODE
 COMPLIANT OR PROPOSED RENOVATIONS TO
 BRING INTO COMPLIANCE.
  
 4.)THE CA NUMBER FOR THE ENGINEERING
 FIRM IS TO BE ON EACH SHEET, FAC61G15-
 23.002.
  
 5.)THE SHEETS SHOULD BE BOUND, NOT
 SUBMITTED LOOSE.
  
 6.)THE INTERNAL PRESSURE COEFFICIENT
 PROVIDED ON THE LETTER FROM THE
 ENGINEER (PREVIOUS REVIEW WHEN PERMIT
 WAS ISSUED) IS NOT CORRECT FOR A
 PARTIALLY ENCLOSED BUILDING.PLEASE
 RESUBMIT AND MAKE CLEAR AS TO WHETHER
 THIS BUILDING WAS DESIGNED AS AN
 ENCLOSED OR PARTIALLY ENCLOSED BUILDING.
  
 7.)SEE FBC3401.7.2.6 REGARDING
 OVER 50% REPAIRS TO EXISTING BUILDINGS.
 SHOW COMPLIANCE WITH FBC TABLE 500 AND
 FBC TABLE 600.DECLARE AN OCCUPANCY,
 BUILDING TYPE, NOTE WHETHER SPRINKLED
 OR NOT, SHOW COMPLIANCE WITH
 EGRESS REQUIREMENTS CHAPTER 10.NOTE
 OCCUPANCY SEPARATIONS FBC704 IF
 REQUIRED.
  
 8.)THERE ARE OLD ELECTRIC AND FIRE
 REVIEWS IN THE COMPUTER; PLEASE SUBMIT
 THOSE APPROVED SHEETS.OTHERWISE NEW
 REVIEWS WILL BE REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:45 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-16 Cont ID  
Sent By shill Date 2004-07-16 Time 17:17 Rev Time 1.00
Received By shill Date 2004-07-16 Time 17:17 Sent To  
Notes
2004-07-16 00:00:00PENDING APPROVAL OF SITE SPECIFIC
 PRODUCT APPROVALS BY ASSISTANT BUILDING
 OFFICIAL - OTHERWISE CODE COMPLIANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-13 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:47 Rev Time 4.00
Received By shill Date 2004-07-12 Time 13:34 Sent To  
Notes
2004-07-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)REGARDING THE SITE SPECIFIC PRODUCT
 APPROVALS:
  
 A. CERTIFICATE OF INDEPENDENCE REQUIRED,
 FAC9B-72.040(5)(G) IN ACCORDANCE WITH
 FAC9B-72.110.
  
 B. FAC9B-72.070(4)(A) REQUIRES THE
 ADDRESS OF THE MANUFACTURER.
  
 C. THE TEST REPORT FOR THE ROOF SYSTEM
 IS TO BE SEALED.PROVIDE THE LICENSE
 NUMBER FOR THE PE FAC61G15-23.002
 (DONALD FLOOD, PE, TEST REPORT).
  
 D. THE SITE SPECIFIC PRODUCT APPROVALS
 SHOULD PROVIDE PRESSURE LIMITATIONS
 TO CORRELATE WITH THE PLANS.
  
 E.THE DOCUMENTATION WHICH HAS BEEN
 PREPARED BY OUT OF STATE ENGINEERS
 CANNOT BE SUBMITTED FOR PUBLIC RECORD.
 ENGINEERING MUST BE PREPARED BY A
 FLORIDA LICENSED ENGINEER.
  
 2.)PLEASE PROVIDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER FOR THE
 ENGINEERING FIRM ON EACH SHEET AS
 REQUIRED BY FAC61G15-23.002.
  
 3.)WHERE HAVE THE DESIGN PRESSURES
 FOR WIND LOAD (S4) BEEN OBTAINED FROM?
  
 4.)THE ROOF SITE SPECIFIC PRODUCT
 APPROVAL MAKES REFERENCE TO DESIGN
 PRESSURES ON THE PLAN, SHEET S4, OF
 -37.7 AND -44.7, BUT THIS IS NOT
 CONSISTENT WITH THE PRESSURES SHOWN
 ON THAT SHEET.PLEASE CLARIFY.
  
 5.)PROVIDE THE ENCLOSURE
 CLASSIFICATION FBC1606.1.7(4) (2003
 AMENDMENT).IF THIS BUILDING IS
 DESIGNED AS AN ENCLOSED BUILDING,PROVIDE
 PRODUCT INFORMATION FOR THE DOORS AND
 LOUVERS THAT ARE BEING REINSTALLED.
  
 5.)WHEN RESUBMITTING, REPLACE ONLY
 SHEETS WHICH HAVE CHANGED.ALL SETS
 ARE TO BE BOUND (DO NOT SUBMIT LOOSE
 SHEETS).SUBMIT OLD SHEETS SEPARATELY
 FOR REFERENCE.
  
 6.)PROVIDE DESIGN PRESSURE REQUIREMENT
 FOR THE WALL PANELS, FBC1606.1.7(5).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-08 Cont ID  
Sent By jwitmer Date 2004-04-08 Time 15:38 Rev Time 3.00
Received By jwitmer Date 2004-04-08 Time 15:38 Sent To PC
Notes
2004-04-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030726
 ADD: 5890 N JOG RD
 CONT: HURRICANE SYSTEMS
 TEL: (954)984-0988
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SCOPE OF WORK FOR THIS PROJECT
 EXCEEDS 50% OF THE BUILDING COST, WORK
 TO COMPLY WITH THE REQUIREMENTS FOR NEW
 BUILDINGS. 3401.7.2.6.
  
 2)PLANS TO PROVIDE WIND DESIGN NOT TO
 THE HIGH WIND HURRICANE ZONE BUT TO
 140 MPH.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRANSLUCENT PANELS
 B) STAINLESS STEEL SIDING
 C) ROOFING ASSEMBLIES
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-10-20 Cont ID  
Sent By btrobaug Date 2004-10-20 Time 16:40 Rev Time 0.75
Received By btrobaug Date 2004-10-20 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-19 Time 13:30 Rev Time 0.25
Received By dpalmer Date 2004-10-06 Time 06:14 Sent To  
Notes
2004-10-06 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING REQUIRED INFORMATION TO BE
 PRINTED ON TITLE BLOCK.
 PLEASE ALSO SEE FS 471.023 FOR ADDITION-
 -AL CA # REQUIRED.
 PLEASE SEE TO SEPARATE ENGINEERING FIRMS
 ARE SHOWN ON ELECTRICAL PLANS. THE ABOVE
 COMMENT IS FOR BOTH FIRMS SHOWN.
 PLEASE SEE EDC'S TITLE BLOCK ALSO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-08-03 Cont ID  
Sent By btrobaug Date 2004-08-03 Time 12:34 Rev Time 0.50
Received By btrobaug Date 2004-08-03 Time 12:01 Sent To  
Notes
2004-08-03 00:00:00 
 ORIGINAL APPROVED PLANS WERE TAKEN BY
 CONTRACTOR AND NOT BROUGHT BACK WHEN
 RESUBMITTED FOR PERMIT. PLEASE PROVIDE
 THE APPROVED PLANS FOR FIRE &
 ELECTRICAL TO COMPRISE A COMPLETE SET.
  
 3ILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-04-01 Cont ID  
Sent By btrobaug Date 2004-04-08 Time 07:25 Rev Time 1.00
Received By btrobaug Date 2004-04-01 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-10-13 Cont ID  
Sent By nmccray Date 2004-10-13 Time 12:32 Rev Time 0.00
Received By nmccray Date 2004-10-13 Time 12:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-09-16 Cont ID  
Sent By mcarsill Date 2004-09-16 Time 08:22 Rev Time 0.00
Received By mcarsill Date 2004-09-16 Time 08:22 Sent To  
Notes
2004-09-16 00:00:00FIRE SPRINKLER PLAN SUBMITTED UNDER
 PERMIT # 04080017.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-08-09 Cont ID  
Sent By nmccray Date 2004-08-09 Time 16:01 Rev Time 0.00
Received By nmccray Date 2004-08-09 Time 16:01 Sent To  
Notes
2004-08-09 00:00:00***********DENIED***********************
 WORK DIRECTIVE FOR ROOF, PURLINS AND
 DECK INSTALLATION NOTE # 19 AND 20
 SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-03-19 Cont ID  
Sent By mcarsill Date 2004-03-19 Time 14:30 Rev Time 0.00
Received By mcarsill Date 2004-03-19 Time 14:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 10:08 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 10:08 Sent To B
Notes
2005-03-08 00:00:00TO "SHILL"DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 15:14 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 15:14 Sent To B
Notes
2005-03-14 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-12-01 Cont ID  
Sent By mjacobs Date 2004-12-01 Time 15:02 Rev Time 0.00
Received By mjacobs Date 2004-12-01 Time 15:02 Sent To B
Notes
2004-12-01 00:00:00SENT TO "B" TO SH DESK.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-10-19 Cont ID  
Sent By dpalmer Date 2004-10-19 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2004-10-19 Time 13:30 Sent To E
Notes
2004-10-19 00:00:00TO BT'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-10-14 Cont ID  
Sent By csiegber Date 2004-10-14 Time 14:56 Rev Time 0.00
Received By csiegber Date 2004-10-14 Time 14:56 Sent To E
Notes
2004-10-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 13:38 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 13:38 Sent To  
Notes
2004-09-20 00:00:00TO COMM BD#26

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 14:44 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 14:44 Sent To B
Notes
2004-08-25 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 11:36 Sent To  
Notes
2004-08-03 00:00:00TO COMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-26 Cont ID  
Sent By shill Date 2004-08-03 Time 08:00 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 16:45 Sent To B
Notes
2004-07-26 00:00:00TO SH DESK/SIGNED & SEALED DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:47 Rev Time 0.00
Received By csiegber Date 2004-07-16 Time 16:47 Sent To B
Notes
2004-07-16 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:54 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 09:54 Sent To  
Notes
2004-07-09 00:00:00TO BS DESK/PER CUST

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-08 Cont ID  
Sent By jwitmer Date 2004-04-08 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2004-03-16 Time 14:02 Sent To PC
Notes
2004-03-16 00:00:00TO COMM BD#13