Plan Review Details - Permit 04030653
Plan Review Stops For Permit 04030653
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-05 Cont ID  
Sent By rmcdouga Date 2004-05-05 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2004-05-05 Time 09:47 Sent To  
Notes
2004-05-05 00:00:00SUBMITTAL FOR COLLIER GARAGE DOOR IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-05-03 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2004-04-28 Time 14:21 Sent To  
Notes
2004-04-28 00:00:00BUILDING PROVISO
  
 1) SUBMIT STATE PRODUCT APPROVAL FOR
 COLLIER GARAGE DOOR WITH APPROVED STATUS
 AND FOR THE 8'X7' GARAGE DOOR.
  
 2) SUBMIT A SIGNED AND SEALED LETTER
 FROM THE ENGINEER STATING THAT THE BUTT
 GLASS WAS INSTALLED TO HIS SPECIFICATION
 BEFORE A C.O. WILL BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-14 Cont ID  
Sent By kstevens Date 2004-04-22 Time 16:58 Rev Time 0.00
Received By rmcdouga Date 2004-04-14 Time 09:20 Sent To  
Notes
2004-04-14 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OVAL WINDOW IN THE MASTER BATH IS
 REQUIRED TO BE TEMPERED PER FBC 2405.2.
  
 3) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS SOLID CORE OR INSULATED AS REQUIRED
 BY FBC 13-603.
  
 4) SPECIFY THE ATTIC LIVE LOAD ON THE
 PLANS. SEE FBC TABLE 1604.1.
  
 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/16" TAPCONS IN DETAIL 8 ON SHEET 8.
  
 6) THE STORM PANEL INSTALLATION SCHEDULE
 AND KEY PLAN HAS SOME DISCREPANCIES WITH
 THE ARCHITECTURAL PLANS. PLEASE CORRECT.
  
 7) THE TRUSS ANCHOR SCHEDULE LISTS A
 NUE-VUE NVSTA 48 CONNECTOR. THE STATE
 PRODUCT APPROVAL SUBMITTED IS FOR NVRT
 12-48.
  
 8) THE TRUSS ANCHOR SCHEDULE LISTS A
 SIMPSON HUC 412 CONNECTOR WITH 1505# OF
 UPLIFT. THE STATE PRODUCT APPROVAL
 SUBMITTED IS FOR A HU 412 WITH 905# OF
 UPLIFT. PLEASE CLARIFY.
  
 9) THE SUBMITTAL FOR THE BUTT GLASS
 WINDOW IS INCOMPLETE AND HAS ERRORS. THE
 THIRD PARTY QUALITY ASSURANCE IS
 REQUIRED. THE LOT # ON SHEET 1 OF 2 IS
 INCORRECT. SPECIFY THE DESIGN PRESSURES.
 SPECIFY LIMITATIONS. SUBMIT CALULATIONS.
 SUBMIT SPECIFICATIONS FOR THE GE 1200
 SILICONE.
  
 10) SUBMIT STATE PRODUCT APPROVAL FOR
 THE COLLIER GARAGE DOOR WITH APPROVED
 STATUS AND FOR THE SMALL 8'X 7' GARAGE
 DOOR WHICH IS SMALLER THAN THE MINIMUM
 SIZE STATED ON THE PRODUCT APPROVAL
 DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-23 Cont ID  
Sent By jleahy Date 2004-03-23 Time 09:51 Rev Time 0.45
Received By jleahy Date 2004-03-20 Time 09:51 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 14:35 Sent To B
Notes
2004-05-03 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 12:19 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 12:19 Sent To P
Notes
2004-04-20 00:00:00TO KS BOX/JL REVIEWER/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-14 Cont ID  
Sent By mmclean Date 2004-04-14 Time 09:19 Rev Time 0.00
Received By rmcdouga Date 2004-03-12 Time 10:45 Sent To  
Notes
2004-03-16 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-23 Cont ID  
Sent By jleahy Date 2004-03-23 Time 09:52 Rev Time 0.25
Received By hmoser Date 2004-03-23 Time 17:02 Sent To P
Notes
2004-03-23 00:00:00PASS/PRIVISO
 NEED 14IN. RETURN AIR IN MASTER.PER
 SECTION 601.4 F.B.C.(M) 2001
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-22 Cont ID  
Sent By kstevens Date 2004-04-22 Time 16:58 Rev Time 0.33
Received By kstevens Date 2004-04-22 Time 16:58 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-31 Cont ID  
Sent By csiegber Date 2004-04-20 Time 12:19 Rev Time 0.25
Received By jleech Date 2004-03-31 Time 19:14 Sent To B
Notes
2004-03-31 00:00:00DENIED;
 RISER DIAGRAM DOESNOT MATCH FLOOR PLAN.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-12 Cont ID  
Sent By csiegber Date 2004-03-12 Time 10:45 Rev Time 0.00
Received By mmclean Date 2004-03-12 Time 15:34 Sent To I
Notes
***NONE***