| 2004-04-15 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE TOTAL SQUARE FEET OF A/C AREA ON |
| | THE PLANS IS INCORRECT ON SHEET 3. |
| | PLEASE CORRECT. |
| | |
| | 3) THE FLORIDA PRODUCT APPROVAL NUMBERS |
| | LISTED FOR TWO OF THE FIXED GLASS |
| | WINDOWS IN THE SCHEDULE ON SHEET 3 ARE |
| | INCORRECT. |
| | |
| | 4) PLEASE CLARIFY THE TP4X CONNECTOR |
| | SPECIFIED ON SHEET 2 FOR THE 3-2X4 POST |
| | IN THE WALL BELOW THE GIRDER TRUSS AT |
| | THE MASTER SUITE. |
| | |
| | 5) SPECIFY THE ATTIC LIVE LOAD ON THE |
| | PLANS. SEE FBC TABLE 1604.1. |
| | |
| | 6) SPECIFY ON THE PLANS THAT THE DOOR |
| | FROM THE GARAGE TO THE CONDITIONED SPACE |
| | IS REQUIRED TO BE SOLID CORE OR |
| | INSULATED PER FBC 13-603. |
| | |
| | 7) THE TRUSS ANCHOR SCHEDULE ON SHEET 9 |
| | LISTS A NU-VUE NVSTA 48 CONNECTOR. THE |
| | STATE PRODUCT APPROVAL SUBMITTED IS FOR |
| | A NVRT 48 CONNECTOR. PLEASE CLARIFY. |
| | |
| | 8) THE TRUSS CONNECTOR SCHEDULE LISTS A |
| | SIMPSON HUC 412 CONNECTOR AND THE STATE |
| | PRODUCT APPROVAL SUBMITTED IS FOR A |
| | HU 412. PLEASE CLARIFY. |
| | |
| | 9) SUBMIT STATE PRODUCT APPROVAL WITH |
| | APPROVED STATUS FOR THE COLLIER GARAGE |
| | DOOR AND FOR THE 8'X7' GARAGE DOOR, |
| | WHICH IS SMALLER THAN THE MINIMUM |
| | ALLOWED BY THE PROD. APP. DRAWING. |
| | |
| | 10) THE SUBMITTAL FOR THE BUTT GLASS |
| | WINDOW IS INCOMPLETE AND HAS ERRORS. |
| | THE THIRD PARTY QUALITY ASSURANCE IS |
| | REQUIRED. THE DIMENSIONS OF THE PANELS |
| | NEED TO MATCH THE ARCHITECTURAL PLANS. |
| | THE LOT NUMBER ON SHEET 1 OF 2 IS WRONG. |
| | THE DESIGN PRESSURES ARE NOT GIVEN. |
| | SUBMIT THE CALCULATIONS. SUBMIT THE |
| | SPECIFICATIONS FOR THE GE 1200 SILICONE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |