Plan Review Details - Permit 04030555
Plan Review Stops For Permit 04030555
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-19 Cont ID  
Sent By jwitmer Date 2004-05-19 Time 16:00 Rev Time 3.33
Received By jwitmer Date 2004-05-19 Time 16:00 Sent To  
Notes
2004-05-19 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 04030555
 ADDRESS: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK
 TELL # (954)444-2995
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
  
 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-19 Time 12:52 Rev Time 2.00
Received By jwitmer Date 2004-05-12 Time 14:12 Sent To  
Notes
2004-05-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030555
 ADD: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK/ JOSH
 TEL: (954)444-2995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SOILS REPORT (3) RAISED SEAL/ SIGNATURE
  
 2) RESIDENET INSPECTOR CONTRACT TO
 HAROLD PISKURA
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-14 Cont ID  
Sent By jwitmer Date 2004-04-14 Time 14:50 Rev Time 3.50
Received By jwitmer Date 2004-04-14 Time 14:50 Sent To PC
Notes
2004-04-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030555
 ADD: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK
 TEL: (954)444-2995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 FOUNDATION
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.PROVIDE REPORT DATED JULY 16,
 2003.
  
 3) S0.1 SITEWORK NOTE # 7, CORRECT, THAT
 THE SIDES OF FOOTINGS MAY BE EARTH
 FORMED. 1804.1.1 LOCAL AMENDMENT, ALL
 FOOTINGS AND CONCRETE PADS SHALL BE
 FORMED FULL DEPTH.
  
 4) S0.1 COMPONENTS AND CLADDING TABLE,
 A) END ZONES ARE TO BE AS PER 1606.2.3
 10% OF THE LEAST HORIZONTAL DIMENSION OR
 40% OF THE EAVE HEIGHT. 80'X10%= 8'-0"
 OR 19'X40%=7.5'. USE WHICHEVER IS LESS.
  
 5) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO:
 X- BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 X- BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SEE PLUMBING COMMENTS IN REGAURDS TO
 CERTIFICATE OF AUTHORIZATION, PRACTICING
 UNDER A FICTITIOUS NAME.
  
 8) 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-19 Cont ID  
Sent By dpalmer Date 2004-05-19 Time 15:59 Rev Time 1.00
Received By dpalmer Date 2004-05-19 Time 15:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 18:56 Rev Time 0.26
Received By dpalmer Date 2004-04-28 Time 18:56 Sent To  
Notes
2004-04-28 00:00:00*** UNSAT **
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 LEGAL SIGNATURE. IF WHAT IS SHOWN IS
 SIGNATURE PER FS 471.025, PLEASE PROVIDE
 COPY OF LICENSE/DRIVER'S LICENSE.
 ANY PERSONEL INFORMATION MAY BE CROSSED
 OUT AS THIS WILL GO IN FILE.
  
 2)NOTE: PLEASE REMOVE ALL OLD /VOIDED
 SHEETS FROM SETS. ONLY LEAVE IN SHEETS
 FOR INSTALLATION OF FOUNDATION CONDUITS
 ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-13 Cont ID  
Sent By dpalmer Date 2004-04-13 Time 18:28 Rev Time 0.50
Received By dpalmer Date 2004-04-13 Time 18:28 Sent To  
Notes
2004-04-13 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE PROVIDE INFORMATION FOR
 WORK GOING INTO FOUNDATION ONLY.
 PERMIT APPLIED FOR IS FOUNDATION.
  
 2)NOTE: PLEASE SEE PLUMB PLAN REVIEW
 NOTES AS THEY PERTAIN TO REQ'D FULL
 SIGNATURE FOR ENGINEER OF RECORD.
 FS 471.025.
 PLEASE ALSO SEE FS 471.023 FOR REQ'D
 CERT OF AUTH # ALSO REQ'D ON TITLE BLOCK
 PLEASE SEE FAC 61G15-23.002 FOR ALL
 INFORMATION REQ'D ON TITLE BLOCK
  
 PLEASE SUBMIT A LAYOUT FOR ELECT SLAB?
 CONDUIT SIZES, GROUNDING ELECTRODE ETC.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-04-15 Cont ID  
Sent By mamini Date 2004-04-15 Time 10:40 Rev Time 0.50
Received By mamini Date 2004-04-15 Time 10:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2004-04-30 Cont ID  
Sent By mcarsill Date 2004-04-30 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2004-04-30 Time 14:49 Sent To  
Notes
2004-04-30 00:00:001) PLANS NOT REVIEWED FOR FIRE CODE
 COMPLIANCE. FOUNDATION PERMIT ONLY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-05-19 Time 12:52 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 12:52 Sent To B
Notes
2004-05-19 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:56 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 15:56 Sent To  
Notes
2004-04-28 00:00:00TO COMM BD#43

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-15 Cont ID  
Sent By mmclean Date 2004-03-11 Time 14:38 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 11:38 Sent To  
Notes
2004-03-11 00:00:00TO COMM BD#34/TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-05-07 Cont ID  
Sent By pkrauss Date 2004-05-07 Time 09:32 Rev Time 0.10
Received By pkrauss Date 2004-05-07 Time 09:32 Sent To  
Notes
2004-05-07 00:00:00PERMIT IS FOR FOUNDATION ONLY -
 MECHANICAL PLAN REVIEW UNDER PERMIT
 04030554.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-10 Cont ID  
Sent By pkrauss Date 2004-04-07 Time 14:53 Rev Time 3.00
Received By pkrauss Date 2004-04-07 Time 06:42 Sent To  
Notes
2004-04-07 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES CO SENSORS
 CONTROLLING THE EXHAUST FANS.IS IT THE
 INTENT THAT THE EXHAUST FANS WILL NOT
 RUN CONTINUOUSLY?
  
 2.INDICATE AT WHAT LEVEL (PPM) THE
 CO SENSORS ARE SET TO ACTIVATE THE
 EXHAUST FANS.
  
 3.PLEASE CLARIFY RETURN AIR TO THE
 RTU.WILL THESE UNITS BE CONTROLLED BY
 A THERMOSTAT OR HUMIDISTAT?
  
 4.PLEASE NOTE PER 2002 NFPA 90A
 4.3.7.1, AIR SHALL NOT BE RECIRCULATED
 FROM ANY SPACE IN WHICH FLAMMABLE VAPORS
 OR DUST ARE PRESENT IN QUANTITIES OR
 CONCENTRATIONS THAT WOULD INTRODUCE A
 HAZARDOUS CONDITION INTO THE RETURN AIR
 SYSTEM.THIS IS ALSO ADDRESSED IN
 2001 FBC(M) 502.1.
  
 6.SEE COMMMENT #3 FROM K. STEVENS
 (PLUMBING).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-12 Cont ID  
Sent By kstevens Date 2004-05-12 Time 16:11 Rev Time 1.25
Received By kstevens Date 2004-05-12 Time 16:11 Sent To  
Notes
2004-05-12 00:00:00FOUNDATION PLUMBING ONLY THIS PERMIT

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By kstevens Date 2004-03-23 Time 08:33 Rev Time 0.50
Received By kstevens Date 2004-03-22 Time 18:45 Sent To  
Notes
2004-03-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES.
  
 1) FOUNDATION ONLY. NO PLUMBING TO BE
 INSTALLED THIS PERMIT.
 2) 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
 3)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - INITIALS ARE NOT ACCEPTABLE
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-11 Cont ID  
Sent By mmclean Date 2004-03-11 Time 14:38 Rev Time 0.00
Received By mmclean Date 2004-03-11 Time 14:38 Sent To I
Notes
2004-03-11 00:00:00APPROVED BY JOSH LONG, PLANNER 659-8031