Plan Review Details - Permit 04030554
Plan Review Stops For Permit 04030554
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-20 Cont ID  
Sent By jwitmer Date 2005-03-20 Time 09:01 Rev Time 0.50
Received By jwitmer Date 2005-03-20 Time 09:01 Sent To  
Notes
2005-03-20 00:00:00REVISIONS-

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 11:11 Rev Time 2.25
Received By jwitmer Date 2004-06-25 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-26 Cont ID  
Sent By jwitmer Date 2004-05-26 Time 15:11 Rev Time 5.50
Received By jwitmer Date 2004-05-26 Time 15:09 Sent To  
Notes
2004-05-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030554
 ADD: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK
 TEL: (561)444-2995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THIS BUILDING REQUIRES A SPECIAL
 INSPECTOR, ALL SUBMITTALS,PLANS AND
 "PRODUCT APPROVALS" REQUIRE (3) COPIES.
  
 2) PROJECTS THAT HAVE A PERMIT APPLICA-
 TION DATE AA OF OCT.1, 2003 REQUIRE
 STATEWIDE APPROVAL, THE MIAMI DADE
 REPORT SUBMITTED "RUSKIN MANUFACTURING"
 FOR EXTERIOR LOUVERS HASN,T SUBMITTED
 FOR THIS APPROVAL REQUIRING LOCAL PRO-
 DUCT APPROVAL. THE LOCAL PRODUCT APPROV-
 AL FORM IS ATTACHED TO THE NOA AND IS TO
 BE FILLED OUT BY THE MANUFACTURER.
 NOTE:
 3) THE VARIOUS MANUACTURED CANOPIES WILL
 REQUIRE A SEPERATE PERMIT REVIEWS AND
 ASSOCIATED FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-15 Cont ID  
Sent By jwitmer Date 2004-04-15 Time 07:40 Rev Time 4.00
Received By jwitmer Date 2004-04-15 Time 07:40 Sent To  
Notes
2004-04-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030554
 ADD: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK
 TEL: (561)444-2995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COMMENTS FROM THE FOUNDATION PERMIT
 (04030555) 1-8.
 2) PLANS INDICATE VARIOUS PRE-ENGINEERED
 CANOPIES, PROVIDE INFORMATION ON THESE
 CANOPIES TO BE CONSIDERED UNDER THIS
 PERMIT. NOTE ON THE FOUNDATION PAGE ,
 FOUNDATION SUBJECT TO CHANGE PENDING THE
 REVIEW. IF ENGINEER TO CHANGE CANOPY
 FOUNDATION, WOULD IT NOT MAKE SENSE TO
 HAVE THIS INFORMATION BEFORE HAND?
 3) PLANS INDICATE A CANOPY ENCLOSED BY
 A FENCE. SHEET BA-1.2 INDICATES A
 300 GAL POLY TANK AND (6) 500 GAL TANKS.
 WHAT TYPE OF LIQUIDS ARE TO BE HOUSED IN
 THESE TANKS? IS THIS A HAZARDOUS OCCUPAN
 CY? DOES THIS AREA REQUIRE A SECONDARY
 CONTAINMENT? THIS AREA TO BE FIRE SPRINK
 LERED? AGAIN NO PLANS SUBMITTED FOR
 CANOPY OR AWNING?
 4) SHEET# S1.0 NOTE# 8, PRECAST COLUMNS
 ARE TO BE FASTENED TO THE FOUNDATION?
 HOW WILL THIS HAPPEN, THIS INFORMATION
 WILL ALSO BE NEEDED FOR THE FOUNDATION
 PERMIT. WILL THERE BE EMBEDS, ETC?
 LOCATIONS?
 5) SHEET S1.1 DETAIL# 3, PLANS INDICATE
 A BEAM AT THE C-1 COLUMN AND SPANING
 INTO THE PRECAST COLUMNS, HOW WILL THIS
 OCCUR? WILL THE CENTER OF THE PRECAST
 COLUMN BE VOID FOR THIS BEAM?
 6) THIS SAME SHEET DOES NOT INFORMATION
 AS TO WHAT TYPE OF BEAM TO BE USED AT
 THE WINDOWS OF THE LOUNGE, SHOP FOREMANS
 WINDOW, HALL OR OTHER OPENINGS IN THE
 BLOCK WALLS?IN SOME CASES THESE OPENINGS
 WILL ABUT AGAINST PRECAST COLUMNS? THE
 EAST WALL WHERE THE LOUVER IS LOCATED
 NO MENTION OF HOW TO HANDLE THIS, OR
 HEIGHT OF OPENING?
 7) SHEET S.0 DETAIL# 7, HOW DOES THE
 VERTICAL BARS ATTACH TO THE SPANDREL
 BEAM?
 8) SHEET M-2 LOUVER EAST WALL WITHIN
 15'-0" OF THE PROPERTY LINE, REQUIRES
 OPENING PROTECTIVES, 705.1.1.2.
 9) INDICATE HOW THE RTU ARE TO BE FASTEN
 ED TO THE ROOF DECK?
 10)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) SWING DOORS
 C) OVERHEAD DOORS
 D) EXTERIOR LOUVERS
 E) ROOFING ASSEMBLIES
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-10 Cont ID  
Sent By dpalmer Date 2005-03-10 Time 12:50 Rev Time 0.30
Received By dpalmer Date 2005-03-10 Time 12:42 Sent To  
Notes
2005-03-10 00:00:00REVIEWED FOR ELECTRICAL,
 FIRE TO REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-12 Cont ID  
Sent By dpalmer Date 2004-05-12 Time 07:38 Rev Time 2.00
Received By dpalmer Date 2004-05-11 Time 16:41 Sent To  
Notes
2004-05-12 00:00:00STAMPED TWO ELEC SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-14 Cont ID  
Sent By dpalmer Date 2004-04-14 Time 15:46 Rev Time 3.00
Received By dpalmer Date 2004-04-14 Time 15:45 Sent To  
Notes
2004-04-14 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SIGN PLANS WITH COMPLETE
 SIGNATURE AS REQ'D UNDER FS 471.025,
 FAC 61G15-23.002
 PLEASE ALSO INCLUDE ALL LICENSE #'S ON
 TITLE BLOCK AS REQ'D UNDER FAC 61G15-23.
 002. FS 471.023 (CA#) DATE ALSO MUST BE
 SIGNED AS ORIG. THESE ITEMS HAVE BEEN
 SENT TO US FROM THE FBPE'S IN OTHER
 CASES AND WILL EFFECT ALL PLANS.
  
 2)NOTE: PLEASE INCLUDE EQUIPMENT GROUND-
 ING CONDUCTORS FOR ALL PANELS.250.122,
 250.110,,,
  
 3)NOTE: PLEASE SEE NOTE #1 E-6, MENTIONS
 4-3 1/2" CONDUITS, YET SB PANEL SHOWS
 4" CONDUITS, PLEASE CORRELATE.
  
 4)NOTE: PLEASE LABEL AND IDENTIFY ALL
 PANELS/EQUIPMENT ON PLANS.
 PANELS SBF AND SBR.
 PLEASE SEE NOTE:4 ON E-2, MENTION 80A
 PANEL TO BE INSTALLED FOR TELE BOARD.
 THIS COULD NOT BE LOCATED ON RISER DIA-
 -GRAM OR ON A PANEL FEEDING THIS 80A
 SUB-PANEL?
 THERE IS A "PANEL TC" LOCATED ONPANEL-
 -BOARD SB, BUT IS ONLY A 60A FEED.
 IS THIS PANEL ANOTHER PANEL OR SAME?
 PLEASE CORRELATE RISER, PANEL SCHEDULES,
 SIZE ETC.
  
 5)NOTE: PLEASE SEE ELECTRIC RISER KEY-
 -NOTES, #3, MENTIONS BOTH SB, SBM TO BE
 "MAIN LUGS ONLY". PLEASE ADJUST NOTE.
 PLEASE ALSO CORRELATE AIC RATINGS INDI-
 -CATED. SBM IS SHOWN AS 10,000. SB AND
 NOTES MENTIONS, 22K.
  
 6)NOTE: PLEASE SEE 700.12E FOR CIRCUIT--
 -ING OF EM/EXT LTS. TO BE ON WITH LOCAL
 BRANCH CIRCUITS.
  
 7)NOTE: PLEASE SEE THAT ALL CIRCUITING
 WILL BE REQ'D TO BE ON PLANS AND CORRE-
 -LATE WITH SUBMITTED PANEL SCHEDULE(S).
 IF PERTAING TO ONLY GFI'S IN BAYS,
 PLEASE CALL TO DICUSS A POSSIBLE NOTE/
 PROVISO. THIS MAY RESULT IN A FUTURE
 REVISION AND FEES DUE AT THAT TIME.
 IF THIS NOT AN OPTION, PLEASE ADDRESS
 AS NOTED.
  
 8)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON ELECTRICAL PLANS.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2005-03-08 Cont ID  
Sent By mamini Date 2005-03-08 Time 14:47 Rev Time 0.50
Received By mamini Date 2005-03-08 Time 14:47 Sent To  
Notes
2005-03-08 00:00:00PASSED:
  
 1. REVISION AS SUBMITTED REVIEWED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-08-12 Cont ID  
Sent By mamini Date 2004-08-12 Time 10:31 Rev Time 0.50
Received By mamini Date 2004-08-12 Time 10:30 Sent To  
Notes
2004-08-12 00:00:00PASSED:
 1. SEE PERMIT # 04060907 FOR UNDERGROUND
 UTILITIES AND SITE WORK FOR THIS
 ADDITION.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-04-15 Cont ID  
Sent By mamini Date 2004-04-15 Time 09:49 Rev Time 1.00
Received By mamini Date 2004-04-15 Time 09:49 Sent To  
Notes
2004-04-15 00:00:00PASSED WITH PROVISOS:
 1. PLEASE CONTACT MR. RODNEY COMPO AT
 837-4051 EXT. 4074 FOR OIL / WATER
 SEPARATOR REQUIREMENTS IN SEWER LINE
 PRIOR TO CONNECTING TO CITY LINE.
 2. PLEASE INFORM FDOT AT 432-4966 AND
 CITY ENGINEER' OFFICE AT 659-8040 PRIOR
 TO ANY WORK WITHIN PUBLIC R.O.W.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-03-31 Cont ID  
Sent By mwennerg Date 2005-03-31 Time 10:24 Rev Time 0.00
Received By mwennerg Date 2005-03-31 Time 10:24 Sent To  
Notes
2005-03-31 00:00:001) ALL COMMENTS FROM THE ORIGINAL REVIEW
 WERE INCLUDED WITH THE FIRE ALARM
 DRAWINGS, 04090486 WHICH WERE PASSED BY
 N MCCRAY ON 1/26/05.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2004-12-08 Cont ID  
Sent By nmccray Date 2004-12-08 Time 11:12 Rev Time 0.00
Received By nmccray Date 2004-12-08 Time 11:12 Sent To  
Notes
2004-12-08 00:00:001) WHEN THE FIRE ALARM CONTROL UNIT,
 INCLUDING THE DAILER-COMMUNICATOR, IS
 REPLACED IN AN EXISTING SYSTEM, IT WILL
 BE TREATED AS A NEW SYSTEM.
  
 2) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 3) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR
 TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSSABLE.
  
 5) THE WEST PALM BEACH FIRE MARSHAL
 OFFICE REQUIRES SMOKE DUCT DETECTORS TO
 SEND A GENERAL FIRE ALARM NOT A
 SUPERVISORY.
  
 6) PLEASE PROVIDE CUT SHEETS FOR ALL NEW
 DEVICES AND EQUIPMENTS.
  
 7) ALL THESE CHANGES SHOULD BE
 SUBMITTED
 UNDER PERMIT 04090486 (FIRE ALARM
 PERMIT).
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-06-30 Cont ID  
Sent By nmccray Date 2004-06-30 Time 14:11 Rev Time 0.00
Received By nmccray Date 2004-06-30 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2004-07-20 Cont ID  
Sent By mcarsill Date 2004-05-19 Time 10:33 Rev Time 0.00
Received By lmartine Date 2004-05-19 Time 10:33 Sent To  
Notes
2004-05-19 00:00:001) ELECTRONIC SWITCHES, CHAINS AND LOCKS
 WILL BE REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 2) PLEASE DISPLAY EXIT ROUTE(S) FOR
 VEHICLE LIFTS 1-6.
  
 3) PLEASE INDICATE TESTING CRITERION
 FOR CO VENTILATION SYSTEM.
  
 4) THE NOTE ON PAGE M-4 INDICATES
 SMOKE BOMBS WILL BE USED TO TEST
 CARBON MONOXIDE SYSTEM. THESE NOTES
 DO NOTINDICATE HOW THE MONITORS
 THEMSELVES WILL BE TESTED. IT WOULD
 APPEAR THAT CALIBRATION GAS SHOULD BE
 USED TO ENSURE SET POINTS ON THE
 DETECTORS ARE PROPER. PLEASE ADVISE.
  
 5) WHY IS THE STORAGE YARD NOT FIRE
 SPRINKLER PROTECTED. IS THERE NOT
 MATERIALS STORED THERE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-12 Cont ID  
Sent By mcarsill Date 2004-03-12 Time 17:58 Rev Time 0.00
Received By mcarsill Date 2004-03-12 Time 17:58 Sent To  
Notes
2004-03-12 00:00:001) PLEASE EXPLAIN ACCESS FOR NEW
 SERVICE SHOP. VARIOUS GATES AND FENCES
 ARE PRESENT ON THE SITE.
  
 2) ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 3) FIRE AND PARAMEDICAL ACCESS TO THE
 SITE SHALL BE PROVIDED DURING
 DEMOLITION AND CONSTRUCTION ACTIVITIES.
  
 4) PLEASE PROVIDE MORE DETAILS ON
 PROPOSED STORAGE.
  
 5) PLEASE PROVIDE FURTHER DETAILS ON
 300 GAL POLY TANK.
  
 6) WHAT OPENING PROTECTIVE DEVICE IS
 PLANNED BETWEEN HALL 103 AND SERVICE
 SHOP 112.
  
 7) THERE APPEARS TO BE TOO MANY
 TABLES AND CHAIRS SHOWN IN LOUNGE 111.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 9) PLEASE EXPLAIN EXITING RATIONALE
 FROM OTHER AREAS BESIDES SERVICE SHOP.
 IT APPEARS THAT EXITING HAS TO ENTER
 VIA THE SERVICE SHOP.
  
 10) ADDITONAL EXIT SIGNS APPEAR TO BE
 NEEDED.
  
 11) ARE THERE ANY EMERGENCY LIGHTS
 PRESENT.
  
 12) ARE FIRE RESCUE VEHICLES EXPECTED
 TO PASS UNDERNEATH THE NEW METAL
 CANOPY.
  
 13) BUILDING ADDRESS REQUIRED. A
 MINIMUM OF 6" HIGH NUMBERS.
  
 14) DOOR SCHEDULE INDICATES NO LABEL
 DOORS.
  
 15) MORE DETAILS REQUIRED ON CARBON
 MONOXIDE EVACUATION SYSTEM THAT IS
 PLANNED FOR USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 13:03 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 13:03 Sent To  
Notes
2005-03-08 00:00:00TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 8 Status P Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 14:00 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 14:00 Sent To ENG
Notes
2005-01-14 00:00:00TO "ENG" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-22 Cont ID  
Sent By mjacobs Date 2004-11-22 Time 11:46 Rev Time 0.00
Received By mjacobs Date 2004-11-22 Time 11:46 Sent To FIRE
Notes
2004-11-22 00:00:00SENT TO "FIRRE" BOX/RREVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 10:52 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 10:52 Sent To M
Notes
2004-10-25 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-09-22 Time 12:53 Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 12:53 Sent To M
Notes
2004-09-22 00:00:00TO PK DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-06 Time 11:56 Rev Time 0.00
Received By csiegber Date 2004-07-06 Time 11:56 Sent To  
Notes
2004-07-06 00:00:00TO COMM BD#43/P&M

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-06-10 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-06-10 Time 15:43 Sent To  
Notes
2004-06-10 00:00:00TO COMM BD#38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-10 Cont ID  
Sent By csiegber Date 2004-06-10 Time 15:42 Rev Time 0.00
Received By csiegber Date 2004-05-10 Time 11:25 Sent To  
Notes
2004-05-10 00:00:00TO COMM BD#22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-05-07 Time 08:43 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 13:23 Sent To  
Notes
2004-03-11 00:00:00TO COMM BD#2/TO Z

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2004-11-05 Cont ID  
Sent By pkrauss Date 2004-11-05 Time 15:21 Rev Time 0.40
Received By pkrauss Date 2004-11-05 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-25 Time 10:52 Rev Time 0.55
Received By pkrauss Date 2004-10-05 Time 17:53 Sent To  
Notes
2004-10-06 00:00:00PROVISO:
 CO SENSORS SHALL ACTIVATE FANS UPON
 DETECTION OF A CONSENTRATION RATE OF NOT
 GREATER THAN 25 PPM PER 2001 FBC(M)
 403.3.
  
 CO SENSORS TO BE TESTED FOR FINAL
 INSPECTION.
  
 PVC CONDENSTATE PIPE LOCATED ON THE
 ROOF SHALL HAVE PROTECTION FROM UV RAYS
 PER MANUFACTURER'S SPECIFICATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-09-22 Time 12:53 Rev Time 0.45
Received By pkrauss Date 2004-07-16 Time 07:28 Sent To  
Notes
2004-07-16 00:00:00PROVISO:
 CO SENSORS SHALL ACTIVATE FANS UPON
 DETECTION OF A CONSENTRATION RATE OF NOT
 GREATER THAN 25 PPM PER 2001 FBC(M)
 403.3.
  
 CO SENORS TO BE TESTED FOR FINAL
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-05-28 Cont ID  
Sent By pkrauss Date 2004-05-28 Time 09:00 Rev Time 0.45
Received By pkrauss Date 2004-05-28 Time 09:00 Sent To  
Notes
2004-05-28 00:00:00PROVISO:
 1. PROVIDE SUBMITTAL FOR TESTING OF THE
 CO SENSORS.PLEASE REVISE PLANS AND
 REMOVE COMMENT "CO SENSORS TO BE TESTED
 BY SMOKE BOMBS".REFERENCE MANUFACTURER
 INSTRUCTIONS FOR TESTING.CO SENSORS
 SHALL ACTIVATE FANS UPON DETECTION OF
 A CONSENTRATION RATE OF 25 PPM (MAXIMUM)
 PER 2001 FBC(M) 403.4.
  
 2. PROVIDE MANFACTURERS INSTALLATION
 INSTRUCTIONS FOR THE CONNECTION OF THE
 UNDERFLOOR EXHAUST SYSTEM TO THE 3"
 MUFFLER HOSE. PROVIDE DETAIL ON JOBSITE
 AT THE TIME OF INSPECTION.
  
 3.PLEASE NOTE PLANS FOR THE UNDERFLOOR
 EXHAUST ARE NOT SIGNED, SEALED & DATED
 BY THE ENGINEER AS REQUIRED PER FS
 471.05.PLEASE HAVE THE ENGINEER COMPLY
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-05-07 Cont ID  
Sent By pkrauss Date 2004-05-07 Time 09:34 Rev Time 1.00
Received By pkrauss Date 2004-05-07 Time 09:34 Sent To  
Notes
2004-05-07 00:00:00PLANS SUBMITTED WITH PERMIT 04030555
 DENIED:
 RESPONSE LETTER DATED 4-16-04 TO
 COMMENTS FROM REVIEW DATED 4-7-04:
  
 RESPONSE #2
 CO-SENSORS SETTING DETERMINED BY OWNER.
 PER 2001 FBC(M) 403.4, FANS SHALL
 OPERATE AUTOMATICALLY UPON DETECTION OF
 A CONCENTRATION OF CO OF 25 PPM BY
 APPROVED DETECTION DEVICE.PLEASE
 PROVIDE SUBMITTAL OF THE CO SENSOR.
  
 RESPONSE #4
 WAITING RETURN CALL FROM INSPECTOR
 CLARIFICATION.PLEASE CONTACT CHIEF
 MECHANCIAL INSPECTOR HAROLD MOSER, AT
 (561) 805-6732.THE BEST TIME TO
 CONTACT MR. MOSER IS BETWEEN 7:00 AM -
 8:00 AM OR 3:00 PM - 4:00 PM MONDAY
 THROUGH FRIDAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-10 Cont ID  
Sent By pkrauss Date 2004-04-10 Time 07:17 Rev Time 3.00
Received By pkrauss Date 2004-04-10 Time 07:10 Sent To  
Notes
2004-04-10 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES CO SENSORS
 CONTROLLING THE EXHAUST FANS.IS IT THE
 DESIGN INTENT EXHAUST FANS WILL NOT RUN
 CONTINUOUSLY?
  
 2.INDICATE AT WHAT LEVEL(PPM) THE CO
 SENSORS ARE SET TO ACTIVATE THE EXHAUST
 FANS.
  
 3.PLEASE CLARIFY RETURN AI TO THE
 RTU.WILL THESE UNITS BE CONTROLLED BY
 A THREMOSTAT OR A HUMIDISTAT?
  
 4.PLEASE NOTE PER 2002 NFPA 90A
 4.3.7.1, AIR SHALL NOT BE RECIRCULATED
 FROM ANY SPACE IN WHICH FLAMMABLE VAPORS
 OR DUST ARE PRESENT IN QUANTITIES OR
 CONCENTRATIONS THAT WOULD INTRODUCE A
 HAZARDOUS CONDITION INTO THE RETURN AIR
 SYSTEM.SEE ALSO 2001 FBC(M) 502.1.
  
 5.SEE COMMENT #3 FROM K. STEVENS
 (PLUMBING).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-07-22 Cont ID  
Sent By lmartine Date 2004-07-22 Time 15:14 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2004-07-22 00:00:00 
 CONTR. SUBMITTED PROPER ENGINEERING FOR
 CONDEN. PIPE
  
 L. MARTINEZ

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-07-06 Time 12:15 Rev Time 1.25
Received By kstevens Date 2004-06-22 Time 18:51 Sent To  
Notes
2004-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: NO RESPONSE TO
 COMMENT TO INDICATE HOW PIPE SUPPORTS
 WILL BE ATTACHED TO THE ROOF. SECTION
 104.2.1
 2) FROM PREVIOUS REVIEW: NO RESPONSE TO
 COMMENTS CONCERNING SEAL, SIGNITURE, AND
 DATE REQUIRED ON THE LANDSCAPE, SURVEY,
 CIVIL AND MECHANICAL SHEETS FOR THE
 LIFTS. ALL LANDSCAPE SHEETS ARE NOT SIG-
 NED AND SEALED AND NONE SHOW LICENSE
 NUMBER, CERTIFICATE OF AUTHORIZATION
 NUMBER OR PRINTED NAME OF ARCHITECT.
 - THE SURVEY SHEET IS NOT SIGNED, SEALED
 AND DATED AS REQUIRED IN FS 472.025.
 - THE SEAL FOR THE CIVIL SHEET SHOW NO
 INFORMATION. SEAL SHALL BE IMPRESSION
 TYPE WITH ALL INFORMATION REQUIRED BY
 FLORIDA STATUTES.
 - MECHANICAL SHEETS FOR LIFTS HAVE BEEN
 SIGNED, SEALED, AND DATED AND ARE OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-05-24 Cont ID  
Sent By kstevens Date 2004-05-22 Time 11:24 Rev Time 1.25
Received By kstevens Date 2004-05-22 Time 11:24 Sent To  
Notes
2004-05-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE
 FLORIDA STATUTES
  
 1) SHT R-01 CONDENSATE LINES. INDICATE
 MATERIAL BEING USED FOR CONDENSATE LINES
 RESPONSE NOTED, BUT NO MATERIAL SHOWN.
 INDICATE HOW PIPE SUPPORTS WILL BE ATT-
 ACHED TO ROOF. SUPPORTS TO BE SPACED PER
 TABLE 308.5. SECTION 104.2.1
 2) SHT R-01 IS NOT SIGNED, DATED OR
 SEALED AS REQUIRED IN FAC 61G15-002(1) &
 (2) NOR IS THERE A CERTIFICATE OF AUTHOR
 IZATION AS REQUIRED IN FAC 61G15-002(2)
 & FS 471.025. ENGINEER
 3) IF THE ARCHITECT IS RESPONSIBLE FOR
 SHEET R-01 THEN HE/SHE SHALL SIGN, DATE
 AND SEAL THE PLANS PER FAC61G1-16.003
 AND FS 481.2055
 4) ALL PLANS SUBMITTED FOR PLUBLIC
 RECORED SHALL BE SIGNED, SEALED, AND
 DATED. ALL TITLE BLOCK INFORMATION WITH
 APPROIATE LICENSES, ADDRESS ECT SHALL BE
 ON EACH SHEET. (SEE SHEETS FOR LANDSCAPE
 SURVEY, CIVIL, AND MECHANICAL SHEETS FOR
 THE LIFTS).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-16 Cont ID  
Sent By kstevens Date 2004-03-16 Time 17:22 Rev Time 3.00
Received By kstevens Date 2004-03-16 Time 17:22 Sent To  
Notes
2004-03-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) CONTACT RODNEY COMPO ENVIRONMENTAL
 COMPLIANCE TO DETERMINE IF A SAND-WATER/
 OIL SEPARATOR WILL BE REQUIRED. WASTE
 ORD 2938-96. (561) 837-4074.
 2) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 3) SHT B.A-9.1 SHOWER STALL SHALL BE
 ACCESSIBLE PER SECTION 11-4.21 AND ALL
 SUBSECTIONS. PROVIDE A DETAIL.
 4) SHT R-01 CONDENSATE LINES. INDICATE
 MATERIAL BEING USED FOR CONDENSATE LINES
 IF PVC, SUPPORTS SHALL BE 4' O/C PER
 TABLE 308.5. ALSO PIPE SHALL BE PROTECT-
 ED FROM U.V. RAYS PER MANUF. INSTALLAT-
 ION INSTRUCTIONS.
 5) SHTS P-1 & P-3 INDICATE SLOPE OF PIPE
 FOR STORM SEWERS. MINIMUM 1/4" PER FOOT
 PER TABLE 1106.3. IS STORM LINES ARE
 TIED TOGETHER, SUBMIT A STORM SEWER DIA-
 GRAM INDICATING SEWER PIPE SIZES AND
 SLOPE OF PIPE AND INDICATE TERMINATION
 OF STORM SEWER.
 6) SHT P-6 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE LOCATED AT ALL
 QUICK CLOSING VALVES PER SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF DROPS. PDI-WH 201 AND
 MANUF. INSTALL. INSTRUCTIONS.
 7) SHT P-6 EWH DETAIL. P/T RELIEF VALVE
 SHALL TIE INTO THE TOP 6" OF THE WATER
 HEATER PER SECTION 504.5.1.
 8) CERTIFICATE OF AUTHORIZATION SHALL BE
 INDICATED ON EACH PLUMBING AND ELECTRIC-
 AL SHEET. MECHANICAL SHEETS ARE NOT
 SIGNED AND SEALED.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-03-10 Cont ID  
Sent By mmclean Date 2005-03-10 Time 17:05 Rev Time 0.00
Received By mmclean Date 2005-03-10 Time 17:05 Sent To  
Notes
2005-03-10 00:00:00APPROVED BY JOSH LONG, SENIOR PLANNER
 822-1449

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-11 Cont ID  
Sent By mmclean Date 2004-06-29 Time 10:49 Rev Time 0.00
Received By mmclean Date 2004-03-11 Time 10:49 Sent To  
Notes
2004-06-29 00:00:00APPROVED BY JOSH LONG, PLANNER 659-8031
 LETTER ATTACHED MM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved