Plan Review Details - Permit 04030492
Plan Review Stops For Permit 04030492
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-21 Cont ID  
Sent By jwitmer Date 2004-05-21 Time 14:25 Rev Time 1.22
Received By jwitmer Date 2004-05-21 Time 14:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-09 Cont ID  
Sent By jwitmer Date 2004-04-09 Time 07:33 Rev Time 2.00
Received By jwitmer Date 2004-04-09 Time 07:32 Sent To PC
Notes
2004-04-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030492
 ADD: 10130 NORTHLAKES BLVD# 651
 CONT: OAK CONSTRUCTION
 TEL: (954)610-2774
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE NEW RAMP ON THE N.W. CORNER OF
 THE BUILDING MUST MEET FL ACCESSIBILITY
 REQUIREMENTS:
 A)11-4.8.4.(2) LANDINGS. ALL
 LANDINGSON RAMPS SHALL NOT BE LESS THAN
 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.EQ1 DOESN'T GIVE THE
 REQUIREMENTS FOR THE BOTTOM LANDING,
 NOTDRAWN IN, A-9 SECTION 2 INDICATES TO
 MATCH ASPHALT SURFACE!
 B)11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60". LANDING
 ALREADYEXIST BUT IF IT DOESN'T MEET
 THIS REQUIRMENT IT MUST BE REDESIGNED.
 C)11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 2) LOUNGE ENTRY DOOR 18" PULL SIDE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3) MENS RESTROOM# 116 ENTRY DOOR PULL
 SIDE 18", SEE 11-4.13.6.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-29 Cont ID  
Sent By btrobaug Date 2004-03-29 Time 17:21 Rev Time 1.00
Received By btrobaug Date 2004-03-29 Time 16:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-03-12 Cont ID  
Sent By mcarsill Date 2004-03-12 Time 18:28 Rev Time 0.00
Received By mcarsill Date 2004-03-12 Time 18:28 Sent To  
Notes
2004-03-12 00:00:001) NEW EXTERIOR RAMPS SHALL BE
 PROVIDED WITH HANDRAILS ON BOTH
 SIDES.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR GREASE EXHAUST FAN SHOWN ON M-2.
  
 3) PRODUCT APPROVALS REQUIRED FOR THE
 DUCT WRAP MENTIONED ON M-2.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 11:27 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 11:14 Sent To  
Notes
2004-05-12 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-09 Cont ID  
Sent By jwitmer Date 2004-04-09 Time 07:32 Rev Time 0.00
Received By jwitmer Date 2004-03-11 Time 13:42 Sent To PC
Notes
2004-03-11 00:00:00TO COMM BD#25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-04-02 Cont ID  
Sent By pkrauss Date 2004-04-02 Time 09:24 Rev Time 0.45
Received By pkrauss Date 2004-04-02 Time 09:24 Sent To  
Notes
2004-04-02 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIRED FOR THE
 COOLERS/REFRIGERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-05-28 Cont ID  
Sent By kstevens Date 2004-05-28 Time 13:12 Rev Time 0.33
Received By kstevens Date 2004-05-28 Time 13:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-05-24 Cont ID  
Sent By kstevens Date 2004-05-24 Time 08:58 Rev Time 1.00
Received By kstevens Date 2004-05-22 Time 11:48 Sent To  
Notes
2004-05-24 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-03-22 Time 13:49 Rev Time 1.25
Received By kstevens Date 2004-03-22 Time 13:49 Sent To  
Notes
2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS PB-1, P-1, & P-2 WATER FILTERS
 SHALL COMPLY WITH NSF-42 PER SECTION
 611.1. SUBMIT MANUF. SPECIFICATION SHEET
 SHOWING COMPLIANCE. WATER & GAS PIPING
 GENERAL NOTES "F" STATES "OR EQUAL".
 THIS IS NOT APPROVED.
 2) SHTS P-3 & P-4 SANITARY WASTE PIPING
 KEY NOTES #9 SAFE WASTE NOT APPROVED.
 NO DOUBLE TRAPING PER SECTION 1001.1.
 FLOOR SINK SHALL BE CONNECTED TO VENTED
 LINE IN COMBINATION WASTE & VENT SYSTEM
 SECTION 912.2.2 NOT TO ANOTHER FLOOR
 SINK LINE.
 3) SEPARATE GAS PERMIT REQUIRED.
 4) ALL CAPPED PLUMBING & GAS LINES SHALL
 BE INSPECTED PRIOR TO COVERING.
 5) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - INITIALS ARE NOT ACCEPTABLE
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]