Plan Review Details - Permit 04030451
Plan Review Stops For Permit 04030451
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-09-20 Time 16:10 Rev Time 1.00
Received By lsmith Date 2004-08-02 Time 16:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-08 Cont ID  
Sent By lsmith Date 2004-07-08 Time 15:22 Rev Time 2.00
Received By lsmith Date 2004-07-08 Time 15:22 Sent To  
Notes
2004-07-08 00:00:00PROVISO:
  
 1. CONTACTED ARCHITECT.HE WILL FAX IN
 DETAIL FOR WINDOW & DOOR BUCKS PER JW'S
 COMMENT #9 REVIEWED 04/05/2004. ALL
 OTHER COMMENTS HAVE BEEN ADDRESSED
 EXCEPT IMPACT FEES.THEY ARE STILL
 UNPAID.NO PERMIT CAN BE ISSUED UNTIL
 THE IMPACT FEES ARE PAID & THE PLANS
 STAMPED BY PBC. SUBMIT A COPY OF THE
 PAID RECEIPT.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By jwitmer Date 2004-04-05 Time 11:59 Rev Time 3.00
Received By jwitmer Date 2004-04-05 Time 08:06 Sent To  
Notes
2004-04-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030451
 ADD: 2810 S DIXIE
 CONT: ALEXANDER KING CONST
 TEL: (561)441-2388
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STRUCTURAL COMPONENTS- WOOD CONNECT
 ORS, CONCRETE ANCHORS
 ************IMPORTANT*****************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 MISSING FLORIDA APPROVAL ON VARIOUS
 PRODUCT REPORTS, WILL REQUIRE LOCAL
 APPROVAL, FORM ATTACHED.SEE RULE 9B-72.
  
 2) PLANS CALL FOR HUGHES ANCHORS. HUGHES
 WAS BOUGHT OUT IN 1999. THERE IS NO
 FLORIDA LISTING FOR HUGHES UNDER THE FL
 PRODUCT APPROVAL SYSTEM. SUBMIT ANOTHER
 MANUFACTORER.
  
 3) SHEET A-5 SECTION# 1, INDICATES THE
 USE OF 5/8" CDX PLYWOOD ON THE FRONT
 PORTICO WALL, "FIRE DISTRICT" DOESN'T
 ALLOW TYPE VI CONSTRUCTION(WOOD) ON
 EXTERIOR WALLS, (VERTICAL SURFACES).
 SEE F102.1.
  
 4) THE SAME DETAIL SHOWS A MOLD LOCATED
 AT THE TOP OF THE PARAPET, BUT NO
 MENTION OF WHAT TYPE OF MATERIALS THAT
 ARE TO BE USED? F102.7 ARCHITECTURAL
 TRIM ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT SHALL BE CONSTRUCTED OF APPROV-
 ED NONCOMBUSTIBLE MATERIAL OR FIRE
 ETARDANT TREATED WOOD.
  
 5) ROOFING: F102.4 ROOF COVERINGS IN THE
 FIRE DISTRICT SHALL CONFORM TO THE
 REQUIREMENTS OF A CLASS A OR B ROOF
 COVERINS AS DEFINED IN 1505.
  
 6)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE THE POSITIVE/ NEGATIVE PRESSURES
 AS TO TABLE 1606.2B INTERIOR AND END
 ZONES.
  
 7) 1606.1.5 MAIN WIND-FORCE RESISTNG
 SYSTEM, PROVIDE A ROOF FRAMING PLAN
 INDICATING THE VERTICAL, HORIZONTAL &
 GRAVITY LOADS TO BE RESISTED.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 8) 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 9) PROVIDE A WINDOW AND DOOR BUCK DETAIL
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 10) PROVIDE THE MINIMUM DESIGN TYPE THIS
 BUILDING IS DESIGNED TO TYPE IV OR V?
 SEE TABLE 600 3'-10' REQUIRE:
 TYPE IV1HR
 TYPE V2HR
  
 11) 705.1.1.2. OPENINGS LESS THAN 15'-0"
 REQUIRE OPENING PROTECTIVES, PROVIDE
 45 MINUTE PROTECTIVES FOR REAR DOORS.
  
 12) 1503.4.1 GUTTERS AND LEADERS PLACED
 ON THE OUTSIDE OF BUILDINGS SHALL BE
 NONCOMBUSTIBLE MATERIAL OR A MINIMUM OF
 SCHEDULE 40 PLASTIC PIPE.
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-07-27 Cont ID  
Sent By dpalmer Date 2004-07-27 Time 12:29 Rev Time 0.75
Received By dpalmer Date 2004-07-27 Time 12:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-22 Cont ID  
Sent By dpalmer Date 2004-06-22 Time 21:00 Rev Time 0.33
Received By dpalmer Date 2004-06-22 Time 21:00 Sent To  
Notes
2004-06-22 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE CIRCUITING MISSING
 FOR EM/EXT LTS IN ONE UNIT.
 SEE HIGHLIGHTED SET.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 ARE REQUIRED TO HAVE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS.
  
 3)NOTE: PLEASE CORRELATE A/C SYSTEMS
 WITH MECHANICAL PLANS.
 PLEASE SEE MECH SHEETS SHOW EACH UNIT
 W/ 10KW HEAT AND ELEC SHOWS 5KW.
 PLEASE ADJUST OCP/ AWG AND LOAD CALCS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-26 Cont ID  
Sent By btrobaug Date 2004-03-26 Time 17:38 Rev Time 1.00
Received By btrobaug Date 2004-03-26 Time 17:04 Sent To  
Notes
2004-03-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT, PER 110.9 & 10.
  
 2} PROVIDE PANEL SCHEDULES FOR ALL
 PANELS.
  
 3} INDICATE NUMBER OF PHASES & VOLTAGE
 OF SERVICE.
  
 4} PLEASE USE THE LIGHTING LOAD PER 220.
 3(A). 3.5/SQ.FT, FOR OFFICE BLDG.
  
 5} CALCULATE ALL CONTINUOUS LOADS PER
 215.2(A).
  
 6} NOTE THAT THERE ARE NO DEMAND FACTORS
 FOR COMMERCIAL HEATING EQUIPMENT.
  
 7} RECEPTACLES ARE TO BE CALCULATED PER
 220.3(B)(11), 180VA.
  
 8} INCLUDE CIRCUIT NUMBER AT EQUIPMENT &
 DEVICES ON DRAWINGS.
  
 9} INDICATE COMPLIANCE WITH 700.12(E) ON
 EM. LIGHT CIRCUIT NUMBERS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2004-08-26 Cont ID  
Sent By mamini Date 2004-08-26 Time 09:47 Rev Time 1.00
Received By mamini Date 2004-08-26 Time 09:47 Sent To  
Notes
2004-08-26 00:00:00PASSED:
 1. REVISION

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-08-25 Time 14:08 Rev Time 0.50
Received By mamini Date 2004-07-22 Time 08:52 Sent To  
Notes
2004-07-22 00:00:00PASSED:
 1. POLLUTION/ EROSION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO BEGINNING
 AND MAINTAINED DURING THE PROJECT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2004-06-23 Cont ID  
Sent By mamini Date 2004-06-23 Time 10:56 Rev Time 0.50
Received By mamini Date 2004-06-23 Time 10:56 Sent To  
Notes
2004-06-23 00:00:00FAILED:
 1. PLEASE SHOW ALL THE CONNECTIONS
 TO THE CITY SERVICES INCLUDING SEWER
 LINE AND CLEAN OUTS,
 NOTE THAT THEY MUST BE APPROVED BY THE
 PUBLIC UTILITIES & ENGINEERING FOR THEIR
 LOCATIONS, ETC. ATT: MANNY GONZALEZ ,
 494-1085.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-11 Cont ID  
Sent By mamini Date 2004-03-11 Time 15:24 Rev Time 1.00
Received By mamini Date 2004-03-11 Time 15:23 Sent To  
Notes
2004-03-11 00:00:00FAILED:
 1. PLEASE SHOW CONNECTIONS TO CITY
 SERVICES AND LOCATION OF BACKFLOWS,
 METERS. NOTE THAT THEY MUST BE APPROVED
 BY THE PUBLIC UTILITIES AND ENGINEERING,
 SUBMIT CIVIL PLANS ONLY ATT; MANNY
 GONZALEZ, 659-8040.
 2. ALL PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" STRIPES, PER CITY
 REQUIREMENT.
 3. PLEAES PROVIDE PERVIOUS & IMPERVIOUS
 AREA CALCULATIONS FOR THE TOTAL SITE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By mcarsill Date 2004-06-23 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2004-06-23 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-12 Cont ID  
Sent By mcarsill Date 2004-03-12 Time 07:25 Rev Time 0.00
Received By mcarsill Date 2004-03-12 Time 07:25 Sent To  
Notes
2004-03-12 00:00:001) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF 6" HIGH NUMBERS
 ARE REQUIRED.
  
 2) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 3) THE THREE FOOT OPENING NEAR THE
 PANTRY SHALL BE AT LEAST FORTY FOUR
 INCHES WIDE.
  
 4) BUILDING MIGHT BE LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 MAY APPLY. PLEASE SEE APPENDIX F,
 LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 17:21 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 17:21 Sent To P
Notes
2005-03-03 00:00:00TO KSTEVENS BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 16:10 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 16:10 Sent To B
Notes
2004-09-20 00:00:00TO LS DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 14:08 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 14:08 Sent To ENG
Notes
2004-08-25 00:00:00TO MA BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 14:17 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 14:17 Sent To  
Notes
2004-07-21 00:00:00TO COMM BD#51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-22 Cont ID  
Sent By csiegber Date 2004-06-22 Time 15:44 Rev Time 0.00
Received By csiegber Date 2004-06-22 Time 15:39 Sent To  
Notes
2004-06-22 00:00:00TO COMM BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-05-07 Time 08:38 Rev Time 0.00
Received By csiegber Date 2004-03-09 Time 14:57 Sent To  
Notes
2004-03-09 00:00:00TO COMM BD#18/TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By pkrauss Date 2004-07-12 Time 16:01 Rev Time 0.55
Received By pkrauss Date 2004-07-12 Time 16:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-02 Cont ID  
Sent By pkrauss Date 2004-04-02 Time 07:43 Rev Time 0.55
Received By pkrauss Date 2004-04-02 Time 07:25 Sent To  
Notes
2004-04-02 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL AND LAYOUT.PLEASE NOTE,
 FRESH AIR INTAKES SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM LOADING DOCKS,
 PARKING LOTS, STREETS & ALLEYS.
  
 3.PROVIDE MOUNTING DETAIL FOR THE
 CONDENSING UNITS LOCATED OF THE ROOF.
 PLEASE NOTE HEIGHT REQUIREMENT FOR
 STANDS SHALL COMPLY WITH 2001 FBC 1511.7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-03-09 Cont ID  
Sent By kstevens Date 2005-03-09 Time 11:25 Rev Time 0.50
Received By kstevens Date 2005-03-09 Time 11:25 Sent To  
Notes
2005-03-09 00:00:00 
  
 PASSED/PROVISO
  
 IN THE INSTALLATION OR REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-07-30 Cont ID  
Sent By kstevens Date 2004-07-30 Time 17:38 Rev Time 1.00
Received By kstevens Date 2004-07-30 Time 17:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-10 Cont ID  
Sent By kstevens Date 2004-07-10 Time 05:32 Rev Time 1.50
Received By kstevens Date 2004-07-09 Time 18:50 Sent To  
Notes
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW, SHT A-1 PER
 TABLE 403.1 A DRINKING FOUNTAIN IS REQ-
 UIRED IN EACH SPACE. ALSO SEE SECTION
 410.1. - RESPONSE NOTED, BUT THE DRINK-
 ING FOUNTAIN OR A BOTTLED WATER COOLER
 IS REQUIRED. PLANS SHOW A DRINKING FOUN-
 TAIN ROUGHED IN ON SANT. AND WATER
 RISER DIAGRAMS, BUT (OPT.) WRITTEN IN
 AFTER. PLEASE CLARIFY. EITHER ONE OR THE
 OTHER SHALL BE CALLED OUT ON PLANS.
 SECTION 104.2.1.
 2) FROM PREVIOUS REVIEW, SHT A-1 BREAK
 ROOM SINK SHALL COMPLY WITH SECTION 11-
 4.24 AND ALL SUBSECTIONS. SUBMIT A DE-
 TAIL. RESPONSE NOTED, BUT THE FOLLOWING
 SUBSECTIONS WERE NOT ADDRESSED. SECTION
 11-4.24.3 KNEE CLEARANCE, 11-4.24.4
 DEPTH, 11-4.24.5 CLEAR FLOOR SPACE,
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 PLEASE ADDRESS THESE SECTIONS. SECTION
 104.2.1
 3) FROM PREVIOUS REVIEW, SUBMIT CALCUL-
 ATIONS FOR ROOF DRAINS PER SECTION 1106
 AND ALL SUBSECTIONS. SHOW SQUARE FEET
 FOR ROOF AREA, AND 1/2 AREA OF ALL VERT-
 ICAL WALLS INCLUDING PARAPETS AND ROOF
 AREAS THAT DRAIN ONTO THE ROOF AREA FROM
 ABOVE ADDED TO CALCULATIONS. GUTTERS
 SHALL BE SIZED PER TABLE 1106.6. SHOW
 SLOPE OF GUTTERS AND INDICATE LOCATION
 OF HIGH POINTS AND LOW POINT OF GUTTERS.
 NO RESPONSE WAS NOTED FOR THIS COMMENT.
 4)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025 - PER DBPR INITIALS ARE NOT
 APPROVED.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - FULL SIGNATURE IS REQUIRED
 IF THIS IS YOUR LEGAL SIGNATURE, SUBMIT
 PROOF BY SENDING COPY OF DRIVERS LICENSE
 OR OTHER LEGAL PROOF, PLUS A NOTORIZED,
 SIGNED SEALED LETTER FOR OUR FILES.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-03-22 Time 11:05 Rev Time 1.25
Received By kstevens Date 2004-03-22 Time 11:05 Sent To  
Notes
2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-1 PER TABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED IN EACH SPACE. ALSO
 SEE SECTION 410.1
 2) SHT A-1 BREAK ROOM SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS
 SUBMIT A DETAIL.
 3) AN RPZV BACKFLOW IS REQUIRED ON WATER
 SERVICE TO EACH SPACE. SECTION 608.13.2
 4) SUBMIT CALCULATIONS FOR ROOF DRAINS
 PER SECTION 1106 AND ALL SUBSECTIONS.
 SHOW 1/2 AREA OF ALL VERTICAL WALLS, IN-
 CLUDING PARAPETS AND ROOF AREAS THAT
 DRAIN ONTO ROOF ADDED TO SQUARE FOOTAGE
 OF ROOF AREA. GUTTERS SHALL BE SIZED PER
 TABLE 1106.6. SHOW SLOP OF GUTTERS AND
 INDICATE HIGH POINT AND LOW POINT OF THE
 GUTTERS.
 5) SHT P.1 A WATER RISER DIAGRAM, (ISO-
 METRIC), IS REQUIRED PER SEC 1-4.3.1.1.
 AIR CHAMBERS ARE NOT APPROVED AND IF ANY
 WATER HAMMERS, (REQUIRED ONLY PER SECT-
 ION 604.9), ARE INSTALLED THEY SHALL BE
 LOCATED NEAR THE FIXTURES IN AN "EFFECT-
 IVE RANGE" NOT IN THE CEILING.
 6) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. - SINK IN
 BREAK ROOM SHALL NOT DRAIN THROUGH BATH-
 ROOM WET VENT.
 7) SHT P-1 SHALL BE SIGNED, SEALED AND
 DATED PER SECTION 104.2.2.
 8) ALL SHEETS ARCHITECT SHALL PLACE HIS/
 HER NAME AND LICENSE NUMBER ON EACH
 SHEET, AND A CERTIFICATE OF AUTHORIZAT-
 ION IS REQUIRED PER FS 481.219 AND FAC
 61G1-16.003/G161-16.004
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-03-09 Time 14:57 Rev Time 0.00
Received By lsmith Date 2004-08-02 Time 16:16 Sent To  
Notes
2004-08-02 00:00:00PASSED ZONING BY ES ON 6/18/04 LS SEE
 STAMP ON PLANS
2004-04-05 00:00:00DENIED, NEED TO APPLY FOR A FORMAL
 SITEPLAN REVIEW BEFORE IT CAN BE GO
 THROUGH PLAN REVIEW.CALLED CONTR FILE
 A MM